Expansion Tank Sizer

Hydronic expansion tanks per ASHRAE and water heater thermal expansion tanks per ASPE

gal

Piping, coils, boilers and chillers. Estimate it below the results.

°F

Heating: fill water. Chilled: the supply temperature.

°F

Heating: the supply temperature. Chilled: ambient, such as 95°F.

psig

Enough to hold positive pressure at the highest point: 0.433 psi per foot above the tank, plus a margin.

psig

Below the relief valve setting, allowing for its location.

Minimum tank volume ASHRAE · diaphragm tank
42gal13.8gal acceptance12psig precharge

Choose a tank with at least this total volume and an acceptance volume no less than the expansion, precharged to the fill pressure.

Water from 50°F to 180°F expands3.02%
Less the steel piping’s growth, 3αΔt0.25%
Expansion of 500.0 gal13.83 gal
× P2 / (P2 − P1) at 26.7 and 39.7 psia× 3.05
Minimum tank volume42.2 gal
0.0 gal
Boilers, chillers, coils and tanks (manufacturer’s data)
0.0 gal

Schedule 40 inside diameters.

2020 ASHRAE Handbook — HVAC Systems and Equipment, Chapter 13, Equations (13) to (15): the water’s expansion v2/v1 − 1 less the piping’s 3αΔt (α = 6.5 × 10⁻⁶ in/in·°F for steel, 9.5 × 10⁻⁶ for copper), times the system volume, divided by (Pa/P1 − Pa/P2) for a plain steel tank or (1 − P1/P2) for a diaphragm tank, or doubled for an open tank, with pressures absolute at 14.7 psia atmospheric. Water’s specific volume from Kell’s density equation, which matches ASHRAE Fundamentals Chapter 1 Table 3. Keep every point in the system above the saturation pressure at the operating temperature and give the pumps enough NPSH.