Water Service Sizer
Building water service and meter sizing per IPC / UPC and AWWA M22
International Plumbing Code 2021
Irrigation, cooling tower makeup, etc.
Displacement meters to 2″, compound meters 3″ to 8″ (AWWA M22 Tables 5.6 and 5.7).
Darcy-Weisbach on new, smooth copper. UPC 610.6 asks for aged-pipe friction unless no loss of capacity with age is expected.
Flushometers draw cold water only, so the hot side uses the flush-tank curve (ASPE practice).
Enter fixture counts below, or a continuous load, to see the demand, the service pipe and meter, and the pressure left at the building.
IPC Table E103.3(2) note a: for fixtures not listed, assume a load by comparing to a listed fixture using water in similar quantities and at similar rates. A 3-compartment sink is commonly compared with a kitchen sink, hotel or restaurant (4.0 WSFU).
Enter or ↓ moves down · + and − step the count · paste a column from a spreadsheet to fill down
Load values from IPC 2021 Appendix E, Table E103.3(2). Hot and cold values as listed; mains serving both use the total.
Sources: AWWA Manual M22, Tables 5.6 (displacement meters, AWWA C700), 5.7 (compound meters, C702) and 5.8 (Class II turbine meters), averages of 1990-model meters. M22 recommends designing to 80% of the maximum capacity. Meter loss at maximum capacity: 15 psi for displacement meters (the C700 limit; M22’s averages are 9.7–11.3 psi), and M22’s averages for compound meters (7.2, 6.2, 8.4 and 14.5 psi at 3″, 4″, 6″ and 8″) and turbine meters (4.0 to 1.7 psi). Actual losses vary by make: use the utility’s or manufacturer’s curve.