Water Heater Sizer

Service water heater recovery and storage by the ASHRAE fixture method, with food service per the Georgia DPH Table K-1 method

°F
°F
Efficiency%
WH-1 100°F rise
39.6gph recovery0.66GPM
79gal storage
41.2MBH input33.0MBH output
Areas
Area 1 · Office buildings · 132 gph × 0.3039.6gph79 gal

Areas combine by heat, so building areas at 140°F and kitchen fixtures at 110°F add correctly: output = Σ gph × 8.33 lb/gal × (basis − inlet); recovery = output ÷ (8.33 × rise); input = output ÷ efficiency.

39.6gph recovery
79 gal storage
Fixtures
FixtureEach
gph
QtyTotal
gph
Basin, private lavatory2
Basin, public lavatory672
Circular wash sink20
Semicircular wash sink10
Foot basin—
Shower30
Bathtub—
Kitchen sink2020
Pantry sink10
Service sink2040
Laundry, stationary tub—
Dishwasher—
Not listed

Hot water demand in gph at 140°F from the manufacturer’s data, or by comparison with a listed fixture of similar use.

Total3 fixture types15132gph

Enter or ↓ moves down · + and − step the count · paste a column from a spreadsheet to fill down

Demand factorStorage capacity factorASHRAE table values for office buildings; enter a value to override.
All heaters
HeaterServingRecoveryStorageInputBooster
WH-1—39.6 gph79 gal41.2 MBH—
ASHRAE hot-water demand per fixture, gph at 140°F
FixtureApartmentsClubsGymnasiumsHospitalsHotelsIndustrial plantsOffice buildingsPrivate residencesSchoolsYMCA
Basin, private lavatory2222222222
Basin, public lavatory46868126—158
Circular wash sink———20203020—30—
Semicircular wash sink———10101510—15—
Foot basin33123312—3312
Shower3015022575752253030225225
Bathtub2020302020——20—30
Kitchen sink1020—20302020102020
Pantry sink510—1010—1051010
Service sink2020—20302020152020
Laundry, stationary tub2028—2828——20—28
Dishwasher1550–150—50–15050–20020–100—1520–10020–100
Hydrotherapeutic shower———400——————
Hubbard bath———600——————
Leg bath———100——————
Arm bath———35——————
Sitz bath———30——————
Continuous-flow bath———165——————
Demand factor0.300.300.400.250.250.400.300.300.400.40
Storage capacity factor1.250.901.000.600.801.002.000.701.001.00

Source: 2023 ASHRAE Handbook — HVAC Applications, Ch. 51 Service Water Heating, Table 13 (p. 51.29); also ASPE Plumbing Engineering Design Handbook Vol. 2, Table 6-1. Demand is never less than the largest single fixture. Storage capacity factor is the ratio of storage tank capacity to probable maximum demand per hour. Dishwasher demand from the table or the manufacturer’s data (note a). Data predates low-flow fixtures.

Food service peak hourly demand, gph (Table K-1)
Handwashing sink (including restrooms)5
Food preparation sink5 per compartment
Hand-operated pre-rinse sprayer45
Mop / utility sink10
Clothes washer15
Shower head14
Hose bibb used for cleaning35
Hose reel10
3-compartment, bar and utensil soak sinksL × W × D × comp. × 0.003255
Warewashing machinefinal rinse gph × 0.70

Source: Georgia DPH Food Service Establishment Manual for Design, Installation and Construction, Section K, Table K-1 (2013; adapted from the FDA Plan Review for Food Establishments). Delivery temperatures from its worked examples: hand sinks 100°F, showers 120°F, other fixtures 110°F, machine supply 140°F. Other jurisdictions may use different tables — confirm with the local health authority. Compartment-sink demand × 0.80 where only single-service tableware is used. Low-flow hand sinks, pre-rinse sprayers and showers: table gph × rated gpm ÷ standard gpm (2.2, 3.5 and 2.5 gpm). Hot-water sanitizing machines need a booster from 140°F to 180°F. Showers use Table K-1’s 14 gph; Section K §2.I lists 35 gph, so confirm which value the reviewer expects.