Methodology & Validation

Calculations follow published sources: the ASHRAE Handbooks, SMACNA, NFPA, the International and Uniform Plumbing Codes, AWWA standards, Crane Technical Paper 410 and health department criteria. This page documents the exact formulas, assumptions, and validation examples used in each tool.

Last updated: November 2026Version 1.90

Reference Standards

ASHRAE Handbook — Fundamentals, Chapter 21: Duct Design (2021 Edition)

SMACNA HVAC Systems Duct Design Manual, 4th Edition

Sizing Method

Each result is the smallest size that meets every active limit: friction at or below the friction rate (equal-friction method), velocity at or below the velocity limit, or both. Round ducts step through standard sizes; rectangular and flat oval ducts step in 2" increments at a set aspect ratio or with one side fixed.

Rectangular and Round Conversion

De = 1.30 · (a · b)^0.625 / (a + b)^0.25

The round diameter with the same friction at the same airflow as an a × b rectangle (ASHRAE Fundamentals, Ch. 21). The converter also runs it backward, solving for the second side from a diameter and one side. Results round up to the next even inch. Equal friction doesn’t mean equal area, so velocities differ.

Friction — Darcy-Weisbach

Δp / 100 ft = 12 · f · (100 / Dh) · ρ · (V / 1097)²
1/√f = −2 · log(12ε / 3.7Dh + 2.51 / (Re · √f))

Dh = Hydraulic diameter 4A/P (inches) of the actual round, rectangular or flat oval section

ε = By duct type, Table 1: 0.0003 ft for metal (galvanized steel, average); 0.003 ft for flex, fully extended, and for fibrous glass duct board, which ASHRAE lists as tentatively medium rough because no test data is available

Kc = Flex only: percent compressed, multiplying friction by 1 + 0.58 · Kc · e^(−0.126·D), D in inches (Eq. 22)

Re = 8.50 · Dh · V (standard air, Eq. 21)

ρ = 0.075 lb/ft³ (standard air)

The round diameter for a friction rate is solved from this equation, then rounded up to the next standard size. This is the same calculation the Duct Static Pressure tool uses, so the two tools agree.

Source: ASHRAE Handbook — Fundamentals 2021, Chapter 21: Darcy-Weisbach (Eq. 18) with the Colebrook friction factor (Eq. 19), solved by iteration. Checked against Ch. 21 Table 13 (53 of 55 sizes identical; the other two sit exactly on a size boundary) and SMACNA Example 5-6.

Rectangular & Flat Oval Sizing

Rectangular and flat oval sizes are found directly against the limits, with friction calculated on their own hydraulic diameter — so a rectangle meets the friction rate itself rather than matching the round duct’s area. The suggested rectangles are taken off a ladder: for each short side in 2-inch steps, the smallest long side that meets the limits; three rungs are shown, the nearest to square, to about 2:1 and to 3:1, so each suggestion sits at the limits rather than inside them. Flat oval suggestions come off the same ladder by minor axis. The ▲▼ steppers reach every other size. Aspect ratios over 4:1 are flagged; SMACNA (§2.8) recommends keeping rectangular ducts close to 1:1, since cost and friction rise with aspect ratio.

Flat oval area and perimeter (minor axis A, major axis B):

Area = (π/4) × A² + A × (B − A); Perimeter = π × A + 2 × (B − A)

System Presets

The System buttons fill in common design limits. None is on to start, with the low-pressure supply limits filled in; clicking an active button turns it off and restores those limits. Values are rules of thumb and can be edited; editing a limit turns the button off.

SystemMax velocityMax friction
Low-pressure supply800 FPM0.08 in. wg / 100 ft
Medium-pressure supply2,000 FPM0.20 in. wg / 100 ft
Return air700 FPM0.06 in. wg / 100 ft
General exhaust (including toilet)1,000 FPM0.08 in. wg / 100 ft
Grease exhaust1,500 FPM target—

Grease ducts are sized to a target velocity: IMC 2021 Section 506.3.4 sets a minimum of 500 FPM, not a maximum.

Assumptions

  • Standard air, 0.075 lb/ft³ (sea level, about 68–70°F)
  • Galvanized steel ductwork, ε = 0.0003 ft
  • Straight duct only — fitting losses not included (use the Duct Static Pressure tool)
  • Sizes always round up, so friction and velocity are at or below the limits as displayed (whole FPM and 0.01 in. wg/100 ft); a size that reads exactly at a limit is accepted

Validation

Exact diameter from the friction equation and the selected size, galvanized steel, standard air:

CFMFriction rateExact DSelectedFriction at size
5000.1010.5"12"0.053
10000.1013.7"14"0.089
20000.1017.7"18"0.093
20000.0818.6"20"0.055
40000.1023.0"24"0.082

Independent check: 800 CFM through a 12 × 12 duct gives 0.080 in. wg / 100 ft, matching a physical ductulator reading.

Reference Standards

ASHRAE Handbook — Fundamentals, Chapter 21: Duct Design (2021 Edition)

ASHRAE Duct Fitting Database (DFDB) — loss coefficients, as tabulated in Ch. 21 Tables 10–11

SMACNA HVAC Systems Duct Design, 4th Edition — Appendix A loss coefficients (elbows with vanes, offsets, contractions, expansions, dampers)

AMCA Publication 201 — Fans and Systems (system effect)

Method

Each run is entered as its index path, component by component, and tagged as supply, return or exhaust along with the equipment that serves it. Straight-duct friction, fitting dynamic losses and equipment pressure drops are summed as total pressure for the index path, and a safety factor is applied; the fan’s external static pressure is that total less the fan outlet velocity pressure (Ch. 21 Eq. 17). Runs are independent — where a single fan serves more than one run (for example an AHU supply fan that also handles the return), the engineer adds those runs; dedicated supply, return and exhaust fans are each sized on their own run.

Straight Duct — Darcy-Weisbach

Δp = 12 · f · (L / Dh) · pv
pv = ρ · (V / 1097)²
1/√f = −2 · log(12ε / 3.7Dh + 2.51 / (Re · √f))
Flex, compressed: Δp × PDCF, PDCF = 1 + 0.58 · Kc · e^(−0.126·D)

Dh = Hydraulic diameter 4A/P (inches) — actual rectangular and flat oval geometry

ε = Absolute roughness (ft) per Ch. 21 Table 1 — medium smooth 0.00015 (aluminum, PVC, stainless), average 0.0003 (galvanized), medium rough 0.003 (fibrous glass duct board; flex duct, fully extended), faced liner 0.005

Kc = Flex duct compression, percent (Eq. 22–23); D its diameter in inches

Re = Reynolds number, 8.50 · Dh · V at standard air (Eq. 21)

ρ = Air density from elevation and temperature (lb/ft³)

Source: ASHRAE Handbook — Fundamentals 2021, Chapter 21: Darcy-Weisbach (Eq. 18), Colebrook (Eq. 19), velocity pressure, Reynolds number (Eq. 21), flex duct correction (Eq. 22) — Table 2’s flex results (0.043 fully extended; 0.071, 0.148, 0.254 at 4, 15 and 30% compressed) reproduce exactly; air density from the standard atmosphere (Chapter 1)

Fittings & Equipment

Δp = C · pv

Loss coefficients are representative values for common elbows, transitions, tees, dampers, entries and exits: diverging junctions from the DFDB values in Ch. 21 Tables 10–11 (branch: 45° conical wye 0.45, 45° straight wye 0.70, 45° entry tap 0.64, 90° conical tee 0.87, 90° straight tee 1.80; main 0.15, at a branch-to-main flow ratio of about 0.2), and elbows with vanes, offsets, contractions, expansions and dampers from SMACNA Appendix A (single-thickness vanes 0.22, double-thickness 0.41; abrupt contraction 0.5·(1 − A₂/A₁)^0.75). Branch coefficients are referenced to the branch velocity; a SMACNA junction coefficient, referenced to the upstream section, converts as C·(Vc/Vb)². Fire/smoke damper and equipment losses come from manufacturer data. Transitions are referenced to the higher of the upstream and downstream velocity pressures; abrupt steps compute C from the area ratio. Any coefficient can be overridden with the DFDB value for the exact geometry and flow ratio. Equipment (filters, coils, terminals, diffusers, louvers, silencers) is entered from manufacturer data.

Import from Revit

  • A run exported with the MEP Calcs add-in for Revit (pyRevit) lists every duct, fitting, accessory and terminal between two picked elements, in order, by following the physical duct connections
  • Airflow is added up by the add-in from the Flow entered on each air terminal beyond each point, counting only terminals of the run’s air type. Revit’s own system flow is not used, so the airflow is right past VAV boxes, at taps, and where systems are split or unassigned
  • A duct with branch taps along it is split at each tap into stretches with their own airflow, with a straight-through main loss at each tap passed
  • Fittings map to the coefficients above: elbows by shape, radius or miter and angle (other angles scale the 90° value by the ASHRAE angle factor Kθ; round radius elbows use the CD3-1 value for the family’s r/D); transitions as gradual contraction, expansion or rectangular↔round; takeoffs and tees by the run’s turn (45° entry, 90° bellmouth or conical tap, 90° straight tap) and, for return and exhaust, the converging coefficients; the leg the run follows sets the airflow and size
  • The fan at the end of the run is set as the serving equipment and left out; VAV boxes, air terminals and other equipment are entered from manufacturer data

Fan Power, Motor and Heat

PA = 0.000157 · cfm · Δp (hp) · PF = PA / ηF · PM = (1 + 0.03) · PF / ηM
ΔT = Δp / (ρ · cp · η)

Each run’s design total pressure and fan airflow give the air power, the fan shaft power at the entered fan efficiency, the motor input with a 3% belt drive loss (none for direct drive) at the motor efficiency, and the smallest standard motor at or above the shaft power plus drive loss (2021 ASHRAE Handbook — Fundamentals, Chapter 18, Heat Gain from Fans). The temperature rise through the fan follows HVAC Systems and Equipment Chapter 21 Equation (1), with the fan efficiency alone when the motor is outside the airstream and the fan, drive and motor efficiencies together when it is inside. Fan laws 1a–1c (Chapter 21 Table 2) carry the run’s design point to a new airflow or speed for the same fan: airflow ∝ speed, pressure ∝ speed², power ∝ speed³; fan speed = motor speed × motor sheave ÷ fan sheave on pitch diameters.

CaseResult
10,000 cfm at 2.5 in. wg, 65% fan, 91% motor, belt drive3.93 air hp, 6.04 bhp, 6.83 hp input, 7.5 hp motor
Same fan from 10,000 to 11,000 cfm at 1,200 rpm, 6.04 bhp1,320 rpm, 3.03 in. wg, 8.04 bhp
Fan heat at 2.5 in. wg, 65%, motor outside the airstream1.43°F rise

Limitations

  • Tee and wye coefficients depend on branch-to-main flow and area ratios. Fixed mid-range values are used; override with the DFDB value for takeoffs on the index run.
  • Flex duct uses ε = 0.003 ft fully extended, with ASHRAE’s correction factor for the percent compressed; ASHRAE recommends 6 ft maximum, fully stretched, connecting rigid duct to diffusers only.
  • Lined duct must be entered at its inside (net) dimensions.
  • Losses are summed as total pressure. Fan static pressure is the total less the fan outlet velocity pressure.

Cross-check

Darcy-Weisbach friction (used by both duct tools) versus Wright’s empirical equal-friction fit, D = (0.109·Q^1.9 / Δp)^0.199, galvanized steel, 100 ft:

CFMSizeDarcy-WeisbachWright fitDuctulator
80012" round0.1250.135—
80012 × 120.0800.0860.080
200018" round0.0930.100—
400024" round0.0820.088—

The Wright fit reads about 7% high and is not used; the Darcy-Weisbach result matches the physical ductulator.

Reference Standards

2021 ASHRAE Handbook — Fundamentals, Chapter 1 Psychrometrics: Equations (3), (5), (6), (21), (24), (28), (32), (35), (37), (39), (43)–(46), Section 8 Numerical Calculation of Moist Air Properties, and Examples 1–4

Method

Perfect-gas relations as Section 8 lays them out. Saturation pressure by IAPWS-IF97 (Eq. 5) at 32°F and above and IAPWS 2008 (Eq. 6) below; humidity ratio W = 0.621945 pw/(p − pw) (Eq. 21); relative humidity pw/pws; specific volume v = 0.370486 (t + 459.67)(1 + 1.607858 W)/p (Eq. 28); enthalpy h = 0.240 t + W (1061 + 0.444 t) (Eq. 32); thermodynamic wet bulb from Eq. 35 (Eq. 37 below freezing), solved by bisection; dew point by the IAPWS-IF97 saturation temperature (Eq. 39), and below freezing by solving Eq. 6. Pressure at elevation by Eq. 3. Mixing conserves dry air, moisture and enthalpy on mass flow, cfm ÷ v (Eq. 46). A coil’s total load is the enthalpy change less the condensate leaving at the leaving air temperature (Eq. 45); the sensible part is the dry-bulb change at the leaving humidity ratio, and the latent part the rest.

Validation

ASHRAE exampleHandbook (chart)Tool
Ex. 1: 100°F db, 65°F wbW 0.00523, h 29.80, td 40°F, 13% rh, v 14.22W 0.00519, h 29.74, td 40.0°F, 12.8% rh, v 14.23
Ex. 2: 20,000 cfm saturated at 35°F heated to 100°F1,507,000 Btu/h1,503,000 Btu/h
Ex. 3: 10,000 cfm, 85°F 50% rh to saturated 50°F50.77 tons50.65 tons
Ex. 4: 5,000 cfm at 40/35°F mixed with 15,000 cfm at 75°F 50% rh65.9°F db, 56.6°F wb65.8°F db, 56.6°F wb

The handbook’s examples read the psychrometric chart, which is drawn from real-gas properties (Table 2); the perfect-gas relations agree within about half a percent, which ASHRAE calls accurate enough for most engineering calculations.

Reference Standards

2025 California Mechanical Code, Chapter 4: Table 402.1, Equations 403.2.1, 403.2.3, 403.3, 403.4, 403.5.1, 403.5.1.1, 403.5.1.3, 403.5.1.4 and 403.5.2, Table 403.2.2, Section 404

2025 Building Energy Efficiency Standards (Title 24 Part 6), Section 120.1(c)3 and Table 120.1-A; Table 120.1-B and CMC Table 403.7 (exhaust); Section 120.1(d)3 and its Exceptions 1 to 3 (demand control ventilation)

2022 California Building Code Table 1004.5 (occupant load factors, for the demand control trigger) and Section 1004.6 (fixed seating)

2021 International Mechanical Code Section 403.3.1.1, Tables 403.3.1.1 (outdoor air and exhaust rates), 403.3.1.1.1.2 and 403.3.1.1.2.3.2

Method

Rooms, zones and systems. Every room is calculated on its own, then rooms sharing a zone name on one system add up into a ventilation zone, and the zones feed their system. Head counts round up to whole people; CMC Vbz rounds to whole cfm and Voz rounds up; Title 24 Vz rounds. No safety factor is applied.

