← Back to tools

Domestic Water Pipe Sizer

Size cold & hot water supply piping per IPC / UPC

International Plumbing Code 2021

System losses include meter, backflow preventer, valves — default 10 PSI covers most commercial systems

IPC max 8 FPS

IPC 2021 — Fixture Unit Values (WSFU)

Table E103.3(2)

FixtureWSFUMin PSI
Water Closet (Flushometer Valve)1035
Water Closet (Flush Tank)2.58
Urinal (Flushometer Valve)525
Lavatory (Public)1.58
Lavatory (Private)18
Shower28
Bathtub28
Kitchen Sink1.58
Service Sink38
Washing Machine28
Dishwasher1.58
Drinking Fountain0.58
Hose Bibb2.58

Source: IPC 2021 Appendix E / Table 604.3

Velocity Guidelines

IPC Code Maximum

Hard limit

8 FPS

Recommended

Noise & erosion control

4–5 FPS

Minimum recommended

Avoid stagnation

0.5 FPS

Source: IPC 2021 Section 604.3

Pressure Guidelines

Typical street pressure40–80 PSI
IPC maximum at fixture80 PSI
Elevation loss0.433 PSI/ft
Typical meter loss4–8 PSI
Typical BFP loss5–10 PSI
Min (flush tank)8 PSI
Min (flushometer valve)35 PSI

Source: IPC 2021 Tables 604.3 & 604.4