Health care space ventilation per ANSI/ASHRAE/ASHE Standard 170-2025
Nursing units and other patient care areas
Behavioral and mental health facilities
Diagnostic and treatment
Patient support facilities
General support facilities: sterile processing
Other general support facilities
Support areas for nursing units and other patient care areas
Design airflow to check · cfm, optional
Operating room Table 7-1 · FGI 2.2-3.4.3
2,000cfm supply400cfm outdoor air
6,000 cu ft. 20 total ach, supplied; 4 outdoor ach. Section 7.1(a)(3).
Pressure to adjacent areasPositive
All room air exhausted outdoorsNo requirement
Recirculating room unitsNot permitted
Unoccupied turndownPermitted
Minimum filterMERV-16
Design relative humidity20–60%
Design temperature68–75°F
Table 7-1 notes j, k also apply to this space.
ANSI/ASHRAE/ASHE Standard 170-2025, Inpatient (Table 7-1). Required airflow is the air change rate times the room volume ÷ 60, rounded up to the next cfm. Per Section 7.1(a)(3) the minimum total air changes are supplied for positive-pressure rooms and exhausted for negative-pressure rooms, and negative rooms not required to be exhausted count their supply. The outdoor air portion must meet the filtration of Section 6.4. Where room units are permitted, they may supply the part of the total above the outdoor air changes (7.1(a)(5)). Spaces not listed take the rates of a functionally equivalent space; where Standard 62.1 also prescribes a rate, the higher governs (7.1(a)(2)). Rates above the minimums are often needed to hold the design temperature and humidity. In California, OSHPD 1–5 facilities follow CMC Table 4-A, which is based on Standard 170-2021 with state amendments.
Room schedule
Add rooms from the check above, or bring a whole floor in from Revit with the ASHRAE 170 Room Check button on the MEP Calcs tab.
Minimums per room by ASHRAE 170-2025. Required airflow is supply, or exhaust for negative rooms exhausted outdoors. Outdoor air totals add the room minimums without diversity.