← Back to tools

Storm Drainage

Roof drains, leaders, storm drains and gutters from roof area and rainfall per IPC / UPC

International Plumbing Code 2021

in/h

100-year, 1-hour storm: IPC Figure 1106.1 or local data.

sq ft

Horizontal projection.

Sharing the roof equally.

Design flow IPC 2021 · 3 in/h
624gpm20,000sq ft
PipeSizeCapacity
Roof drain and vertical conductor each of 4
156 gpm · Table 1106.2
4″
180 gpm
Check the roof drain’s published flow at the design head (1105.2)
Leader each of 4
156 gpm · Table 1106.3
4″
192 gpm
Or rectangular 3 × 4¼″ or 3½ × 4″
Horizontal storm drain
624 gpm at 1/8″ per foot
8″
714 gpm

Secondary roof drains are sized like the primary at the same rainfall rate, with no credit for the primary system, and discharge above grade where they will be seen (1108.2, 1108.3): 4″ each here.

Scuppers instead: at least 4″ high and as wide as the circumference of the 4″ roof drain, 12.6″ (1108.3). Ponding depth is set by the roof’s structural design.

8″semicircular247gpm

One gutter run to each leader, carrying 156 gpm (Table 1106.6).

sq ft

Half of the wall area is added to the roof (1106.4).

gpm

Pumps, condensate and other steady discharge into the building storm drain.

Flow by IPC 2021 Equation 11-1, gpm = R × A × 0.0104, on the projected roof plus half of any wall draining onto it (1106.4). Each roof drain and vertical conductor is the smallest size in Table 1106.2’s vertical column, and each leader the smallest in Table 1106.3, for the flow one drain carries; the horizontal storm drain is the smallest in Table 1106.2 at the slope for the total flow, plus any continuous flow. Roof drains are checked against the manufacturer’s published flow at the design head (1105.2). Secondary drains and scuppers per 1108. This sizes drains that share the roof equally; size each drain and branch with the area it serves.