California. Every room is calculated two ways and the greater governs. CMC: Vbz = Rp·Pz + Ra·Az from Table 402.1, with Pz the designer’s count or the table’s default density, and Voz = Vbz ÷ Ez (Table 403.2.2). Title 24: Vz is the larger of 15 cfm × Pz or Ra × Az from Table 120.1-A, with Pz the greater of the designer’s count and the table’s minimum density (half the CBC egress load); spaces the table doesn’t list use its “All others” row. Service spaces with no outdoor air row of their own (toilets, locker and shower rooms, janitor closets, parking and the like) carry no outdoor air, which reaches them as transfer air (Section 120.1(c)3 Exception 2 and 120.1(g)2C); a toilet room that is ducted outdoor air takes the “All others” row. Systems: single zone and 100% outdoor air add their zones; multiple-zone recirculating systems take Vou = D·Σ(Rp·Pz) + Σ(Ra·Az), D = Ps ÷ ΣPz, Vot = Vou ÷ Ev with Ev = 0.88D + 0.22 below D = 0.60 and 0.75 at or above it (CMC 403.5), or Ev = the lowest zone Evz = 1 + Xs − Zpz (Section 404), and the intake is the greater of that and the sum of the Title 24 zone rates. The CMC’s California amendment to Section 402.1 defers to the Energy Code; both are shown so the result never falls short of either.

Exhaust. Title 24 Table 120.1-B and CMC Table 403.7, which carry the same rates. Each occupancy brings the exhaust type the code lists for it (an office break room is taken as a kitchenette, and can be set to none); per-area rates multiply the floor area, per-fixture rates multiply the water closets and urinals, showerheads or rooms, at the lower rate for continuous operation (for public toilets, the higher rate where heavy use is expected). Rooms whose rate is set by another standard (paint booths, refrigerating machinery rooms) and kitchens with hoods take an entered override. All rates round up to whole cfm.

Demand control ventilation. Title 24 Section 120.1(d)3: required where the room reaches 25 people per 1,000 sq ft by the larger of its design density and its egress density (1,000 ÷ the CBC Table 1004.5 occupant load factor for the function of space the category usually is, or one entered from the life-safety plan; twice the Table 120.1-A minimum where the CBC has no area factor, as its footnote 1 implies), and the serving system has an air economizer, modulating outdoor air or more than 3,000 cfm of design outdoor air. Exception 1 exempts a room whose exhaust exceeds its outdoor air less 0.2 cfm per sq ft; Exception 2 forbids it in science laboratories, barber shops, beauty and nail salons, daycare sickrooms and where food is prepared without a hood; Exception 3 exempts rooms under 150 sq ft or with fewer than 10 people.

Other states. 2021 IMC: Vbz = Rp·Pz + Ra·Az from Table 403.3.1.1 with Pz never less than the table’s occupant load, Voz = Vbz ÷ Ez, and multiple-zone Vot = Vou ÷ Ev with Ev from Table 403.3.1.1.2.3.2 at the largest Zp = Voz ÷ Vpz, interpolated. Exhaust by the exhaust rates of Table 403.3.1.1, which are ASHRAE 62.1 Table 6-2’s. The demand control column applies the Title 24 rule as a reference check only.

Validation

Zone (California)CMC VozTitle 24 VzRequired
Office space, 5,000 sq ft, default density5 × 25 + 0.06 × 5,000 = 425 cfmlarger of 15 × 25 or 0.15 × 5,000 = 750 cfm750 cfm (Title 24)
Classroom, 900 sq ft, 30 students10 × 30 + 0.12 × 900 = 408 cfmlarger of 15 × 30 or 135 = 450 cfm450 cfm (Title 24)
Conference, 400 sq ft, ceiling warm air (Ez 0.8)(5 × 20 + 24) ÷ 0.8 = 155 cfm15 × 14 (33 per 1,000 sq ft, rounded up) = 210 cfm210 cfm (Title 24)
Public toilet room, 180 sq ft, 3 water closets and urinals, heavy useno outdoor air row: transfer air—exhaust 70 × 3 = 210 cfm
Office break room, 300 sq ft5 × 15 + 0.12 × 300 = 111 cfmlarger of 15 × 10 or 45 = 150 cfm150 cfm; kitchenette exhaust 0.3 × 300 = 90 cfm

Demand control: the 400 sq ft conference room above is at 35 people per 1,000 sq ft by design and 66.7 by egress (15 sq ft per occupant), so its trigger is met; it is required only on a system with an economizer, modulating outdoor air or more than 3,000 cfm of outdoor air. The 5,000 sq ft office at 5 per 1,000 sq ft (egress 6.7) is not.

Assumptions & Limitations

  • Residential dwelling units (CMC 405, Title 24 120.1(b), IMC 403.3.2) and natural ventilation are not covered; occupied-standby reductions are not applied
  • Health care spaces in OSHPD facilities follow CMC Table 4-A, and elsewhere ASHRAE 170; see the ASHRAE 170 Room Check
  • Kitchen hood exhaust is by the Kitchen Hood Exhaust tool and overrides the per-area kitchen rate; parking garages with two or more open sides need no exhaust
  • The CBC function of space behind each occupancy’s egress density is the usual one, not the architect’s code analysis: enter the load factor from the life-safety plan where it differs, and take fixed-seating counts from the seat count (CBC 1004.6)
  • Rooms imported from Revit get an occupancy category matched from the Space’s name, then its space type, fixture counts from plumbing fixture family and type names, and the supply system from the air terminals’ system name; check each one, and pick a category for any the import couldn’t place

Reference Standards

ANSI/ASHRAE/ASHE Standard 170-2025, Ventilation of Health Care Facilities: Section 7.1 and Tables 7-1 (inpatient), 8-1 (specialized outpatient) and 9-1 (residential health, care and support)

Method

Required airflow = air changes × room volume ÷ 60, rounded up to the next cfm. Per Section 7.1(a)(3) the minimum total air changes are supplied for positive rooms and exhausted for negative rooms; negative rooms not required to be exhausted count their supply. Entered supply, exhaust and outdoor air are checked against the minimums, and the pressure relationship by supply against return plus exhaust (above for positive, below for negative). Rooms imported from Revit take the ceiling height found over the Space, or the Space’s height where none is found, and a space type matched from the Space’s name, which should be checked; Revit carries no outdoor air per room, so that check waits for an entered value. The table’s pressure, direct exhaust, recirculating room unit, turndown, filter, humidity and temperature requirements are shown for the space. Where a table gives a note in place of a pressure, the note governs. Table 8-2 (general outpatient) is not included. In California, OSHPD 1–5 facilities follow CMC Table 4-A (based on Standard 170-2021 with amendments).

Reference Standards

2025 California Mechanical Code Sections 508.5 (Tables 508.5.1.2–508.5.1.5, 508.5.2.2), 511.2 and 511.3

2021 International Mechanical Code Sections 506.3.4, 507.5 and 508.1

Method

Net hood exhaust (total hood exhaust less makeup air discharged inside the hood) is the rate per linear foot for the hood type and the heaviest appliance duty under the hood, times the hood length; double island canopies are per side. Rates (cfm per foot) for wall-mounted, single island, double island, backshelf and eyebrow hoods: light 200, 400, 250, 250, 250; medium 300, 500, 300, 300, 250; heavy 400, 600, 400, 400, not permitted; extra-heavy 550, 700, 550, not permitted, not permitted. The CMC and IMC tables match. CMC noncanopy hoods take 300 cfm per foot of cooking equipment; IMC Type II dishwashing hoods 100 cfm per foot. The grease duct is the even-inch round size nearest the design velocity, rounded up, never under 500 fpm, and in California no more than 2,500 fpm. Listed hoods follow their label rate, which is often lower than these minimums.

Reference Standards

ASHRAE Handbook — Fundamentals, Chapter 16: Ventilation and Infiltration (flow through openings)

ASHRAE Handbook — Fundamentals (2021), Chapter 16, Eq. 44 (flow through an orifice), and ASHRAE Handbook — HVAC Applications (2023), Chapter 54 Fire and Smoke Control, Eq. 9 — the I-P form of the orifice equation for door gaps (C = 0.65; C = 0.35 for open doorways)

NFPA 80, Standard for Fire Doors and Other Opening Protectives — §4.8.4.1 (undercut) and §6.3.1.7 (edge clearances), used as the default gaps

ASHRAE Standard 170-2025 — §7.2.1(e) requires airborne infection isolation rooms to be at least −0.01 in. w.c. and §7.2.2(d) requires protective environment rooms to be at least +0.01 in. w.c. relative to adjacent spaces

Air Balance

Offset = supply + makeup − return − exhaust

A space with more air delivered than removed is positive and pushes its offset out through its doors; a space with more removed than delivered is negative and draws air in. Spaces whose offset is within the neutral band (±10 CFM by default) are shown as neutral.

Door Airflow — Network Solution

Q = 2610 · A · √ΔP

Q = Airflow through the door (CFM)

A = Leakage area of the door or opening (ft²)

ΔP = Pressure difference across the door (in. w.c.)

2610 = Includes a flow coefficient of 0.65, flow exponent n = 0.5 (orifice flow) and standard air density

1405 = Open doorways: flow coefficient 0.35, because stationary vortices form in the opening (Ch. 54)

Spaces are the nodes of an airflow network and doors are its openings. The pressure of every space is solved (Newton’s method) so that the flow out through its doors equals its offset. Doors to areas that are not modeled connect to a reference zone, “Rest of building,” held at 0 in. w.c. This gives the direction, CFM and ΔP at every door, including air that passes through a neutral space on its way between a positive and a negative one.

The quick check divides each space’s offset evenly over its doors. It is shown for fast review; the network flow is the governing value.

Door Leakage Area

Closed door: A = W × undercut + (2H + W) × crack (+ H × crack for the meeting stile of a pair)
Opening: A = W × H

Defaults are a 3′-0″ × 7′-0″ door with a 3/4″ undercut (NFPA 80 §4.8.4.1) and a 1/8″ crack at the jambs and head (§6.3.1.7: nominal for hollow metal doors, which are allowed 1/8″ ± 1/16″, and the maximum for wood doors), giving about 52.5 in². A hollow metal door at the full 3/16″ gives about 65.3 in²; gasketed doors leak much less, so enter a measured or manufacturer leakage area where it matters. Airflow through the default door:

ΔP, in. w.c.0.010.020.030.05
CFM95135165213

Floor Plan Tools

  • The scale is read from the sheet’s scale note when present, picked from standard scales, or calibrated from two points a known distance apart
  • Click-to-fill floods the room from the click and traces its outline on the wall faces. Doors are found from their swings — arcs of door-sized radius and about a quarter turn, whether drawn as curves or as chains of short lines — and each doorway is closed with a line from the hinge across the opening, so the fill stops at the door while openings without a door stay open and fill as one space. Openings narrower than the gap setting (3.5 ft by default) are also closed, for doors drawn without a swing
  • On vector PDFs the fill reads walls only. Walls are recognized as the line style drawn mostly as long parallel pairs a few inches apart (the two faces of a wall), so furniture, equipment, piping and text drawn in other styles are ignored; the wall style can also be picked by clicking a wall line, or turned off to use all linework
  • Door swings (arcs and leaves) and small free-standing marks such as columns are left out of the fill, and room names and numbers are read from the room tag inside the outline
  • Place spaces automatically runs the same fill from every room name on the sheet. Text reads as a room name when it is a word of three or more letters and not a dimension, area, equipment or system tag (VAV, FCU, CHWS and the like). Names that land in a room already found are skipped, and regions under 20 SF or over 20,000 SF, or open to the sheet edge (title block text, corridors open to a lobby), are left out. Multi-line tags are joined, even where the upper lines spill past the room outline
  • Import from Revit reads the Spaces on a sheet exported with the MEP Calcs add-in for Revit: each Space’s outline at the wall finish faces, name and number; supply, return and exhaust airflow summed from the Flow of the air terminals in it (a terminal above the Space’s upper limit is matched by plan position); and doors from the model and its linked models with width and height, placed on the wall between the spaces either side. Positions are converted from the model to the sheet through the viewport, so a PDF printed from the same sheet at full size lines up exactly; a different paper size is scaled to fit. The drawing scale comes from the view. A Space still named “Space” takes the name of the architect’s Room it sits in, or else the room tag on the PDF; holes (columns, shafts) are cut out; slivers under 15 SF with no airflow are left out; a door repeated in two linked models is placed once. Each import brings in only the checked items — space outlines, names and numbers, supply, return and exhaust airflow, doors, drawing scale — so a model still in progress can be brought in a piece at a time. A Revit space updates the space already on the plan that came from it, or that was drawn by hand or auto-placed where it is (keeping that outline and anything not checked); with outlines unchecked, nothing new is added
  • The 3D view extrudes each space to its height (from Revit, set on the space, or the default ceiling height in Setup) and colors it by its pressure class; doors are drawn in the walls at their width and height with an arrow and the airflow through each, or “=” where balanced. It shows the same results as the plan. With walls imported from Revit, walls are drawn at their thickness from the level to the level above (or cut at 4 ft to see into the rooms), with windows and doors as openings, glass in the windows, curtain walls as glass with mullions on their grid lines, and columns; curved walls are drawn as short straight pieces. The architecture is for presentation only and doesn’t enter the airflow calculation
  • Split space cuts a space along a line drawn wall to wall. The larger part keeps the name and number; the smaller takes a room name found inside it, or the same name with “B”. Entered airflows are shared by floor area so the totals don’t change, and each door stays with the part whose wall it sits on
  • Drawing tools snap to line ends, intersections and lines in vector PDFs; polygon and rectangle markups (such as Bluebeam area takeoffs) can be imported as spaces
  • Space areas are reported from the outlines at the drawing scale

Assumptions & Limitations

  • Steady state at standard air; stack effect, wind and door opening events are not included
  • Leakage through walls, ceilings, plenums and ductwork is not included — all offset leaves through the doors and openings entered
  • Spaces with offset but no path to the reference zone are flagged; a closed group that balances on its own shows pressures relative to that group
  • Undercuts and crack widths are design assumptions; critical rooms should be verified by testing and against their governing standard — ASHRAE 170 (health care), ANSI/ASSP Z9.5 (laboratories), ISO 14644 (cleanrooms)
  • A door with zero leakage area is treated as sealed and carries no flow
  • One floor plan sheet per project

Reference Standards

ASHRAE Handbook — Fundamentals, Chapter 22: Pipe Design (2021 Edition)

ASME B36.10M — Welded and Seamless Wrought Steel Pipe

ASTM B88 — Standard Specification for Seamless Copper Water Tube

Sizing Method

Uses the Darcy-Weisbach equation with the Colebrook friction factor (ASHRAE Chapter 22), at the mean of the supply and return temperatures. The recommended size is the smallest within ASHRAE’s limits: 2″ and smaller by velocity, 2–4 FPS; over 2″ by friction, 0.75–4 ft/100 ft, with velocity capped at 8 FPS as a design limit for noise. A flow too small to reach 2 FPS in any size takes the smallest size within the upper limits.

