Gas Pipe Sizer
Fuel gas piping by the longest length method per the 2025 California Plumbing Code (NFPA 54)
Pressure drop 0.5 in. w.c, supply under 2 psi.
Meter or regulator to the most remote outlet.
From the gas supplier (1214.3).
Read at the 60 ft row for 60 ft, 0.5 in. w.c. drop, 1,000 Btu/cf.
Enter the load each section carries, the sum of the outlets past it. Every section is read at the same longest length (1215.1.1).
Longest length method (1215.1.1): every section is sized for the load it carries, read at the length from the point of delivery to the most remote outlet, rounded up to the next table row. Capacities are the 2025 California Plumbing Code Section 1215.3 sizing equations with Table 1215.3’s Cr and Y at the inside diameters of Tables 1215.2, rounded to three figures as the tables print them; they agree with the tables. Natural gas loads are converted to cfh at the heating value entered (1214.3). The specific gravity is the tables’ (0.60 natural, 1.50 propane); for other gases use the supplier’s factors (1214.1). Appliance inputs default to Table 1208.3.1 typical values; use the nameplate input (1214.2). CSST is sized from the manufacturer’s tables.
Commercial and other appliances: enter the nameplate input in thousands of Btu/h.
Enter or ↓ moves down · + and − step the count · paste a column from a spreadsheet to fill down
Inputs default to the approximate values of 2025 California Plumbing Code Table 1208.3.1 (NFPA 54 Table A.5.3.2.1); type the nameplate input in the Each column to replace one.