Domestic Water Pipe Sizer

Cold & hot water supply piping per International Plumbing Code 2021

GPM

IPC Table 604.3 · siphonic; blowout 45 psi. Override with the manufacturer’s value if higher.

System losses: meter, backflow preventer and valves from manufacturer data (a reduced-pressure backflow preventer alone is often 10–15 PSI). Developed length is the pipe run to the most demanding fixture; add an allowance for fittings, since only straight pipe friction is calculated.

Darcy-Weisbach on new, smooth copper; about 6–8% below the code friction charts. UPC 610.6 asks for aged-pipe friction unless no loss of capacity with age is expected.

UPC 610.12.1 copper: 8 FPS cold, 5 FPS hot · 4–5 FPS common practice

Enter a flow rate to size the pipe for velocity and the pressure left at the fixture.

FixtureColdHotTotalMin pipeGPM · PSI
Bathroom group — private, flush tank2.71.53.6——
Bathroom group — private, flushometer valve638——
Bathtub — private111.4½"4 · 20
Bathtub — public334½"4 · 20
Shower head — private, mixing valve111.4½"2.5 · 20
Shower head — public, mixing valve334½"2.5 · 20
Bidet — private1.51.52⅜"2 · 20
Lavatory — private0.50.50.7⅜"0.8 · 8
Lavatory — public1.51.52⅜"0.4 · 8
Kitchen sink — private111.4½"1.75 · 8
Kitchen sink — hotel, restaurant334½"—
Combination fixture — private2.252.253½"4 · 8
Laundry trays (1 to 3) — private111.4½"4 · 8
Service sink — offices, etc.2.252.253½"3 · 8
Dishwashing machine — private—1.41.4½"2.75 · 8
Washing machine (8 lb) — private111.4——
Washing machine (8 lb) — public2.252.253——
Washing machine (15 lb) — public334——
Drinking fountain — offices, etc.0.25—0.25⅜"0.75 · 8
Urinal — public, 1" flushometer valve10—10¾"12 · 25
Urinal — public, ¾" flushometer valve5—5¾"12 · 25
Urinal — public, flush tank3—3½"—
Water closet — private, flushometer valve6—61"25 · 35
Water closet — private, flush tank2.2—2.2⅜"3 · 20
Water closet — public, flushometer valve10—101"25 · 35
Water closet — public, flush tank5—5⅜"3 · 20
Water closet — flushometer tank2—2⅜"1.6 · 20

Source: IPC 2021 Appendix E Table E103.3(2) (load values), Table 604.3 (flow rate and flow pressure at the outlet), Table 604.5 (minimum fixture supply pipe). Fixtures not listed: compare with a listed fixture of similar use (note a).

Velocity Guidelines

GuidelineWhyValue
UPC maximum, copper — coldUPC 2024 Section 610.12.18 FPS
UPC maximum, copper — hotUPC 2024 Section 610.12.15 FPS
Common design practiceNoise and erosion control4–5 FPS

IPC 2021 sets no fixed velocity limit in Chapter 6; the UPC limits are a sound benchmark for copper.

Pressure Guidelines

ItemValue
Maximum static pressure in the building (PRV above this)80 PSI
IPC — faucets, lavatories, sinks (Table 604.3)8 PSI
IPC — tank water closet, shower/tub mixing valve20 PSI
IPC — urinal flushometer valve25 PSI
IPC — water closet flushometer valve (siphonic / blowout)35 / 45 PSI
UPC — minimum residual pressure (Section 608.1)15 PSI
Elevation loss0.433 PSI/ft
Reduced-pressure backflow preventer (manufacturer data)often 10–15 PSI

Source: IPC 2021 Table 604.3 and Section 604.8; UPC 2024 Sections 608.1 and 608.2. Meter and backflow losses are typical values — use the manufacturer’s data.