Domestic Water Pipe Sizer
Cold & hot water supply piping per International Plumbing Code 2021
IPC Table 604.3 · siphonic; blowout 45 psi. Override with the manufacturer’s value if higher.
System losses: meter, backflow preventer and valves from manufacturer data (a reduced-pressure backflow preventer alone is often 10–15 PSI). Developed length is the pipe run to the most demanding fixture; add an allowance for fittings, since only straight pipe friction is calculated.
Darcy-Weisbach on new, smooth copper; about 6–8% below the code friction charts. UPC 610.6 asks for aged-pipe friction unless no loss of capacity with age is expected.
UPC 610.12.1 copper: 8 FPS cold, 5 FPS hot · 4–5 FPS common practice
Enter a flow rate to size the pipe for velocity and the pressure left at the fixture.
Source: IPC 2021 Appendix E Table E103.3(2) (load values), Table 604.3 (flow rate and flow pressure at the outlet), Table 604.5 (minimum fixture supply pipe). Fixtures not listed: compare with a listed fixture of similar use (note a).
Velocity Guidelines
IPC 2021 sets no fixed velocity limit in Chapter 6; the UPC limits are a sound benchmark for copper.
Pressure Guidelines
Source: IPC 2021 Table 604.3 and Section 604.8; UPC 2024 Sections 608.1 and 608.2. Meter and backflow losses are typical values — use the manufacturer’s data.