Ventilation Outdoor Air

Room by room: outdoor air, exhaust and demand control, grouped into zones and systems

2025 California Mechanical Code and 2025 Energy Code (Title 24 Part 6) Section 120.1; every room and system takes the greater. Exhaust per Table 120.1-B and demand control per 120.1(d)3.

Design outdoor air 6 rooms · 6 zones · 2 systems
1,080cfm at the intakes570cfm exhaust
Sum of the rooms’ outdoor air1,080 cfm
Governing code by room0 CMC · 3 Title 24
Demand control ventilation requirednone
SystemTypeIntake
cfm
Exhaust
cfm

CMC 403.5.1.3: Ev from occupant diversity; each zone’s primary airflow must be at least 1.5 Voz.

people

Most people in all its zones at once; empty means the sum of the zones (no diversity).

Zone population59 people
Occupant diversity D1.00
Uncorrected intake Vou643 cfm
Ventilation efficiency Ev (simplified)0.75
CMC intake Vot858 cfm
Title 24, sum of the zones’ Vz1,080 cfm
Intake, the greater1,080 cfm
Demand controlnot required on this system

CMC 403.5.1.3: Ev from occupant diversity; each zone’s primary airflow must be at least 1.5 Voz.

people

Most people in all its zones at once; empty means the sum of the zones (no diversity).

Zone population0 people
Occupant diversity D1.00
Uncorrected intake Vou0 cfm
Ventilation efficiency Ev (simplified)0.75
CMC intake Vot0 cfm
Title 24, sum of the zones’ Vz0 cfm
Intake, the greater0 cfm
Demand controlnot required on this system

Each room is figured two ways. CMC: Vbz = Rp·Pz + Ra·Az with Table 402.1 rates, Pz the count entered or the table’s default density rounded up to whole people (403.2.1); Voz = Vbz ÷ Ez with Table 403.2.2 (403.2.3). Title 24 Section 120.1(c)3: Vz is the larger of 15 cfm × Pz or Ra × Az with Table 120.1-A, where Pz is the greater of the count entered and the table’s minimum density (half the CBC egress load). The room’s outdoor air is the greater of the two. Rooms with the same zone name on one system add up into a zone. Systems: single zone and 100% outdoor air add their zones; multiple-zone recirculating Vou = D·Σ(Rp·Pz) + Σ(Ra·Az), D = Ps ÷ ΣPz, Vot = Vou ÷ Ev with Ev = 0.88D + 0.22 below D = 0.60 and 0.75 at or above it (403.5), or by Section 404; the intake is the greater of that and the sum of the Title 24 zone rates. Exhaust: Table 120.1-B and CMC Table 403.7, by area or per fixture, the lower rate for continuous operation. Demand control: Section 120.1(d)3, triggered at 25 people per 1,000 sq ft by the larger of the design density and the CBC Table 1004.5 egress density, with its three exceptions, and only on systems with an economizer, modulating outdoor air or more than 3,000 cfm of outdoor air.

Rooms
No.RoomOccupancyArea
sq ft
People
if known
ZoneSystemOutdoor air
cfm
Exhaust
cfm
DCV
720
Title 24
—No
CMC: 5.0 cfm × 24 people + 0.06 × 4,800 sq ft = 408 = 408 cfm. Title 24: larger of 15 × 24 people or 0.15 × area = 720 cfm. Demand control: no — Below 25 people per 1,000 sq ft. Trigger density 6.7 per 1,000 sq ft (egress at 150 sq ft per occupant). Zp 0.15.
210
Title 24
—Trigger met
CMC: 5.0 cfm × 20 people + 0.06 × 400 sq ft = 124 ÷ Ez 0.80 = 155 cfm. Title 24: larger of 15 × 14 people or 0.15 × area = 210 cfm. Demand control: trigger met — The room is at or above 25 people per 1,000 sq ft, but demand control is only required where the system has an air economizer, modulating outdoor air or more than 3,000 cfm of outdoor air. Trigger density 66.7 per 1,000 sq ft (egress at 15 sq ft per occupant). Zp 0.44.
150
Title 24
90Trigger met
CMC: 5.0 cfm × 15 people + 0.12 × 300 sq ft = 111 = 111 cfm. Title 24 (Breakrooms): larger of 15 × 10 people or 0.15 × area = 150 cfm. Exhaust (Kitchenettes): 0.3 cfm/sq ft × 300 = 90 cfm Assumes a kitchenette; choose None if there is no sink. Demand control: trigger met — The room is at or above 25 people per 1,000 sq ft, but demand control is only required where the system has an air economizer, modulating outdoor air or more than 3,000 cfm of outdoor air. Trigger density 66.7 per 1,000 sq ft (egress at 15 sq ft per occupant). Zp 0.50.
0210—
CMC: 0.0 cfm × 0 people + 0.00 × 180 sq ft = 0 = 0 cfm. Title 24 (—): larger of 15 × 0 people or 0.00 × area = 0 cfm. No outdoor air row: outdoor air by transfer air (Title 24 120.1(c)3 Exception 2). Exhaust (Toilets, public): 70 cfm × 3 water closet or urinals = 210 cfm
0210—
CMC: 0.0 cfm × 0 people + 0.00 × 180 sq ft = 0 = 0 cfm. Title 24 (—): larger of 15 × 0 people or 0.00 × area = 0 cfm. No outdoor air row: outdoor air by transfer air (Title 24 120.1(c)3 Exception 2). Exhaust (Toilets, public): 70 cfm × 3 water closet or urinals = 210 cfm
060—
CMC: 0.0 cfm × 0 people + 0.00 × 60 sq ft = 0 = 0 cfm. Title 24 (—): larger of 15 × 0 people or 0.00 × area = 0 cfm. No outdoor air row: outdoor air by transfer air (Title 24 120.1(c)3 Exception 2). Exhaust (Janitor closets, trash rooms, recycling): 1 cfm/sq ft × 60 = 60 cfm
Total6 rooms5,9201,080570

Rates from CMC Table 402.1, Title 24 Part 6 Tables 120.1-A and 120.1-B, CMC Table 403.7 and CBC Table 1004.5. Health care spaces in OSHPD facilities follow CMC Table 4-A (ASHRAE 170) instead.