Hydronic Head Loss
Total dynamic head for pump selection · Darcy-Weisbach and K-factors per ASHRAE Fundamentals Ch. 22 and Crane TP-410
Supply 44°F · ρ 62.36 lb/ft³ · ν 1.55e-5 ft²/sReturn 54°F · ρ 62.29 lb/ft³ · ν 1.33e-5 ft²/s
Pump discharge → index circuit → back to pump suction · list every pipe run, fitting, valve and piece of equipment in order, and mark where the return side starts
#ComponentGPMSizeft/sKHeadΣ
Enter the pump flow, then add the pipe, fittings, valves and equipment below in the order the water reaches them. The loop is drawn as you go.
Add to Loop 1
Enter adds · hover between rows to insert · ✎ or click a piece in the drawing to editDarcy-Weisbach with the Colebrook friction factor at the zone’s water temperature. Length as decimal feet (19.75) or feet-inches (19-9).
Pipe: h = f (L/D) V²/2g — Darcy-Weisbach, ASHRAE Handbook—Fundamentals Ch. 22
Friction factor: Colebrook, solved iteratively; laminar 64/Re below Re 2,300
Fittings & valves: h = K V²/2g; ASHRAE Ch. 22 threaded (below 2½"), flanged (2½"–12") and welded (long-radius ells interpolated on velocity, tees, 4" and up) tables; Crane TP-410 K = n·fT outside them and for ball and butterfly valves
Reducers: ASHRAE Ch. 22 welded reducer/expansion data where the size pair is tabulated, referenced to the upstream velocity; other pairs default to K 0.14 — enter the manufacturer’s K
Water properties: density and viscosity at the supply or return temperature; components after the “return side starts” marker use return-side properties
Pipe data: ASME B36.10M Sch. 40 steel · ASTM B88 Type L copper
Equipment: manufacturer pressure drop in ft or psi (psi × 144 / ρ). Static lift counts only for an open system; in a closed loop it cancels.
Butterfly valves default to Crane 45·fT (2"–8"), 35·fT (10"–14"), 25·fT (16"–24") — for manufacturer data use K = 891·d⁴/Cv² (d in inches). Plain water only; glycol solutions need corrected properties.