Formulas

Darcy-Weisbach

ΔP = f × (L/D) × (V²/2g)

Colebrook-White

1/√f = −2 log₁₀(ε/3.7D + 2.51/Re√f)

Reynolds Number

Re = V × D / ν

f = Darcy friction factor

D = Internal diameter (ft)

V = Flow velocity (ft/s)

ε = Absolute roughness (ft)

ν = Kinematic viscosity (ft²/s)

Source: ASHRAE Handbook — Fundamentals 2021, Chapter 22

Pipe Internal Diameters

Nominal SizeMaterialID (in)Standard
½"Type L Copper0.545ASTM B88
¾"Type L Copper0.785ASTM B88
1"Type L Copper1.025ASTM B88
1¼"Type L Copper1.265ASTM B88
1½"Type L Copper1.505ASTM B88
2"Type L Copper1.985ASTM B88
2½"Sch 40 Black Steel2.469ASME B36.10M
3"Sch 40 Black Steel3.068ASME B36.10M
4"Sch 40 Black Steel4.026ASME B36.10M
6"Sch 40 Black Steel6.065ASME B36.10M
8"Sch 40 Black Steel7.981ASME B36.10M
10"Sch 40 Black Steel10.020ASME B36.10M
12"Sch 40 Black Steel11.938ASME B36.10M

Fluid Properties by System Type

System TypeSupply / Returnν at mean (ft²/s)
Chilled Water44°F / 54°F1.43 × 10⁻⁵ (49°F)
Heating Hot Water140°F / 120°F5.66 × 10⁻⁶ (130°F)
High Temp Hot Water180°F / 160°F4.15 × 10⁻⁶ (170°F)
Condenser Water85°F / 95°F8.40 × 10⁻⁶ (90°F)

Water viscosity from a curve fit to tabulated water properties (within about 2.5%, 32–212°F) — see Hydronic Head Loss, Fluid Properties.

Glycol Solutions

Propylene and ethylene glycol at 20–50% by volume use tabulated viscosity and density, interpolated to the mean temperature (20–200°F). Viscosity relative to water rises sharply in cold water:

Solution (by volume)Freezesν ÷ water at 49°Fν ÷ water at 130°F
30% propylene glycol8°F3.4×2.2×
30% ethylene glycol4°F2.2×1.9×

Source: The Dow Chemical Company, Engineering and Operating Guide for DOWFROST and DOWFROST HD (propylene glycol) and for DOWTHERM SR-1 and DOWTHERM 4000 (ethylene glycol), viscosity, density and freezing point tables. The same data appear in ASHRAE Handbook—Fundamentals 2021 Ch. 31 Tables 6 and 9 (ethylene glycol) and 10 and 13 (propylene glycol), by volume percent; every tabulated point here matches them.

Assumptions & Limitations

  • Straight pipe only — fitting losses not included (use the Hydronic Head Loss tool)
  • Colebrook solved iteratively; laminar flow (Re < 2300) uses f = 64/Re
  • Copper ε = 0.000005 ft, steel ε = 0.00015 ft
  • The 8 FPS cap over 2″ is a design limit for noise. ASHRAE’s erosion limits (Ch. 22 Table 23) are higher: 15, 14, 13, 12 and 10 FPS at 1,500, 2,000, 3,000, 4,000 and 6,000 operating hours a year, and erosion is not significant below 10 FPS without cavitation
  • Pipe schedule follows the project specification and the ASME B31.9 pressure–temperature rating

Reference Standards

ASHRAE Handbook — Fundamentals, 2021 I-P Edition, Chapter 22: Pipe Design

Crane Co. — Flow of Fluids Through Valves, Fittings and Pipe, Technical Paper No. 410 (TP-410)

ASME B36.10M — Welded and Seamless Wrought Steel Pipe, Schedule 40

ASTM B88 — Standard Specification for Seamless Copper Water Tube, Type L

Pipe Friction

Darcy-Weisbach — ASHRAE Ch. 22

Δh = f · (L/D) · (V²/2g)

Flow Velocity

V = GPM × 0.002228 / A(ft²)

Colebrook Friction Factor — ASHRAE Ch. 22 (solved iteratively)

1/√f = 1.74 − 2·log(2ε/D + 18.7 / Re·√f)

ε = 0.00015 ft (carbon steel) · 0.000005 ft (copper Type L)

g = 32.174 ft/s²

Re = Reynolds number = V·D/ν

Fitting Losses

K-Factor Method — ASHRAE Ch. 22

Δh = K · (V²/2g)

Velocity V is referenced to the upstream pipe for reducers and expansions.

K-Factor Sources

Fitting TypePipe Size RangeSource
Threaded fittings and valvesBelow 2½"ASHRAE Ch. 22, threaded fitting table (sizes not listed use the nearest listed size)
Flanged elbows, returns, valves; tees and LR elbows 2½"–3"2½"–12"ASHRAE Ch. 22, flanged fitting table
Welded long-radius elbows (R/D = 1.5)4"–24"ASHRAE Ch. 22 Table 6 (research values at 4, 8 and 12 fps), interpolated on velocity
Welded tees (line & branch)4"–16"ASHRAE Ch. 22, welded tee table
Reducers & expansionsTabulated size pairsASHRAE Ch. 22 Table 6 (research values at 4, 8 and 12 fps); other pairs K = 0.14, a typical value, unless overridden
Standard / 45° elbows, returns, valvesAbove 12"Crane TP-410: 30, 16, 50 fT; gate 8, globe 340, angle 150, swing check 100 fT
Tees (line / branch)Above 16"Crane TP-410: 20 / 60 fT
Ball valve, full portAll sizesCrane TP-410: 3 fT
Butterfly valveAll sizesCrane TP-410: 45 fT (2"–8"), 35 fT (10"–14"), 25 fT (16"–24")
Any valve from manufacturer CvAll sizesK = 891·d⁴/Cv² (d in inches; Crane TP-410 Ch. 3)

fT = fully turbulent friction factor for clean commercial steel pipe, Crane TP-410. Connection type auto-selected: threaded below 2½″, flanged/welded at 2½″ and up. Copper fittings use the steel values for the same size (ASHRAE has no K table for copper fittings and treats copper elbow equivalents as roughly equal to iron). Published K values carry wide uncertainty; use manufacturer data where available.

Crane TP-410 fT Values

Nominal Pipe SizefT
½"0.027
¾"0.025
1"0.023
1¼"0.022
1½"0.021
2"0.019
2½"–3"0.018
4"0.017
5"0.016
6"0.015
8"–10"0.014
12"–16"0.013
18"–24"0.012

Source: Crane Co., Flow of Fluids Through Valves, Fittings and Pipe, Technical Paper No. 410 — friction factors for clean commercial steel pipe with flow in the zone of complete turbulence.

Fluid Properties

Water density and viscosity are computed from curve fits vs. temperature, valid from 32°F to 212°F:

ρ = 62.56 − 0.00289·T − 0.0000378·T² (lb/ft³)
μ = exp(−11.0318 + 1057.51/(T + 214.624)) (lbm/ft·s)
ν = μ / ρ (ft²/s)

T in °F. The viscosity fit is within about 2.5% of tabulated water properties (NIST / IAPWS) over this range.

Supply / Return Temperature Zones

The calculator accepts separate supply and return temperatures and computes fluid properties independently for each. Components in the circuit are assigned to a zone (supply or return) based on their position relative to user-placed zone-switch markers in the component list. Each component's friction calculation uses the density and viscosity corresponding to its assigned zone.

Zone markers are bidirectional — the user can switch back and forth between supply and return as many times as needed. This supports circuits such as condenser water systems where flow goes from the pump (supply temp) through the chiller (warms up), through return piping (return temp), through the cooling tower (cools back down), and back to the pump (supply temp again).

The viscosity difference between supply and return in typical HVAC systems (44/54°F CHW, 85/95°F CW, 140/120°F HHW) changes pipe friction by about 1–2% — small, but captured.

Worked Example

500 GPM of condenser water at 85°F in 6" Sch 40 steel (ID 6.065", ε = 0.00015 ft):

ItemValue
Velocity, Reynolds number5.55 ft/s, Re = 315,500
Friction factor (Colebrook)f = 0.0169
Pipe friction1.60 ft / 100 ft
Four welded LR elbows, K = 0.252 (interpolated at 5.55 ft/s)0.48 ft
Tee, flow through branch, K = 0.560.27 ft
Two butterfly valves, K = 45 × 0.015 = 0.6750.65 ft
Table lookups: 8" LR elbow at 7.1 ft/s / 10" at 4.5 ft/s / 8" tee lineK = 0.205 / 0.205 / 0.080

Velocity head V²/2g = 0.479 ft. The loop head is the sum of all components; design TDH = loop head × safety factor (default 1.10).

Assumptions & Limitations

  • Supply and return temperatures are entered separately; fluid properties are computed at each temperature and applied to components based on their zone in the loop
  • Zone assignment is user-controlled via divider markers in the component list — supports multi-zone circuits (e.g., condenser water where flow goes supply → chiller → return → tower → supply)
  • Each loop is entered as its pump's index circuit: discharge → most resistant path → suction. Flow carries down the loop and is set only where it changes (at branches)
  • Static lift is counted only when the loop is marked as an open system (e.g. condenser water to a cooling tower); in a closed loop it cancels
  • Equipment pressure drops are entered from manufacturer data in ft or psi (psi × 144 / ρ at the zone temperature)
  • Plain water properties — glycol solutions need corrected density and viscosity (the Hydronic Pipe Sizer includes them)
  • Threaded fittings below 2½", flanged/welded at 2½" and up, per common HVAC practice
  • Welded long-radius elbow K values are velocity-interpolated across the 4 / 8 / 12 ft/s columns
  • Welded tee K values are taken at the tabulated velocity — velocity dependence not accounted for
  • Crane K values above the ASHRAE table range are less conservative than the welded data near the table edge — check large fittings against manufacturer data
  • Published K values carry wide uncertainty (ASHRAE Ch. 22)
  • Safety factor default 1.10 — adjustable by user

Reference Standards

International Plumbing Code (IPC) 2021 — Appendix E: Sizing of Water Piping System

2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 6: Water Supply and Distribution

ASTM B88 — Standard Specification for Seamless Copper Water Tube (Type L)

Sizing Method

Uses Water Supply Fixture Units (WSFU) to estimate peak demand, converted to GPM on Hunter’s demand curves. IPC: Table E103.3(3), using its flushometer column when the load includes flushometer valves. UPC: the Appendix A method — fixture units per Table A 103.1 (Table 610.3 with flushometer valves given their own values: 1.6 GPF water closet 5.0 / 5.0 / 8.0 private / public / assembly, 1.0 GPF urinal 3.0 / 4.0 / 5.0), converted on Chart A 103.1: Curve 1 when the load includes flushometer valves (the same Hunter curve as the IPC flushometer column; Appendix A Example A 108.1, 1365 FU → 252 GPM, reproduces), Curve 2 for flush tanks (as tabulated in the UPC Useful Tables). Table 610.10 belongs to the code’s Table 610.4 sizing method and isn’t used. Pipe size is the smallest that keeps velocity within the limit and leaves the required flow pressure at the most demanding fixture.

Table 610.4, 2025 California Plumbing Code. That edition also permits sizing the meter and building supply straight from its fixture unit table (Section 610.4). Street pressure, at 80% where a regulator sets it (608.2), less ½ psi per foot to the highest outlet (610.8) places the system in the 30–45, 46–60 or over-60 psi range; the first length column at or past the developed length to the most remote outlet is read down to the first meter and building supply pair whose fixture units reach the total. Fixture units are Table 610.3 values, except water closets and urinals with flushometer valves, which count by Table 610.10 in accumulative values (40, 70, 90, 105, 115 + 10 each for water closets; 20, 35, 45, 53, 58 + 5 each for urinals). Branches are sized the same way from the fixture units they serve (610.9); no building supply is smaller than ¾″. Below 30 psi, past 1,000 ft or past the last row, the Appendix A method applies.

Pressure Drop Formula

ΔP (PSI) = f × (L/D) × (V²/2g) × 0.4335

0.4335 = Conversion factor from ft w.g. to PSI

ν = 1.217 × 10⁻⁵ ft²/s (water at 60°F)

ε = 0.000005 ft (Type L Copper)

Pressure Budget

P_fixture = P_available − P_elevation − P_system − P_friction

P_elevation = Height × 0.433 PSI/ft

P_system = Meter + backflow preventer + valves, from manufacturer data (default 10 PSI)

P_friction = Darcy-Weisbach loss over the developed length on new, smooth copper, or Hazen-Williams C = 130 for aged pipe (UPC 610.6 asks for aged-pipe friction unless no loss with age is expected; new copper runs about 6–8% below the code friction charts)

Method: IPC 2021 Appendix E (Section E103.3); required flow pressure at the fixture from IPC Table 604.3 or UPC Section 608.1.

IPC 2021 Fixture Unit Values (selected)

FixtureWSFU (total)Min PipeFlow PSI
Water closet — public, flushometer valve10.01"35 (siphonic)
Water closet — private, flushometer valve6.01"35 (siphonic)
Water closet — public, flush tank5.03/8"20
Water closet — private, flush tank2.23/8"20
Urinal — public, ¾" flushometer valve5.0¾"25
Lavatory — public2.03/8"8
Lavatory — private0.73/8"8
Shower head — public / private4.0 / 1.4½"20 (mixing valve)
Kitchen sink — hotel, restaurant4.0½"—
Service sink — offices, etc.3.0½"8
Drinking fountain0.253/8"8

Source: IPC 2021 Table E103.3(2) (loads), Table 604.5 (minimum pipe), Table 604.3 (flow pressure). The tools carry all 27 rows of Table E103.3(2) and all of UPC Table 610.3, with UPC flushometers per Appendix A Table A 103.1. Values checked against the 2021 IPC and the 2025 California Plumbing Code (2024 UPC base); the California code lists a mobile home at 6.0 fixture units where the UPC lists 12.0.

