Water Service Sizer

Building water service and meter sizing per IPC / UPC and AWWA M22

International Plumbing Code 2021

GPM

Irrigation, cooling tower makeup, etc.

PSI
ft
ft

Displacement meters to 2″, compound meters 3″ to 8″ (AWWA M22 Tables 5.6 and 5.7).

Darcy-Weisbach on new, smooth copper. UPC 610.6 asks for aged-pipe friction unless no loss of capacity with age is expected.

Flushometers draw cold water only, so the hot side uses the flush-tank curve (ASPE practice).

Enter fixture counts below, or a continuous load, to see the demand, the service pipe and meter, and the pressure left at the building.

Fixture count
FixtureEach
WSFU
QtyTotal
WSFU
Bathroom group — private, flush tank2.7 cold · 1.5 hot3.6
Bathroom group — private, flushometer valve6 cold · 3 hot8
Bathtub — private1 cold · 1 hot1.4
Bathtub — public3 cold · 3 hot4
Shower head — private, mixing valve1 cold · 1 hot1.4
Shower head — public, mixing valve3 cold · 3 hot4
Bidet — private1.5 cold · 1.5 hot2
Lavatory — private0.5 cold · 0.5 hot0.7
Lavatory — public1.5 cold · 1.5 hot2
Kitchen sink — private1 cold · 1 hot1.4
Kitchen sink — hotel, restaurant3 cold · 3 hot4
Combination fixture — private2.25 cold · 2.25 hot3
Laundry trays (1 to 3) — private1 cold · 1 hot1.4
Service sink — offices, etc.2.25 cold · 2.25 hot3
Dishwashing machine — private0 cold · 1.4 hot1.4
Washing machine (8 lb) — private1 cold · 1 hot1.4
Washing machine (8 lb) — public2.25 cold · 2.25 hot3
Washing machine (15 lb) — public3 cold · 3 hot4
Drinking fountain — offices, etc.Cold only0.25
Urinal — public, 1" flushometer valveCold only10
Urinal — public, ¾" flushometer valveCold only5
Urinal — public, flush tankCold only3
Water closet — private, flushometer valveCold only6
Water closet — private, flush tankCold only2.2
Water closet — public, flushometer valveCold only10
Water closet — public, flush tankCold only5
Water closet — flushometer tankCold only2
Not listed

IPC Table E103.3(2) note a: for fixtures not listed, assume a load by comparing to a listed fixture using water in similar quantities and at similar rates. A 3-compartment sink is commonly compared with a kitchen sink, hotel or restaurant (4.0 WSFU).

Total——

Enter or ↓ moves down · + and − step the count · paste a column from a spreadsheet to fill down

Load values from IPC 2021 Appendix E, Table E103.3(2). Hot and cold values as listed; mains serving both use the total.

MeterTypeSafe maxContinuous
⅝"Displacement (C700)20 GPM10 GPM
¾"Displacement (C700)30 GPM15 GPM
1"Displacement (C700)50 GPM25 GPM
1½"Displacement (C700)100 GPM50 GPM
2"Displacement (C700)160 GPM80 GPM
3"Compound (C702)320 GPM160 GPM
4"Compound (C702)500 GPM250 GPM
6"Compound (C702)1000 GPM500 GPM
8"Compound (C702)1600 GPM800 GPM
2"Turbine, Class II (C701)160 GPM100 GPM
3"Turbine, Class II (C701)350 GPM240 GPM
4"Turbine, Class II (C701)630 GPM420 GPM
6"Turbine, Class II (C701)1400 GPM920 GPM
8"Turbine, Class II (C701)2400 GPM1600 GPM
10"Turbine, Class II (C701)3800 GPM2500 GPM
12"Turbine, Class II (C701)5000 GPM3300 GPM

Sources: AWWA Manual M22, Tables 5.6 (displacement meters, AWWA C700), 5.7 (compound meters, C702) and 5.8 (Class II turbine meters), averages of 1990-model meters. M22 recommends designing to 80% of the maximum capacity. Meter loss at maximum capacity: 15 psi for displacement meters (the C700 limit; M22’s averages are 9.7–11.3 psi), and M22’s averages for compound meters (7.2, 6.2, 8.4 and 14.5 psi at 3″, 4″, 6″ and 8″) and turbine meters (4.0 to 1.7 psi). Actual losses vary by make: use the utility’s or manufacturer’s curve.