Water Heater Sizer
Service water heater recovery and storage by the ASHRAE fixture method, with food service per the Georgia DPH Table K-1 method
Areas combine by heat, so building areas at 140°F and kitchen fixtures at 110°F add correctly: output = Σ gph × 8.33 lb/gal × (basis − inlet); recovery = output ÷ (8.33 × rise); input = output ÷ efficiency.
Hot water demand in gph at 140°F from the manufacturer’s data, or by comparison with a listed fixture of similar use.
Enter or ↓ moves down · + and − step the count · paste a column from a spreadsheet to fill down
| Fixture | Apartments | Clubs | Gymnasiums | Hospitals | Hotels | Industrial plants | Office buildings | Private residences | Schools | YMCA |
|---|---|---|---|---|---|---|---|---|---|---|
| Basin, private lavatory | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Basin, public lavatory | 4 | 6 | 8 | 6 | 8 | 12 | 6 | — | 15 | 8 |
| Circular wash sink | — | — | — | 20 | 20 | 30 | 20 | — | 30 | — |
| Semicircular wash sink | — | — | — | 10 | 10 | 15 | 10 | — | 15 | — |
| Foot basin | 3 | 3 | 12 | 3 | 3 | 12 | — | 3 | 3 | 12 |
| Shower | 30 | 150 | 225 | 75 | 75 | 225 | 30 | 30 | 225 | 225 |
| Bathtub | 20 | 20 | 30 | 20 | 20 | — | — | 20 | — | 30 |
| Kitchen sink | 10 | 20 | — | 20 | 30 | 20 | 20 | 10 | 20 | 20 |
| Pantry sink | 5 | 10 | — | 10 | 10 | — | 10 | 5 | 10 | 10 |
| Service sink | 20 | 20 | — | 20 | 30 | 20 | 20 | 15 | 20 | 20 |
| Laundry, stationary tub | 20 | 28 | — | 28 | 28 | — | — | 20 | — | 28 |
| Dishwasher | 15 | 50–150 | — | 50–150 | 50–200 | 20–100 | — | 15 | 20–100 | 20–100 |
| Hydrotherapeutic shower | — | — | — | 400 | — | — | — | — | — | — |
| Hubbard bath | — | — | — | 600 | — | — | — | — | — | — |
| Leg bath | — | — | — | 100 | — | — | — | — | — | — |
| Arm bath | — | — | — | 35 | — | — | — | — | — | — |
| Sitz bath | — | — | — | 30 | — | — | — | — | — | — |
| Continuous-flow bath | — | — | — | 165 | — | — | — | — | — | — |
| Demand factor | 0.30 | 0.30 | 0.40 | 0.25 | 0.25 | 0.40 | 0.30 | 0.30 | 0.40 | 0.40 |
| Storage capacity factor | 1.25 | 0.90 | 1.00 | 0.60 | 0.80 | 1.00 | 2.00 | 0.70 | 1.00 | 1.00 |
Source: 2023 ASHRAE Handbook — HVAC Applications, Ch. 51 Service Water Heating, Table 13 (p. 51.29); also ASPE Plumbing Engineering Design Handbook Vol. 2, Table 6-1. Demand is never less than the largest single fixture. Storage capacity factor is the ratio of storage tank capacity to probable maximum demand per hour. Dishwasher demand from the table or the manufacturer’s data (note a). Data predates low-flow fixtures.
Source: Georgia DPH Food Service Establishment Manual for Design, Installation and Construction, Section K, Table K-1 (2013; adapted from the FDA Plan Review for Food Establishments). Delivery temperatures from its worked examples: hand sinks 100°F, showers 120°F, other fixtures 110°F, machine supply 140°F. Other jurisdictions may use different tables — confirm with the local health authority. Compartment-sink demand × 0.80 where only single-service tableware is used. Low-flow hand sinks, pre-rinse sprayers and showers: table gph × rated gpm ÷ standard gpm (2.2, 3.5 and 2.5 gpm). Hot-water sanitizing machines need a booster from 140°F to 180°F. Showers use Table K-1’s 14 gph; Section K §2.I lists 35 gph, so confirm which value the reviewer expects.