Assumptions & Limitations

  • Type L Copper used for all domestic water sizing
  • Water properties at 60°F; for hot water this slightly overstates friction, which is conservative
  • Straight pipe friction only — enter a developed length that includes an allowance for fittings
  • System losses default to 10 PSI; a reduced-pressure backflow preventer alone is often 10–15 PSI, so use manufacturer data
  • Loads above the end of the code demand table are extrapolated and flagged
  • IPC and UPC WSFU values differ — select correct code for your jurisdiction
  • UPC 610.12.1 limits copper to 8 FPS cold and 5 FPS hot; the IPC sets no fixed velocity limit
  • UPC minimum residual pressure is 15 PSI (Section 608.1); fixtures requiring more use the manufacturer’s value

Reference Standards

International Plumbing Code (IPC) 2021 — Appendix E

2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 6

AWWA Manual M22, Tables 5.6–5.8 — displacement (C700), compound (C702) and Class II turbine meter capacities and average pressure losses

AWWA Manual M22 — Sizing Water Service Lines and Meters (meter capacities, design at 80% of maximum, average losses), as tabulated in the ASPE Data Book Vol. 2, Tables 5-1 and 5-2

Sizing Method

Fixture counts are multiplied by their WSFU values per IPC / UPC tables, totaled, and converted to peak GPM on the code demand curves. UPC fixtures use the Private, Public or Assembly column of Table 610.3, with flushometer valves at their Appendix A Table A 103.1 values, converted on Appendix A Chart A 103.1. Continuous loads (irrigation, cooling tower makeup, etc.) are added directly. The service pipe is sized for velocity ≤ 8 FPS (the UPC 610.12.1 limit for copper on cold water) and the meter is the smallest with the peak flow within 80% of its safe maximum operating capacity (AWWA M22).

Demand Curve Selection

If any flushometer water closets or urinals are entered, the flushometer curve is used for the total and cold-water load (IPC Table E103.3(3) flushometer column; UPC Appendix A Curve 1); otherwise the flush-tank curve. This is conservative where flushometers are a small part of the load (ASPE suggests computing both and using the greater, which for the same fixture units is the flushometer curve). Hot-water demand uses the flush-tank curve by default, since flushometers draw cold water only (ASPE practice); the IPC’s own Appendix E sample problem applies the system’s curve to the hot side too, which the tool offers as an option.

Validation

LoadFixture unitsDemand
IPC public: 10 flushometer water closets, 5 ¾" flushometer urinals, 10 lavatories100 + 25 + 20 = 145 WSFU78.0 GPM (flushometer column)
IPC: 400 WSFU, flushometer / flush tank400 WSFU127 / 105 GPM
UPC public: 10 1.6 GPF flushometer water closets, 5 1.0 GPF flushometer urinals, 10 lavatories (Table A 103.1)50 + 20 + 10 = 80 FU61.2 GPM (Curve 1)
Meter at 78 GPM1½" displacement, 100 GPM max (78 ≤ 80% of 100)Loss ≈ 15 × (78/100)² = 9.1 PSI

Demand by linear interpolation in the code tables (the IPC sample problem rounds up to the next table row instead, about 1.5% higher). Below about 50 fixture units the UPC flush-tank curve runs under the IPC’s, as the UPC chart does.

Fixtures Not Listed in the Code Tables

Fixtures that neither code lists, such as a three-compartment sink, can be added with a user-entered load. IPC Table E103.3(2) note a and UPC Table 610.3 note 2 both direct the designer to assign such fixtures a load by comparison with listed fixtures of similar flow and use. For example, a three-compartment sink is commonly compared with the IPC kitchen sink, hotel or restaurant (4.0 WSFU), or the UPC service sink (3 FU public). The assigned value is the designer’s judgment and should be confirmed with the authority having jurisdiction.

Meter Capacities

Meter SizeTypeSafe Max (GPM)Continuous (GPM)
⅝"Displacement2010
¾"Displacement3015
1"Displacement5025
1½"Displacement10050
2"Displacement16080
3"Compound320160
4"Compound500250
6"Compound1000500
8"Compound1600800
2"–12"Turbine, Class II160 – 5,000100 – 3,300

Source: AWWA Manual M22, Tables 5.6 (displacement), 5.7 (compound) and 5.8 (Class II turbine), averages of 1990-model meters. M22 recommends designing to 80% of the maximum capacity; the meter is selected at 80%. The displacement and compound capacities match the ASPE Data Book reprint used before. Meter type and size are set by the water utility.

Pressure Budget

P_entry = P_street − P_elevation − P_pipe_friction − P_meter

P_elevation = Elevation × 0.433 PSI/ft

P_pipe_friction = Darcy-Weisbach loss over service line length

P_meter = P_max × (Q / Q_max)² — P_max is 15 PSI for displacement meters (the AWWA C700 limit; M22’s averages are about 9–11 PSI, so this is conservative) and M22’s averages for compound meters (7.2, 6.2, 8.4 and 14.5 PSI at 3", 4", 6" and 8") and turbine meters (4.0 to 1.7 PSI); actual losses vary by make, so use the utility’s or manufacturer’s curve

Assumptions & Limitations

  • Service pipe sized as Type L Copper, velocity ≤ 8 FPS
  • Meter sized with the peak GPM within 80% of its safe maximum operating capacity (AWWA M22); a continuous load above the meter’s continuous rating is flagged — verify with the water utility
  • The pressure left at the building entry is reported for comparison with the building’s needs; it is not judged against a fixed threshold
  • Emergency shower ANSI Z358.1 minimum 20 GPM — add to continuous load if simultaneous operation required
  • Eyewash, ice makers, coffee makers and other unlisted fixtures — enter as not-listed fixtures with a load assigned by comparison
  • Continuous loads added directly to fixture GPM before service sizing

Reference Standards

International Plumbing Code (IPC) 2021 — Chapter 7 Sanitary Drainage (Tables 709.1, 709.2, 710.1(1), 710.1(2); Sections 704.2, 709.3, 711) and Chapter 9 Vents (Table 906.1; Sections 904.2, 906.1, 908)

2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 7 (Tables 702.1, 702.1(1), 702.2, 703.2, 717.1; Sections 702.3, 703)

Sizing Method

Fixture counts are multiplied by their drainage fixture units and totaled, with continuous flow at 2 fixture units per gpm in both codes. Each pipe is the smallest size whose table capacity reaches the total. IPC: the building drain or sewer from Table 710.1(1) at the chosen slope, 3″ or larger with a water closet (note a); the horizontal branch and stack from Table 710.1(2), the stack by its number of branch intervals (three or fewer, or more) and also by the most that enters one interval; branches and stacks with a water closet are 3″ or larger, since a 3″ closet outlet can’t drain into smaller pipe (704.2); the stack vent or vent stack from Table 906.1 for the stack size, load and developed length, never under half the stack or 1¼″ (906.1). Five or more branch intervals call for a vent stack (904.2), more than ten for relief vents (908). UPC: Table 702.1 values for the private, public or assembly column, with three or more clothes washers in a battery at 6 each (note 5); drains, stacks and vents from Table 703.2 — horizontal at ¼″ per foot or 0.8 of that at ⅛″ for 4″ and up (note 5), stacks within the listed length, vents within their units and length and never under 1¼″ or half the drain served (note 6); water closets and six-unit traps on 3″ or larger, six at most on 3″ (notes 3 and 4); up to eight public lavatories on 1½″ (note 7). Past 6″, the building sewer comes from Table 717.1, whose minimum load for each slope is flagged when the load falls short.

Validation

LoadFixture unitsSizes
IPC: 20 public 1.6 gpf water closets, 20 lavatories; ¼″ slope, 3 intervals, 100 ft vent80 + 20 = 100 dfuDrain 4″ (216), branch 4″ (160), stack 5″ (one-interval limit 90 on 4″), vent 4″
IPC: 60 bathroom groups (1.6 gpf); 6 intervals, 50 dfu per interval, 120 ft vent300 dfuStack 4″ (500, 90 per interval), vent 3″ (170 ft); vent stack required
UPC public: 10 flushometer water closets, 10 lavatories, 4 1.0 gpf urinals; ¼″ slope, 40 ft stack, 100 ft vent40 + 10 + 8 = 58 FUDrain 4″ (216), stack 4″ (256), vent 3″ (84 units, 212 ft)
UPC: 4 domestic clothes washers in a battery4 × 6 = 24 FUDrain 3″ (35), vent 2″ (24 units)
UPC public: 150 flushometer water closets at ⅛″600 FU8″ sewer (2,800), flagged under its 625 FU minimum at ⅛″

Assumptions & Limitations

  • One run carries the whole load entered; size each branch and stack with the load it carries, and never reduce a drain in the direction of flow
  • Stack offsets in buildings of five stories or more (IPC 711) and the UPC vent rules beyond Table 703.2 are left to the designer
  • Individual, branch and circuit vents are not sized; the vent shown is the stack vent or vent stack
  • Fixtures not listed take the value for their trap size: IPC Table 709.2, or UPC Section 702.1 within the Table 702.1(1) limit

Reference Standards

International Plumbing Code (IPC) 2021 — Chapter 11 Storm Drainage (Equation 11-1; Tables 1106.2, 1106.3, 1106.6; Sections 1105.2, 1106.4, 1108)

2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 11 (Tables 1103.1, 1103.2, 1103.3; Sections 1101.12, 1103.4, 1104.1)

Sizing Method

The design rainfall is the 100-year, 1-hour rate the user enters from the code’s map or table or local data. IPC: flow is gpm = R × A × 0.0104 (Eq. 11-1) on the projected roof plus half of any wall draining onto it (1106.4). With the roof shared equally among the drains, each roof drain and vertical conductor is the smallest size in Table 1106.2’s vertical column for one drain’s flow, each leader the smallest in Table 1106.3 (with its rectangular equivalents), and the horizontal storm drain the smallest in Table 1106.2 at the slope for the total flow plus any continuous flow. Gutters come from Table 1106.6 at the gutter slope. UPC: each roof drain, leader or vertical pipe is the smallest in Table 1103.1 whose allowable area at the rate covers the area one drain serves; the horizontal storm drain comes from Table 1103.2 at 1/8, 1/4 or 1/2 in/ft; semicircular gutters from Table 1103.3. At rates a table doesn’t list, the allowable area is the 1 in/h value divided by the rate (notes 2). Walls add 50% (one wall) or 35% (two adjacent walls of equal height) of their area (1103.4); continuous flow counts 24 sq ft per gpm at 4 in/h (1104.1). A secondary system combined with the primary is sized at double the rate (1101.12.2.2.2). Scuppers are at least 4″ high and as wide as the circumference of the roof drain for the area served (IPC 1108.3, UPC 1101.12.2.1).

Validation

CaseLoadSizes
IPC: 20,000 sq ft at 3 in/h, 4 drains, 1/8″ slope3 × 20,000 × 0.0104 = 624 gpm; 156 gpm per drainConductor 4″ (180), leader 4″ (192), horizontal 8″ (714 gpm)
UPC: the same roof5,000 sq ft per drainVertical 4″ (6,130 sq ft at 3 in/h), horizontal 10″ at 1/8″ (27,600)
UPC: 10,000 sq ft at 2.5 in/h, 2 drains, 1/4″, 10 gpm continuous5,000 sq ft per drain; 10,000 + 10 × 96 ÷ 2.5 = 10,384 sq ftVertical 4″ (18,400 ÷ 2.5 = 7,360), horizontal 6″ (30,200 ÷ 2.5 = 12,080)
UPC: 20,000 sq ft, 4 drains, combined secondary at 3 in/hSized at 6 in/hVertical 5″ (5,765), horizontal 12″ at 1/8″ (22,200)

Assumptions & Limitations

  • The roof is shared equally among the drains entered; size each drain and branch with the area it actually serves
  • Roof drains must also be checked against the manufacturer’s published flow at the design head
  • Ponding depth, overflow elevations and roof structure are for the structural design (IBC 1611); siphonic and controlled-flow systems are not covered

Reference Standards

2025 California Plumbing Code (2024 UPC) Chapter 12 Fuel Gas Piping, which carries NFPA 54 Chapter 6: Sections 1214 and 1215, Tables 1208.3.1, 1215.2(1)–(36) and 1215.3, Equations 1215.3(1) and (2)

NFPA 54 National Fuel Gas Code (2006 edition consulted for comparison)

Sizing Method

Longest length method (1215.1.1). Each section is sized for the load it carries, read at the length from the meter or regulator to the most remote outlet, rounded up to the next length row of the tables. Natural gas loads are converted to cfh at the heating value entered (1214.3); propane is sized in thousands of Btu/h, as its tables are. Capacities come from the Section 1215.3 sizing equations in their flow form, Q = 2313 D2.623 (ΔH / (Cr L))0.541 below 1.5 psi and Q = 2237 D2.623 [(P1² − P2²) Y / (Cr L)]0.541 at 1.5 psi and above, with Table 1215.3’s Cr and Y and each table’s inside diameters, rounded to three figures as the tables print them. Every cell of Tables 1215.2(1), (5), (7), (8), (9) and (27) agrees, and Tables 1215.2(2), (3), (11), (19)–(21) and (24)–(26) agree to within one unit in the last printed figure (for example 859 against 860). Tables 1215.2(4) and (6), natural gas in Schedule 40 pipe at 2 psi and 5 psi, print 5–11% lower capacities than the equation; for ½″–4″ at those pressures the tool reads the printed tables. Propane converts at 2.488 MBH per cfh below 1.5 psi and 2.49 above, the factors that reproduce the propane tables. Other pressures and drops use the equations directly, as Section 1215.1 permits.

