Expansion Tank Sizer
Hydronic expansion tanks per ASHRAE and water heater thermal expansion tanks per ASPE
Piping, coils, boilers and chillers. Estimate it below the results.
Heating: fill water. Chilled: the supply temperature.
Heating: the supply temperature. Chilled: ambient, such as 95°F.
Enough to hold positive pressure at the highest point: 0.433 psi per foot above the tank, plus a margin.
Below the relief valve setting, allowing for its location.
Choose a tank with at least this total volume and an acceptance volume no less than the expansion, precharged to the fill pressure.
Schedule 40 inside diameters.
2020 ASHRAE Handbook — HVAC Systems and Equipment, Chapter 13, Equations (13) to (15): the water’s expansion v2/v1 − 1 less the piping’s 3αΔt (α = 6.5 × 10⁻⁶ in/in·°F for steel, 9.5 × 10⁻⁶ for copper), times the system volume, divided by (Pa/P1 − Pa/P2) for a plain steel tank or (1 − P1/P2) for a diaphragm tank, or doubled for an open tank, with pressures absolute at 14.7 psia atmospheric. Water’s specific volume from Kell’s density equation, which matches ASHRAE Fundamentals Chapter 1 Table 3. Keep every point in the system above the saturation pressure at the operating temperature and give the pumps enough NPSH.