Validation

CaseLoadSize
CPC Figure 1215.1.1 example: 1,100 Btu/cf, 0.5 in. w.c. drop, 60 ftOutlets 32, 3, 59 and 136 cfh; sections 35, 94 and 230 cfhOutlets ½″, ½″, ½″, ¾″; sections ½″, ¾″ and 1″, as the example
Natural gas, 2 psi, 1 psi drop, ½″ Schedule 40 at 60 ft—615 cfh, Table 1215.2(4)
Propane, 10 psi, 1 psi drop, ½″ Schedule 40 at 10 ft—3,320 MBH, Table 1215.2(24)
Propane, 11 in. w.c., 0.5 in. drop, ½″ Schedule 40 at 60 ft—110 MBH, Table 1215.2(27)

Assumptions & Limitations

  • Specific gravity 0.60 for natural gas and 1.50 for propane, as the tables; other gases need the supplier’s conversion factors (1214.1)
  • Appliance inputs default to Table 1208.3.1’s approximate values; the nameplate input governs (1214.2)
  • The branch and hybrid pressure methods, regulator losses and CSST are not covered; size CSST from the manufacturer’s tables
  • Plastic pipe is for outdoor underground use only (1210.1.7)

Reference Standards

2020 ASHRAE Handbook — HVAC Systems and Equipment, Chapter 13 Hydronic Heating and Cooling, Equations (13)–(15) and Example 1

ASPE Plumbing Engineering Design Handbook Vol. 2 (2010), Chapter 5, Equation 5-6 and Tables 5-10 and 5-11

2025 California Plumbing Code Section 608.3 and IPC 2021 Section 607.3 (thermal expansion control)

Sizing Method

Hydronic: the net expansion is the water’s v2/v1 − 1 between the lower and higher temperatures less the piping’s 3αΔt (α = 6.5 × 10⁻⁶ in/in·°F for steel, 9.5 × 10⁻⁶ for copper). The tank volume is the system volume times the net expansion divided by (Pa/P1 − Pa/P2) for a plain steel tank with an air/water interface, divided by (1 − P1/P2) for a diaphragm tank, or doubled for an open tank, with absolute pressures at 14.7 psia atmospheric. The acceptance volume is the net expansion; a diaphragm tank is precharged to the fill pressure. Water heaters: ASPE Equation 5-6, the heater and piping volume times the density ratio (d1 − d2)/d2 times p2/(p2 − p1) in absolute pressure, precharged to the minimum supply pressure. Water density is from Kell’s equation (1975), which reproduces ASHRAE Fundamentals Chapter 1 Table 3 specific volumes to their four printed figures and ASPE Table 5-10 within 0.0002.

Validation

CaseHandbookTool
ASHRAE Example 1: 3,000 gal, 40 to 220°F, 10 and 25 psig, steel, plain steel tank578 gal580 gal
The same with a diaphragm tank344 gal345 gal
ASPE: 40 to 140°F expansion ratio (Table 5-10)0.01710.0171
ASPE: 40 and 100 psig pressure ratio (Table 5-11)1.911.91

The handbook example uses specific volumes rounded to four figures (0.01602 and 0.01677 ft³/lb); unrounded, the same example gives 580 and 345 gal.

Assumptions & Limitations

  • Pressures are at the tank connection; the fill pressure must keep the highest point positive, and the maximum stays below the relief valve setting
  • Glycol solutions expand differently from water; use the fluid manufacturer’s data
  • The system volume estimate counts pipe only; add equipment volumes from manufacturer’s data

Reference Standards

2023 ASHRAE Handbook — HVAC Applications, Chapter 51 Service Water Heating, Table 13: Hot-Water Demand per Fixture for Various Types of Buildings (p. 51.29). Values also checked against ASPE Plumbing Engineering Design Handbook Vol. 2 (2010), Chapter 6, Table 6-1.

Georgia Department of Public Health — Food Service Establishment Manual for Design, Installation and Construction (Rules and Regulations, DPH Chapter 511-6-1), Section K: Hot Water Supply Requirements, Table K-1 and worked examples (2013). Table K-1 is adapted from the FDA Plan Review for Food Establishments guidance (2008).

Heaters and Areas

A project can hold any number of water heaters, each with a tag, the area it serves, its own storage temperature, fuel and efficiency. Each heater serves one or more areas, and each area has a category: one of the ten ASHRAE building types, or food service. Fixtures are entered under the area they belong to, so a mixed-use building is sized area by area with the right values for each use.

Areas on one heater are combined by heat, because building areas are tabulated at 140°F and food service fixtures at their delivery temperatures (100–140°F). Adding areas assumes their peak hours coincide, which is conservative.

Output = Σ gph × 8.33 × (T_basis − T_cold); recovery = output ÷ (8.33 × (T_storage − T_cold))

Food Service Areas

Kitchens use the Georgia DPH Table K-1 fixture method instead of an ASHRAE building column. Each fixture’s peak hourly demand is added with no diversity factor, and recovery must meet that peak hour. Health departments differ — other jurisdictions may require their own tables, so confirm the method with the local health authority.

FixturePeak hourly demand
Handwashing sink (including restrooms)5 gph
Food preparation sink5 gph per compartment
Hand-operated pre-rinse sprayer45 gph
Mop / utility sink, hose reel10 gph
Clothes washer15 gph
Shower head14 gph (Section K §2.I lists 35 gph)
Hose bibb used for cleaning35 gph
3-compartment, bar and utensil soak sinksL × W × D (in) × compartments × 0.003255
Warewashing machinefinal-rinse gph × 0.70
  • Compartment-sink factor 0.003255 gal/in³ is a 75% fill, allowing for submerged utensils; × 0.80 where only single-service tableware is used
  • Low-flow hand sinks, pre-rinse sprayers and showers: table gph × rated gpm ÷ standard gpm (2.2, 3.5 and 2.5 gpm)
  • Delivery temperatures follow Section K’s worked examples: hand sinks 100°F, showers 120°F, warewashing sinks and other fixtures 110°F, warewashing machine supply 140°F
  • Fixtures not in Table K-1 (for example a garbage can washer) are entered as unlisted fixtures from manufacturer data
  • Hot-water sanitizing machines need a booster from 140°F to 180°F: booster output = machine gph × 8.33 × 40°F, sized separately from the main heater. The tool shows output (equal to input for an electric booster); a gas booster’s input is output ÷ efficiency, and Georgia’s worked example uses 75%
  • The method sizes recovery only; minimum storage for kitchens is set by the local health authority

Sizing Method

Building areas (ASHRAE fixture method):

Possible max demand = Σ (fixtures × gph per fixture)
Probable max demand = possible max demand × demand factor, never less than the largest single fixture
Storage (gal) = recovery at the storage temperature × storage capacity factor
Output (Btu/h) = recovery gph × 8.33 lb/gal × (T_storage − T_cold)

The probable maximum demand is the heater recovery rate. The handbook notes that total demand is never less than the demand of the largest single fixture, and that the demand factors are not valid for very few fixtures, so the tool uses the larger of the two and says when the largest fixture governs. Fixture demand, demand factor and storage capacity factor come from the table column for the building type. Heat input is output divided by the heater’s thermal efficiency; electric heaters show input in kW (3,412 Btu/h per kW).

Storage Temperature Adjustment

The table is based on a final temperature of 140°F. For other storage temperatures, recovery is scaled so the delivered heat is unchanged, and storage scales with it (stored water at a lower temperature delivers less heat per gallon):

gph at T_storage = gph at 140°F × (140 − T_cold) ÷ (T_storage − T_cold)

Storing at 140°F with mixing valves at the fixtures keeps the table basis and helps control Legionella growth.

Assumptions & Limitations

  • Applies to storage-type heaters; instantaneous and semi-instantaneous heaters need peak-flow sizing instead
  • Dishwasher demand uses the manufacturer’s value when entered, otherwise the top of the table range (table note a)
  • Fixtures not listed for a building type are excluded; enter them as unlisted fixtures with a manufacturer or comparison value
  • Table data predates low-flow fixtures; shower demand in particular may be conservative
  • Demand and storage factors may be overridden where the building type is not listed or historical data supports it
  • Recirculation heat loss is not included
  • Each heater is sized for the areas assigned to it; heaters are not combined

Reference Standards

ASHRAE Handbook — Fundamentals (2021): Chapter 18, Nonresidential Cooling and Heating Load Calculations (radiant time series method, heating loads, system effects); Chapter 14, Climatic Design Information (solar position, clear-sky model, design-day profiles); Chapter 15, Fenestration (angular SHGC, interior attenuation, exterior shading); Chapter 1, Psychrometrics.

ANSI/ASHRAE Standard 62.1 (ventilation rate procedure, multiple-zone system ventilation efficiency) and ANSI/ASHRAE/ASHE Standard 170 (minimum air changes for healthcare spaces).

Cooling: Radiant Time Series

Each space is calculated hour by hour on a design day for the 21st of every month; the peak is the largest hourly sensible load of the 288. Every heat gain is split into radiant and convective parts (Ch. 18 Table 14). The convective part is load in the same hour; the radiant part is spread over the following hours by the space’s radiant time series — the solar series for beam sun through unshaded glass, the nonsolar series for everything else.

Q(θ) = Σ convective gain(θ) + Σⱼ rⱼ · radiant gain(θ − j)
  • Walls and roofs: sol-air temperature on each surface, then the conduction time series of the construction: q(θ) = U·A·Σ cⱼ (t_sol-air(θ − j) − t_room)
  • Conduction time series are computed from the construction’s own layers (finite-volume model of the layers, steady periodic) rather than taken from a table of representative walls
  • Radiant time series are computed for each space by a heat balance of its own surfaces — exterior walls, glass, partitions, floor slab shared with the floor below, ceiling, roof and furnishings — instead of one prototype for the whole project
  • Windows: beam SHGC at the hour’s incidence angle and diffuse SHGC from the rated SHGC and pane count (Fresnel transmittance with path-length absorption), interior shades by their attenuation coefficients, overhangs and fins by the sunlit area
  • Lighting splits between the room and the ceiling plenum by luminaire (Ch. 18 Table 3); people by activity (Table 1); equipment with or without cooling fans; process loads with their own radiant share and schedule
  • Infiltration and outdoor air: 1.10 · CFM · Δt sensible and 4840 · CFM · ΔW latent, corrected for elevation

Heating and Systems

Heating is steady state at the heating design temperature: U·A·Δt for every exterior surface, slab edges by F-factor × exposed perimeter, partitions to unconditioned space, below-grade surfaces to the ground temperature, and infiltration — with no credit for sun, people, lights or equipment.

An air system’s coil load is the coincident (block) load of its spaces each hour, plus the return plenum (lighting and roof heat), supply and return duct gains, duct leakage, supply and return fan heat (brake horsepower from total static and fan efficiency) and the outdoor air (less any energy recovery). Outdoor air follows the 62.1 multiple-zone procedure: Vou from people and area rates with occupant diversity, zone Voz = Vbz/Ez, and Ev from the zone with the highest outdoor air fraction; VAV box minimums are taken at least 1.5 × Voz. The coil-leaving state is checked against saturation, which flags supply temperatures too warm to meet the room humidity.

Envelope from Revit

  • Exterior walls are the walls of Exterior function along each space’s boundary where no other space is across; interior-function walls are never exterior. Wall area is the wall’s height in the storey (floor to floor), less its windows and doors
  • Constructions come from the Revit type’s layers, outside to inside: each material’s thermal asset (conductivity, density, specific heat) where it has one, otherwise a typical material matched by name. Air spaces and empty stud layers count as air spaces (R-0.87); insulation between steel studs counts at 45% of its R-value (ASHRAE 90.1 Appendix A). Revit doesn’t model framing, so check the U-factor of framed walls
  • Windows, doors and skylights by type and size; a type’s U-factor and SHGC are used when they are set in Revit (Revit’s stock single-glazing default is ignored). Curtain walls give their glass from the share of glazed panels, with door panels as doors
  • When set, the share of an exterior wall above the ceiling (wall height less ceiling height, over wall height) goes to the plenum and the return air rather than the room. Slab edge gain in cooling, when set, is F-factor × exposed perimeter × (outdoor dry bulb − room), off by default
  • Ceiling height, and the roof or floor above, from the ceiling and roof found straight above each space; a roof keeps its slope and the ceiling below it (with a ceiling air space) becomes part of the roof assembly

Air Balance

Required supply is the larger of the space’s load airflow and its minimum air changes; design supply rounds that up to the chosen increment unless entered. Return = supply + transfer in − exhaust − transfer out − offset, and not less than zero, so a space whose exhaust exceeds its supply shows a negative net. In heating, a VAV space runs the larger of its heating airflow and its box minimum; other systems keep their cooling airflow. The CO₂ figure on the ventilation schedule is a steady-state comparison, V = N / (Cs − Co), with an editable generation rate, and doesn’t set the design.

Validation

ASHRAE Fundamentals 2021 Ch. 18 worked example: a corner office, 130 ft², spandrel and brick walls, two windows with blinds and a 5 ft overhang, roof above (Btu/h):

ResultHandbookHandbook tablesComputed by MEP Calcs
July 3:00 PM3,1583,1523,250
True peak (September 5:00 PM)3,9163,9054,004
Peak month and hour, four orientationsSep 17 · Sep 17 · Jul 15 · Jul 13all matchall match
Block load of the four offices12,79312,88813,310
Heating4,0334,0334,033
  • “Handbook tables” runs the engine with the chapter’s own conduction and radiant time series and design-day temperatures; it lands within 0.3% (the example’s brick and roof conduction series are not stated in the chapter)
  • “Computed” uses the method as built — every conduction and radiant series from the actual constructions and room — and runs 2–4% above the printed values, the conservative side, consistent with ASHRAE’s own comparison of RTS with the heat balance method
  • Conduction time series computed from layers match all 103 walls and roofs of Ch. 18 Tables 16–17 within 1 percentage point per hour, except one wall the handbook misprints (Wall 5)
  • Room heat balance radiant series follow Ch. 18 Tables 19–20 for the representative zones of Table 21 within a few percentage points per hour (medium-weight, carpeted, 50% glass: 48% vs 49% in the first hour)
  • Solar geometry and clear-sky irradiance reproduce Ch. 14 Examples 2–8 (sun angle 68.62°, beam 244 Btu/h·ft², wall irradiance 88.8 / 22.4 / 27.9); design-day temperatures reproduce Ch. 14 Table 8
  • Angular SHGC from the rated SHGC and pane count reproduces the Ch. 15 values for the example glass within 0.01 at every angle

Assumptions & Limitations

  • Design weather is entered from the station’s climatic design data; months not entered are estimated from the peak month
  • Design days are clear-sky and steady periodic (each day repeats); weekend and holiday schedules don’t apply
  • Below-grade surfaces are left out of cooling, as the chapter recommends; floors over conditioned space carry no load
  • The multiple-zone outdoor air uses the zone with the highest outdoor air fraction; systems with DOAS give their terminal units no outdoor air
  • Safety factors, duct gains and leakage are as entered for each system; none are added by default

Intended Use

MEP Calcs is intended as a quick-check and preliminary sizing tool for licensed MEP engineers and designers. Results should be reviewed by a qualified engineer before use on construction documents. All calculations are provided for informational purposes only.

Version History

v1.90November 2026Ventilation Outdoor Air — rooms marked, combined and drawn, and template sheets that stay architectural. On the plan, a room that gets no outdoor air of its own is marked No outdoor air and not counted: a stair, an elevator or a shaft by its name, anything under 50 sq ft that is not a toilet or a janitor's closet, a small unnamed space no door opens into, and now a storage room or closet, which is taken as unoccupied. That last is a starting assumption and not a code reading: the codes list a rate for a storage room people occupy, so any room marked this way is counted again with one click, and a room already counted or marked by hand keeps what was set. Rooms that are open to one another can be combined: tick them, and the first keeps its name and occupancy and takes the sum of their areas; the combined room is tagged once, can be split back, and stays combined when its sheet is read again. A room the model does not have can be drawn on the plan as a rectangle or an outline; its area comes from the outline at the sheet's scale, and it is named, set and counted like any other, or removed. Revit add-in — a template sheet now gives the layout and not the drawing: new sheets take its title block, scale, crop, grids and the plan's place on the sheet, and the plan is drawn as a plain architectural plan with every trade's work off and no view template, so a duct plan used as the template no longer puts ductwork on them. Spaces placed for these sheets are also not placed where no door opens into them, unless the space is a room of the architect's of 150 sq ft or more (an open office reached through an opening). Checked: the page in the browser with stand-in rooms; the add-in by a dry run outside Revit only. No formula changed; which rooms are counted to begin with did, as described.
v1.89November 2026Ventilation Outdoor Air — rooms kept in step with the drawing. The page showed the drawing Revit sent last under room outlines read when the sheets were first loaded, so after a sheet was made again in Revit with its plan in another place the rooms sat beside the drawing and not on it. A sheet sent again from Revit since its rooms were read here is now read again by itself when the page opens: the outlines, numbers, names and areas follow Revit, rooms that are new are added, and what was set on each room (occupancy, people, zone, left out or counted) stays. A line says which sheets were read again. Only a sheet that shares rooms with the plan here is taken, so the same sheet number in another building is left alone. Checked in the browser with a stand-in account. No calculation changed.
v1.88November 2026Projects first, and the duct criteria by system. Signed in, where the project tools are open, there is a Projects page: every project as a card, and a card that starts a new one; opening a project makes it the one every tool has open and goes to its dashboard. A project sent from Revit that has not been opened in this browser shows there too, and opening it makes the site project of that name. The page is in the top bar, the home page shows the projects worked on last, and a project's dashboard and its project menu lead back to it. Duct Sizer, in a project: the criteria are grouped by system, each divided by where the duct is in it, and picked in two short rows, the system and then the division: LP Supply (main 1,200 FPM, branch 800, runout 600, all at 0.08 in. wg per 100 ft), MP Supply (main 2,000, branch 1,500, at 0.20), Return (main 1,000, branch 700, at 0.06) and Exhaust (general 1,000 at 0.08; grease 1,500, velocity only). The MP branch and the return main are new starting values, taken from within the page's own table of typical velocities; the rest are the values the page had. A division can be added to any system, and criteria saved before the grouping are read as they were. For everyone else the page and its presets are unchanged. Checked in the browser with a stand-in account; not against the real account. No calculation changed.
v1.87November 2026Projects, one sheet a level, and rooms that are no rooms. Duct Sizer — design criteria by project: signed in, where the project tools are open, the sizer works inside the open project and takes its limits from that project's own criteria, a velocity and a friction rate for each class of duct (low-pressure supply main, supply branch, the branch to a diffuser, medium-pressure main, return, general exhaust, grease exhaust, and any class added), starting from the page's standard values; changes save with the project and go with its copy in the account, and named sets are kept in the browser. For everyone else the page and its standard presets are unchanged. A project has a dashboard: its name, number and engineer, and the tools picked for it, each open on that project. Ventilation Outdoor Air — a space that is no room to ventilate comes in left out and not dropped: a stair, an elevator, a shaft or the like by its name, anything under 50 sq ft that is not a toilet or a janitor's closet, and, where the export found the building's doors, a small unnamed space with no door into it. Rooms left out are drawn grey on the plan and listed under Left out, are not counted, scheduled or exported, and any of them is counted again with one click; any room can be left out by hand. Two sheets that show the same rooms are one plan, the one loaded last, so a level sent twice is one tab. From Revit — one sheet of Spaces is kept a level in a project: a sheet sent again is updated, and a level already there from another sheet of the same model over the same ground is replaced by the one sent, with its drawing; sheets sent together, and sheets of a level that cover different ground, are both kept. The add-in says which it will be beside each sheet before anything is sent. Spaces placed by Make sheets for this are not placed in stairs, elevators, shafts and voids, or in anything under 50 sq ft that is not a toilet or a janitor's closet. The add-in's tab is grouped by what each button reads, each group with a tinted title: 3D Model (3D Coordination, as Coordination is now called), Rooms and Spaces, Ductwork and Account. Checked: the pages in the browser with stand-in rooms and a stand-in account; the rule that replaces a level against stand-in records; the add-in by a dry run outside Revit only. Not checked against the real account or in Revit. No calculation changed: sizes and outdoor air are found the same way, to whichever limits and rooms are in force.
v1.86November 2026Revit add-in — the sheets list no longer squeezed out. On the calculators' page the panel that makes sheets used to open under the list of sheets and take all its room, so no sheet could be seen or ticked while it was open, and it stayed open after the sheets were made. The panel now shows in place of the list, with a link back; once the sheets are made the list returns with the new sheets ticked and a line above it saying what was done, or that none can be sent yet where their levels hold no Spaces. All, None and the link that makes sheets sit above the list. A project's sheets are each named once in the note beside it (a sheet and its drawing had both been listed). Checked by a dry run outside Revit only. Nothing on the site changed. No calculation changed.
v1.85November 2026Ventilation Outdoor Air — the plan rebuilt on the Air balance workspace, and template sheets set right. Rooms that came from Revit now open on a plan that fills the page, the same one Air balance uses: the sheet's drawing under the rooms moves with them as it is dragged and zoomed (before, the drawing was redrawn a moment after the rooms moved, which showed them apart), each room carries a tag with its number, name and outdoor air, and the Fit and zoom buttons are where Air balance has them. The panel beside it sets the room that is picked, or several ticked with Shift-click, and lists the level's rooms with their outdoor air and the ones still to set; levels are tabs over the plan. Plan and Schedule are two views of the same rooms, and the schedule keeps the code, systems, exhaust, demand control, print and Excel. Revit add-in, sheets made from a template sheet: the new title block no longer takes the template sheet's number and name (a title block shows its sheet's parameters as its own, which is what raised the error that a sheet number was in use); the building is put at the same spot on the sheet as on the template by lining the model up, where before the plan was centred by its outer box and landed off the sheet whenever its grids ran longer; the grids take the template plan's lengths and bubbles; schedules on the template sheet, a keynote legend among them, are placed too. Checked: the page in the browser with stand-in rooms and a test drawing; the add-in by a dry run outside Revit only. No calculation changed.
v1.84November 2026Revit add-in — sheets made like a sheet of yours. Make sheets for this has a Template: pick one of your sheets and each new sheet is set up as that one is, with its title block in the same place and what is typed into it and into the sheet, its plan's settings, view template and scope box or crop, the plan at the same spot on the sheet with the same viewport type, and, where ticked, its legends and the notes, lines and symbols drawn on the sheet itself. Spaces are switched on in the new plans and every room tagged as before; where the view template has Spaces off it is left off the new plan with its settings kept, and the window says so. The template is remembered for next time, and new sheets are numbered on from any made before. Checked by a dry run outside Revit only. Nothing on the site changed. No calculation changed.
v1.83November 2026Ventilation Outdoor Air — the sheet's own drawing under the rooms, and made sheets that read as plans. Revit add-in: with Send each sheet's drawing too ticked (Revit 2022 or later), a PDF of each ticked sheet at its own size goes to the project with its Spaces, and the Outdoor air plan shows it under the rooms by itself, with the furniture, walls and tags as the sheet has them; a PDF can still be opened by hand. Make sheets for this now makes its clean plans at 1/8 in. scale with every discipline drawn as itself, the walls, doors, stairs, furniture, casework and fixtures switched on and ductwork and piping off, and tags every room: with the model's Space tag, with the stock Space tag from Revit's library where the model has none, or failing that with room tags on the architect's rooms. Checked: the page in the browser with a test drawing; the add-in by a dry run outside Revit only, so the PDF export and the tags have not run in Revit. No calculation changed.
v1.82November 2026Ventilation Outdoor Air — the plan for rooms that were already here. Rooms loaded from Revit before the plan existed had no outlines kept with them, so the plan did not appear until their sheets were loaded again. The page now fetches the plan of such rooms from the sheets in the account by itself, the project of the same name first, without touching the rooms or what was set on them; where it can't, a line under the list says to load the sheets again. No calculation changed.
v1.81November 2026Ventilation Outdoor Air — the plan worked like the Air balance plan. The sheets' PDFs can be opened (one combined set, or a PDF a sheet) and each level's drawing shows under its rooms, found by the page that carries the sheet number in its title block; the rooms' outlines are in the sheet's own points, so they sit on the drawing, and the PDFs stay on the computer for the visit. A room picked on the plan is set beside it without leaving the drawing: its occupancy, area, people and zone, with its outdoor air, the code that governs, its exhaust and demand control as they change, and a button that goes to the next room still to set; several rooms ticked on the plan are given an occupancy or a zone together there. Each room on the plan shows its outdoor air. Ctrl or ⌘ with the wheel zooms about the pointer. Checked in the browser with stand-in rooms and a test PDF; not yet with a real sheet set. No calculation changed.
v1.80November 2026MEP Coordination — steadier on heavy models, doors that open, and firmer footing. On a large model the Shaded and Consistent Colors styles used to drop to a lower resolution and leave out small elements while the view moved and bring them back at each stop, which read as flashing; the picture is now drawn one way, moving and still. Doors from Revit open as doors: the leaf alone swings and the frame stays, a pair opens as two leaves, stile-and-rail and glazed leaves are recognised, overhead and coiling doors rise, and a door that can't be read any other way is read from its opening; a door sent as a frame with no leaf in it still has nothing to swing. In Ultra an open door can be walked through even where another model's wall stands in the opening. On foot you no longer drop into the slot between two flights of a stair or between open treads, ramps are walked on, a walk through walls no longer falls down a shaft, and with walls solid railings stop you. Running water and flushing are removed from Ultra. Ventilation Outdoor Air: system names that only came in with rooms from Revit no longer switch systems on, so a project loaded from Revit starts with systems off (the switch is beside the room list). Measured on a test model and one real model at 60 frames a second; not checked on a slow graphics card. Model geometry, measurements and calculations did not change.
v1.79November 2026Ventilation Outdoor Air — a plan to work from, systems optional, an Excel export, and sheets made in Revit. The rooms that come from Revit are now drawn as a floor plan from the Spaces' own outlines, one level at a time with the walls behind, pinned above the list: clicking a room goes to its row, clicking a row lights its room, Shift-click on the plan ticks several to set together, and rooms still without an occupancy stand out. Systems are optional and off unless rooms already name one: with them off every room adds up, a zone needs no system, and Revit's own system names are not brought in. The schedule exports as an Excel workbook made in the browser (the rooms with their totals as formulas, and the systems). Revit add-in: on the page shared by the tools that read Spaces, Make sheets for this makes a plan of each level in a range (a clean one of the architecture and the Spaces, or one set up like a plan of yours), tags every Space and puts each plan on a new sheet to send from, optionally placing Spaces first in rooms that have none and naming them from the architect's rooms; it is one step to undo. Checked: the page in the browser with stand-in data; the add-in by a dry run outside Revit only. No calculation changed: with systems off the rooms are added up as rooms on no named system always were. Model geometry and measurements did not change.
v1.78November 2026One project from Revit to every tool. Revit add-in: every button on the MEP Calcs tab now opens the one window, on its own page (Shift+click for the prompts each had before). Load Calculation, Ventilation Outdoor Air, Room Pressurization and the ASHRAE 170 Room Check share a page that lists the sheets of the model with a floor plan, each with its level and how many Spaces are on it; the ticked sheets, several levels at once, are read by one export that holds what all four tools use and sent to a project in the account, where a sheet sent again takes the place of the one before. Copy and paste remains for one sheet with nothing kept in the account, and is the only way while signed out. Duct Static Pressure keeps its two picks, started from its page. Sending a 3D view: from a linked model only what the view shows is sent (exactly, in Revit 2024 and later; before that, less what is demolished or not yet built in the view's phase, secondary design options, and Parts or the elements they were cut from), where before a wall and the wall that replaced it could both be sent, one over the other; a railing's top rail and handrails go with it. Site: Load Calculation, Air balance, Outdoor air and the ASHRAE 170 check each have a From Revit picker that lists the account's projects and their sheets and loads the ticked ones through the same import a paste uses: several levels at once into Outdoor air, the room check and the load calculation (each sheet onto its own level), one sheet for the floor open in Air balance. A project sent from Revit opens as the site project of the same name, so its loads, air balance, outdoor air and 3D view are found together. The account page has a Projects section: each project with the parts of its 3D model and its sheets of Spaces, and a button for each tool; the 3D link from the account lists what can be opened and no longer opens the last model by itself. Checked: the add-in by a dry run outside Revit only; the site against a test account with stand-in files. No calculation changed: the same Spaces export feeds the same imports. Model geometry and measurements did not change.
v1.77November 2026Revit add-in — one MEP Calcs window for every tool, and a viewer that updates itself. Fixed: the window still took a long time to appear, because every plan sheet in the model and its links was read before it showed; the sheets are now read after the window is answered. The window is redrawn in the site's own look and holds every tool that goes between Revit and the site: a rail with Coordination and the five calculators (Load Calculation, Ventilation Outdoor Air, Room Pressurization, ASHRAE 170 Room Check, Duct Static Pressure), each with what it sends, what to have open and where it lands, and a button that starts it; the account signed in and the add-in's version sit at the foot of the rail. On the Coordination page a project is picked from a list or named as a new one, its parts are listed as rows, and a tick decides whether the viewer is opened after sending. MEP Coordination viewer: an open project or model is checked against the account every half minute and when its tab comes back, and a part sent again from Revit is loaded by itself, with the eye, the visibility, the cuts, the sheets and the measurements left as they were; it waits while you are on foot or rendering. The window was checked by a dry run outside Revit; the viewer's update was checked in the browser with a stand-in account. Model geometry, measurements and calculations did not change.
v1.76November 2026Revit add-in — the Coordination window opens at once, and making a view comes first. The window used to count everything its view held and ask the site for the account's projects before it showed itself, which on a large model left Revit busy with nothing on screen. It now shows first: the open view is counted a little at a time while the window stays usable (Send works before the count is done), any other view is counted when asked, and the project list arrives while the window is already open. Having a view made (a new 3D view of chosen levels with its section box on) is now the first thing in the window instead of inside the how-to; any 3D view in the model can be picked without opening it, and the view sent last time from that model is picked on opening. Shift+click on Coordination goes to the earlier prompts. Checked by a dry run outside Revit. Model geometry, measurements and calculations did not change.
v1.75November 2026Revit add-in — a Coordination window, and floors that go with the architecture. Clicking Coordination now opens one window in place of a chain of prompts, set as it was the last time for that model, so sending a part again after a change is one click (Send again). The view: any 3D view in the model can be picked, not only the open one, with what its section box covers; a short guide says what makes a good view for sending, and a view of chosen levels with its section box on can be made from the window. What to send: each trade shows how many elements of it the view holds, with the categories, before anything is read, and only the ticked trades are read, so one trade is a much shorter wait than a whole building. Where it goes: a project in the account, listed with the parts each team has sent, who sent them and when; the account on its own; or a file. Fixed: an architect’s model sent as Architecture lost its floors, and flat roofs drawn as floors, because every floor was counted as Structure; a floor now goes with Structure only when it is marked Structural. More categories are sent (roof soffits, fascias and gutters, slab edges, ramps, masses, parts, pads, food service and medical equipment, signage, structural connections, and electrical, data, communication, fire alarm, security, nurse call and telephone devices). If the window cannot open on a Revit, the add-in says why and asks with its older prompts. No calculation changed, and nothing about how geometry is read or measured changed.
v1.74November 2026MEP Coordination — no flashing as you move, Ultra as the finished building, recorded sounds, and projects that put themselves together. Steadiness in Realistic: the picture is now the same moving and still. The light samples through the model each take their light at the surface they serve (a floor’s at the floor; they stood some feet off it, and ran about a fifth dark on floors and a fifth bright on ceilings), stand twice as close together up and down, follow an even-filling sequence of directions in place of random ones, and the ones round the eye (orbiting, round what is looked at) are swept on their own all the time, so they hold hundreds of rays each within seconds where every sweep used to be spread over the whole building. With that, each pixel’s own gathering of light at rest is switched off: it came in at every stop and went at every step, and under lamps it was grainy, which read as the lighting flashing. The picture’s copy of the samples eases toward new values over a moment and never steps; a cut that follows you between floors no longer starts the light over; when the lights or the time of day change, the samples round the eye are begun again first, so the room in view is relit in a second or two; and the notice that the light is settling goes by the light round you, not by the whole building’s (in Ultra it used to stay up for minutes). Realistic keeps one resolution and one level of detail orbiting, as it already did on foot. The exposure eases over about a second (half that into a brighter view) and hardly moves for a small difference, so a room no longer pumps as windows cross the view; under open sky it stops where a sunny day would have it, so asphalt stays dark and white paint is not burned out. Fixed: dark bands across a floor along the bottom and sides of the view (the shading of corners, and the reflections, read the picture’s depth on the line between two of its pixels and on some rows took a level floor for a tilted one; samples past the edge of the picture counted as ledges). Reflections are walked only as far as the picture goes and soften with distance from what they mirror, more on a duller finish. A concrete floor is matte unless its material is named polished, ground or coated (every concrete slab used to mirror like a polished one). New on foot: whatever stands on the floor (a table, a chair, a car, a curb) keeps part of the room’s or the sky’s light off the floor beneath and beside it, a soft shadow worked from the heights of things round you. Ultra is now the building as built: everything shown and solid whatever the sheet or the visibility list say, no clearances or door swings, no cut, and nothing walked through, glass included; a plain walk passes through walls by default, as a look round a model should (Settings still has the choice). Looking with the mouse: on foot in any style, M or the Mouse look button gives the mouse to looking without a button held, and M or Esc gives it back; a click is then on the dot in the middle of the view. Views: beside its sheet (Plan or Split) the 3D view is set up from the sheet as before; on its own (3D) it is the whole model with everything showing, and goes back to the sheet’s set-up beside it again. Sounds: footsteps and swing doors are now recordings (real footfalls on concrete, wood, carpet and grass by what is underfoot, and a real door and latch, from two public-domain packs by Kenney, CC0), since synthesized ones never sounded real; the elevator, its bell, buttons and water are still synthesized. Projects: a coordination project in the account now holds each team’s part, sent from its own Revit model with the add-in asking which project it belongs to; opening the project fetches every part and puts them together by shared coordinates, and a part sent again takes the place of the one before. The Parts list shows who sent each part and when, with a check to show or hide it, and an open project offers a newer part in one line without reloading on its own. Sample building: its 28 sheets are redrawn the way a permit set is plotted (3/16 in. plans lettered in a single-stroke hand, the architecture screened back under each trade’s work, column grid and dimension strings, keynotes, legends, abbreviations, schedules, and a title block with key plan and revision table; sizes, airflows, tags and counts are read from the sample model, while lighting circuits, fixture watts and plumbing connection sizes are worked out for the sheets); its plumbing is complete, with no run passing through a duct, a beam, a column, equipment or another trade’s pipe; its furniture, plants, artwork, cars and trees are redrawn. Its sprinklers are laid out room by room and connected: every head is on a 1 in. drop or sprig from a branch line sized for the heads beyond it, with upright heads between the garage’s beams and hangers to the deck. Floating and embedded items were corrected (lavatory traps, roof leaders, plant tanks, switchgear pads, strip lights, diffusers on partitions, furniture in columns), garage and plant floors are plain sealed or broomed concrete, and the lobby’s high ceiling now clears the steel. Model geometry and measurements did not change, and no calculation changed.
v1.73November 2026MEP Coordination — a whole sample building, parts from each team, and a livelier Realistic. The sample is now a five-story office over a parking level on a landscaped site, made in the browser: architecture and furniture on every floor, structure, a central plant with air, hydronic, plumbing, gas, fire protection, power and lighting systems connected end to end, two elevators, two walkable stairs, and a 28-sheet set (architectural, mechanical, plumbing and electrical plans for every level); a Sample building button opens it beside any model. Parts: the Coordination button in Revit now asks what to send, everything the view shows or chosen trades, and the file carries the site’s shared coordinates; in the viewer, Parts under Model adds another team’s file (or a model sent to the account) to the open one, moved into its coordinates, and a part sent again replaces the one before. Light switches and site entourage are exported. Realistic: reflections are traced for anything smooth or metallic whichever way it faces, and for glass from its own depth, not floors alone, so they move as you do; door leaves throw shadow and the sun’s shadow near you is redrawn as a door swings; the flashlight (F) throws real shadows from the hip; the Lights button lights the fixtures’ faces at once, the lamps are as bright by day as at dusk, and the room is relit in about a second where it used to drift over many; the ground lies at grade (it lay at the model’s lowest point, a story down under a basement) and is drawn behind the model’s own site, so Surroundings no longer covers paving. Ultra: E on a chair sits you down, on a duct, pipe or piece of equipment shows what it is and opens its properties, and on a wall switch works the lights. Walking: a crack or a missing piece in a floor no longer drops you through it; the Walk button follows when a view, section or sheet ends the walk. Sounds: no background tone at all; footsteps are one soft tap; doors are a latch and a wooden thud; the car is a low rumble. Duct velocity coloring moved from the view’s toolbar to Visibility / Graphics. Ventilation Outdoor Air joins the project beside Loads, Air balance and 3D for signed-in accounts: its rooms, zones and systems are kept with the open project and follow it to another computer, and rooms the project already holds in Loads or Air balance can be brought in as a first pass (number, name, area, and the head count, zone, system or supply airflow where they exist). No calculation changed, and model geometry and measurements did not change.
v1.72November 2026MEP Coordination — a steadier, faster walk and new sounds. Speed: the exposure is metered and eased on the graphics card with nothing read back (the read-back stalled the walk several times a second on a sharp display); the solid model is drawn once for depth alone and then shaded, so each pixel is shaded for the one surface it shows; the stand-in lights of Lights on leave every surface’s shading while the traced light carries the fixtures (sixteen idle lights had been worked out for every pixel); near the eye the sun’s shadow is looked up in the near map alone. Steadiness: on foot the picture keeps one resolution, moving or still, which starts from the size of the view and settles where the machine draws sixty frames a second, stepping down only after a second or two of late frames and up only with clear room or as a rare trial; edge smoothing follows the display and never the resolution in use; the light gathered at rest now stays on the surfaces it was gathered for when you move and fades over a second, holds through a small look-around, and comes in as gently, where it used to arrive in steps and vanish at the first step; what is behind you is no longer tested for being hidden, so a quick turn shows it at once; a change in the number of lights compiles behind the pill. Fixed: turning Ultra on with Lights off dropped Ultra’s own setup (no car, no sound). Sounds, all still synthesized, were remade: a room’s reverberation (less of it inside the car), footsteps by floor finish (hard floor or carpet) with a heel and a scuff, a latch and an air push for swing doors, rollers for the car doors, a two-note bell (one strike up, two down), a hoist motor that winds up and down, a quiet air tone in the car, running water and a flush, all through one limiter and balanced by measured level. Ultra turns the building’s lights on. The pill that says what the viewer is working on is back at the top of the view, small, out of the middle of the picture. The last picture now holds from the moment a style is picked until it is ready, where a frame of the old materials under the new style could stand while the shaders compiled. Model geometry and measurements did not change.
v1.71November 2026MEP Coordination — walking and looking, faster and steadier. Changing the time of day, the lights or the surroundings keeps every material and only moves the light, and a pill at the top of the view says what the viewer is working on (updating the view, tracing the light, light settling) instead of the view freezing; section caps are cut a few elements a frame, so moving or switching a section never stalls. Walking: eye height is 5 ft (an existing setting of 5 ft 6 in. moves to it); dragging right looks right, with an Invert look setting for the view to follow the drag; a doorway never traps you (nothing blocks you within 3.5 ft of a door); a door is the whole assembly of its opening, since many families are nested as separate elements (frame, panel, trim, each handle): the panels swing, a pair on their outer edges and apart, the handles ride on their panel, and the frame and trim stay; a Cut above button cuts the building off just under the slab above the floor you are on and follows you between floors; standing in an elevator (a cab, or its doors, named for it in the model; elevator and other sliding doors now slide open as you reach them) offers the floors it serves; pick one and the view fades and you are there, or with Ultra (a Realistic-only toggle beside Surroundings, which adds its details behind the busy pill) the viewer draws the car itself (models seldom carry one): a lit cab the width of the hoistway doors, with sliding doors, a handrail, a panel of floor buttons and a call button beside the doors on every floor. The car waits at the lowest stop; press the call button on the wall beside the doors and it comes to your floor, the hoistway and car doors slide open, you step in, press a floor on the panel (or in the bar), the doors close, the car takes you at about 8 ft a second, and they open again. The hoistway doors only open when the car is there, and a shaft without its car cannot be walked into. The car is measured from the shaft’s own walls (the side of the hoistway doors with no floor and walls close on three sides), stands clear of every floor’s door assembly, and replaces the model’s per-floor stand-ins for the car doors while Ultra is on; every landing gets a position indicator over the doors (the floor the car is passing, with an arrow while it moves), a lantern that lights as it arrives, and the call button; what Ultra draws is lit as Realistic lights the model. Ultra also turns the walk into a first-person one: a click takes the mouse for looking (Esc frees it), a dot in the middle of the view names what E or a click would use (an elevator button, a door, a plumbing fixture, a light fixture), swing doors open and shut by hand and stop you while shut, Space hops, C crouches, F is a flashlight, and footsteps, doors, the elevator’s hum and its chime (once going up, twice going down) are synthesized in the browser with nothing downloaded; the picture stays at up to 2 device pixels per screen pixel, moving or still. None of what Ultra adds is a model element: it is never picked, measured, listed or exported. The surroundings no longer place figures. Realistic draws at no more than 1.5 device pixels per screen pixel at rest and 1 while moving; an element draws only while it is at least about a pixel across for its detail, and after each picture every mesh’s box is tested against the picture’s depth so meshes wholly behind slabs and walls are left out of the next pictures (glass hides nothing behind it), so a tall tower seen whole no longer costs every one of its 20 million triangles. Still renders: a Preview traces at half size with four times the samples and is smoothed up; every quality traces five bounces; a pixel far brighter than its neighbours (a lucky path) is held down before smoothing; a dark room is brought up in steps as a camera would; indoors, window glass is thin see-through glass so the sun and sky light the room directly, and only the nearest two dozen fixtures on your floor are area lights, with the rest merely lit, so interiors no longer sparkle. A trade (mechanical, mechanical piping, plumbing, fire protection, electrical, lighting, structure, architecture, site) can be put in front with everything else faded, as the velocity view does, and only the trades the model holds are offered; a pipe counts as mechanical piping by its system classification and name (hydronic, chilled, heating, condenser, refrigerant, steam) and as plumbing otherwise. Realistic hides equipment clearances and door swings while it is on. The Wireframe and Hidden Line styles are gone. Model geometry and measurements did not change.
v1.70November 2026Ventilation Outdoor Air rebuilt room by room. Each room carries its number, name, occupancy, area, head count, zone and system; rooms sharing a zone name on one system add up into a ventilation zone, and each system has its own type, ventilation efficiency and population. California rooms are figured by the CMC and by Title 24 with the greater governing, as before, with people rounded up to whole people and airflows to whole cfm. New: exhaust per Title 24 Table 120.1-B and CMC Table 403.7 (by area or per fixture, with continuous or heavy-use rates and an override), exhaust-only service spaces (toilets, lockers, showers, janitor closets, copy rooms, parking and the like, with outdoor air by transfer), a demand control ventilation check per Title 24 Section 120.1(d)3 with its three exceptions and the CBC Table 1004.5 egress density, and a printable ventilation schedule. The Revit export now carries each Space’s HVAC zone, the supply system feeding it and the water closets, urinals and showers in it, and the import guesses an occupancy for service spaces too; rooms can be ticked and put into a zone, on a system or under one occupancy together. Title 24 lists the pool and the deck of a swimming space apart, so the calculator now does as well. No other calculation changed.
v1.69November 2026MEP Coordination — Surroundings in Realistic. A Surroundings button puts the building on a lawn that runs to a line of trees on the horizon, with trees and a few figures for scale placed clear of the building and its paving; they cast shadows and show in reflections and through glass. They are drawn only: they are not model elements, so they are never picked, measured, listed or counted, and they stand in for the setting rather than showing the real site. A section box cuts them like the model. Model geometry and measurements did not change.
v1.68November 2026MEP Coordination — bounced light in Realistic. When the view is still, light is traced from the sun, the sky and the light fixtures and bounced around the rooms, sharpening over a few seconds; while you move, a coarser stored estimate of the same light is used, so rooms do not go flat. The tracing uses the walls, floors, ceilings, roofs and stairs and the larger faces of everything else; small parts receive the light but do not block or bounce it. With Lights on, a light fixture uses its output in lumens and its color temperature when the Revit export carries them (files exported before this use a size-based guess); brightness is set for the picture and is not a photometric calculation. Model geometry and measurements did not change.
v1.67November 2026MEP Coordination — real surface finishes in Realistic. The Revit export now lists each material once (name, class, colors, glossiness, and the size of its appearance image; no image leaves Revit) and every face says which one it has. The viewer draws the finish itself at real size: wood planks, panels and slats, concrete, carpet and carpet tile, ceramic and porcelain tile, brick, concrete block, stone, terrazzo, brushed and perforated metal, acoustic ceiling tile and fabric, chosen from the material name, class and appearance type, with joints laid along the building and carried around curved walls. Files exported before this open as before, with finishes guessed from the category and type name. Model geometry and measurements did not change.
v1.66November 2026MEP Coordination — Realistic looks closer to a rendering while you move. A time of day (morning, midday, afternoon, golden hour or dusk) sets the sun and sky; sun shadows are sharp near the view; daylight reaches indoors from the edge of the building and falls off into the room (an estimate; the Render still traces it); polished floors reflect the room, glass reflects the sky and tints what is behind it, and corners are softly shaded; bright light glows and exposure adjusts between indoors and outdoors. Surfaces still take their color from the Revit model: the export carries no textures. Model geometry and measurements did not change.
v1.65November 2026The Revit add-in can sign in to an MEP Calcs account: a token from the account page, pasted into the new Sign in button. Signed in, the Coordination button sends the model to the account and the viewer opens with it, on any computer; models sent this way are listed on the Coordination page and can be removed there. Signed out, nothing changes: the file is saved on the computer. No calculation changed.
v1.64November 2026Duct Sizer: click any size to type a dimension over it, as on a ductulator; Enter commits, Escape cancels, and the arrow keys step by 2 in. Typed sizes round up to the next even inch, and a round size to the next standard diameter. No calculation changed.
v1.63November 2026The Fan Calculator is folded into Duct Static Pressure Loss. Each run now shows its fan brake horsepower, standard motor size, input kW and fan heat under the design total pressure, with the fan and motor efficiencies, drive and motor location set per run; the All Runs table and the report carry the fan power; and fan laws and sheave changes start from the run’s design point in a section at the foot of the page. The old address redirects. No calculation changed.
v1.62November 2026Four new tools. ASHRAE 170 Room Check: required air changes, pressure, exhaust, filters, humidity and temperature for health care spaces from Standard 170-2025 Tables 7-1, 8-1 and 9-1, checked against design airflows, with a room schedule. Fan Calculator: brake horsepower and motor size (ASHRAE Fundamentals Ch. 18), fan laws (S&E Ch. 21), sheave changes and fan heat. Ventilation: zone and system outdoor air for California, taking the greater of the 2025 California Mechanical Code (Chapter 4) and the 2025 Energy Code (Title 24 Part 6, Section 120.1) for every zone and the system, or the 2021 IMC elsewhere, with single-zone, 100% outdoor air and multiple-zone systems. Kitchen Hood Exhaust: hood exhaust by hood type and appliance duty, makeup air and grease duct size per the CMC or IMC. The Revit add-in has two new buttons. Ventilation Outdoor Air: each Space comes in as a zone with its area, supply airflow and head count, and an occupancy category matched from its name. ASHRAE 170 Room Check: each Space lands on the room schedule with its area, ceiling height and terminal airflows, with the space type matched from its name. Water Service Sizer: meter capacities and losses now come straight from AWWA Manual M22 Tables 5.6–5.8; compound meter losses at maximum are 7.2, 6.2 and 8.4 psi (3″, 4″, 6″), lower than the 13.4, 9.6 and 9.4 psi used before, an 8″ compound meter is added, and Class II turbine meters 2″–12″ are a new option. Displacement meters are unchanged.
v1.61November 2026Psychrometric Calculator — a new tool. Moist air properties from dry bulb and wet bulb, relative humidity, dew point or humidity ratio, at any elevation; mixing of two airstreams; and coil loads (total, sensible, latent, condensate), all by ASHRAE Fundamentals Chapter 1, with a small psychrometric chart.
v1.60November 2026Three new calculators. Storm Drainage: roof drain, leader, storm drain and gutter sizes from roof area and rainfall per IPC 2021 Section 1106 or the 2025 California Plumbing Code Section 1103, with walls, continuous flow and secondary drainage. Gas Pipe Sizer: natural gas and propane by the longest length method of the 2025 California Plumbing Code Chapter 12 (NFPA 54), for Schedule 40 steel, copper tubing and polyethylene at the code’s pressures or any other, with appliances entered in a table. Expansion Tank Sizer: hydronic tanks per ASHRAE (diaphragm, plain steel or open) and water heater thermal expansion tanks per ASPE.
v1.59November 2026Sanitary Drainage and Vents — a new calculator. Building drain or sewer, horizontal branch, stack and vent sizes from the fixture count, per IPC 2021 Tables 709.1, 710.1(1), 710.1(2) and 906.1, or the 2024 UPC (2025 California Plumbing Code) Tables 702.1, 703.2 and 717.1 with their notes. Fixture counts in the Water Service, Water Heater and Sanitary tools are now entered in one table with each value, quantity and row total, group subtotals, a running total, search, and keyboard entry and paste like a spreadsheet. No calculation changed.
v1.58November 2026Domestic Water Pipe Sizer and Water Service Sizer — UPC values were compared with the 2025 California Plumbing Code (2024 UPC base): Table 610.3, Table 610.4 (all 630 values), Table 610.10, Appendix A Table A 103.1, the demand table, and Sections 608.1 and 610.12.1 all match, so the labels now name that edition. No value changed.
v1.57November 2026Visual polish. Hydronic Pipe Sizer shows the recommended size between the next smaller and larger, with the full list folded under Compare sizes. Column titles across the tools are darker over a lighter unit, on a hairline. Static Pressure and Head Loss fold the project details away and drop the colored borders. Pages cross-fade as you move between them, and the logo is in the top bar. Each calculator’s browser tab has its own name, and a link to the site shows a preview card. No calculation changed.
v1.56November 2026Domestic Water Pipe Sizer — the Table 610.4 method is back, labeled as the 2019 California Plumbing Code. All 630 of its values and Table 610.10 were compared with that edition; it has not been compared with the 2021 UPC. It no longer picks a ½″ building supply, which Section 610.8 doesn’t allow. Other methods did not change.
v1.55November 2026Duct Sizer — a duct type choice. Duct board sizes rectangular inside dimensions at ε = 0.003 ft, which ASHRAE lists as tentative. Flex sizes round at ε = 0.003 ft fully extended, with its percent compressed by Eq. 22, the same values the Duct Static Pressure tool uses. Metal sizing did not change.
v1.54November 2026Duct Sizer — duct sizes are even numbers only. The converter rounds up to the next even inch, and 5, 7 and 9 inch round are no longer offered, so a small branch that fit one of those now gets the next even size up. The friction and velocity calculations did not change.
v1.53November 2026Duct Sizer — a converter between rectangular and round: the equivalent round for a rectangle, and the second side of a rectangle from a diameter and one side, by the ASHRAE equal-friction equation, rounded up to the next whole inch. No other calculation changed.
v1.52November 2026Load Calculation, Air Balance and 3D now work from one project, with a switch between them. Air Balance holds a plan for each floor, and 3D reopens a project’s model in the browser it was opened in. No calculation changed.
v1.51November 2026Room Pressurization, Load Calculation and MEP Coordination are private for now, and the Pro waitlist is closed. The other calculators are unchanged. No calculation changed.
v1.50November 2026Domestic Water Pipe Sizer and Water Service Sizer — UPC references now name the edition they were checked against: the 2018 UPC, as adopted in the 2019 California Plumbing Code, not the 2021 UPC. No value or calculation changed.
v1.49November 2026Domestic Water Pipe Sizer — the UPC Table 610.4 method is hidden until its values are checked against the 2021 UPC. They were read from the 2019 California Plumbing Code and only spot-checked. The Appendix A and IPC methods did not change.
v1.48November 2026Room Pressurization and MEP Coordination plan views — in dark mode the area around the sheet no longer flashes white when the view settles after a zoom or pan; only the sheet itself is paper white. No calculation changed.
v1.47November 2026Water Heater Sizer — opens on a worked office example in the same layout as the other sizers: storage temperature, cold inlet, type and efficiency in one column with the recovery, storage and input beside them; heater tabs appear only with a second heater; project details fold next to the report button; demand and storage factors fold inside each area. Domestic Water Pipe Sizer — a UPC Table 610.4 method: meter and building supply from fixture units (Table 610.3, flushometer valves per Table 610.10), developed length and the pressure range at the meter after ½ psi per foot to the highest outlet, with the table column shown. Input labels across the tools are sentence case and every table row closes with a rule. The Appendix A and IPC methods did not change.
v1.46November 2026Calculators — one spacing rhythm in every results panel: column heads sit on a single rule, a set distance to each section name and from it to the first row, air instead of a rule between sections, and the two folded lines (Compare, How it’s calculated) share one style. No calculation changed.
v1.45November 2026Calculators — quieter typography: labels, section names and column heads in sentence case at one size and weight, section names without color swatches, and the Duct Sizer rows set on a fixed grid so sizes, ratios and results line up, with lighter steppers that come up on hover. No calculation changed.
v1.44November 2026Duct Sizer — the suggested rectangular and flat oval sizes are taken off a ladder of the smallest size that meets the limits for each short side, and the three shown are the nearest to square, 2:1 and 3:1, so they sit at the velocity and friction limits instead of well inside them (600 CFM at 800 FPM and 0.08: 12×10, 16×8, 22×6). The limits and the friction calculation did not change.
v1.43November 2026Calculators — one answer in view, everything else a line away. Each sizer opens with a worked example, the sizing mode sits with the inputs as a segmented control instead of a bar above, result rows show numbers under a units header, and the comparison charts, the explanation of the result and the reference tables each fold behind one line closed by default. The Duct Sizer offers three rectangular candidates instead of four. The fixture-unit table in the Domestic Water Pipe Sizer and the notes under the Static Pressure, Head Loss and Water Heater results fold the same way. No sizing rule changed.
v1.42November 2026Load Calculation — several projects in the browser (Projects: open, copy, delete, templates), each with its floor plans and saved report copies; a station sheet can be pasted on Climate and its site, heating design temperature, monthly design dry bulb and coincident wet bulb at a chosen percentile, daily ranges and clear-sky depths are read from it, with the design days shown hour by hour; loads and the hour-by-hour profile in the space, zone and system panels; design against required airflow with a balanced flag for spaces, zones and systems; VAV box minimum and reheat per zone; slab-on-grade types by F-factor; room types with a noise criterion, a diffuser maximum (diffusers counted in the equipment list), a plan color and their own matching words; the system’s supply airflow hands off to the Duct Sizer and Static Pressure tools; keyboard shortcuts on ?, with [ and ] for the previous and next screen. The calculation method did not change; a zone set to no reheat or its own box minimum changes only that zone. Across the tools: charts of every size at the entered flow against its limits (Duct Sizer, Hydronic Pipe Sizer, Domestic Water Pipe Sizer), duct cross sections to one scale, pressure budgets drawn as a bar, a meter capacity gauge, loss along the run piece by piece beside the run drawing (Duct Static Pressure, Hydronic Head Loss), and results panels that offer a typical value to try. No sizing rule changed.
v1.41November 2026MEP Coordination — renders finish on large models: only what the camera can see goes to the ray tracer, along with the surfaces that shape the light; each quality has a time limit; rooms get their lights on and dark images are brightened; per-face Revit colors now reach renders. Less flashing where finishes sit on slabs and walls. Doors open as you walk up to them, walking defaults to 5 mph and a 90° view, measuring keeps up while walking, and clicking a selected element again deselects it. Model geometry and measurements did not change.
v1.40November 2026Duct Sizer — Friction Rate Only and Velocity Only now list the same range of sizes as Both Constraints, with ▲▼ to test others; the sizing method did not change. MEP Coordination — walking starts from the 3D view: click a floor or wall and it flies you in; smoother movement and view, with settings for speed, field of view, eye height, look sensitivity and smoothness; hide and isolate can be undone from the view, the Visibility panel or the keyboard. Model geometry and measurements did not change.
v1.39November 2026MEP Coordination — Realistic shows what ducts and pipes are made of (galvanized duct, insulation jackets, copper, cast iron, black steel) instead of system colors, with pure modeling colors on equipment replaced by painted gray. Less flashing while moving: surfaces sharing a plane keep a fixed order, and the camera range, small-element dropout and indoor and outdoor light no longer change from frame to frame. Model geometry and measurements did not change.
v1.38November 2026MEP Coordination — Revit material colors now reach the viewer: the add-in was writing them in a form that could not be read, so surfaces fell back to white. Files already exported are repaired on opening. Realistic uses each element’s own material color and transparency, so solid and spandrel panels are no longer drawn as glass. Model geometry and measurements did not change.
v1.37November 2026MEP Coordination — the Realistic style lit by the sun and a real sky outdoors and neutral room light indoors, with film-like contrast, faint edges and painted equipment no longer treated as bare metal. Model geometry and measurements did not change.
v1.36November 2026MEP Coordination — much faster on big models: heavy groups split by area so what is off screen is not drawn, shadows redrawn only when something changes, a tight camera depth range, and on models too heavy to move at full detail, a lower resolution and fewer small elements while moving, with everything back as soon as the view stops. Model geometry and measurements did not change.
v1.35November 2026Reports — every printed report in Inter and the same finished look; Load Calculation room types keep their name column in view while the table scrolls. The calculations did not change.
v1.34November 2026Site — Inter type, one finished look and smooth motion on every page; the calculations did not change.
v1.33November 2026Load Calculation — air balance by space and system with transfer air, cooling and heating; results by system, zone and space with a month-by-hour peak map; part of an exterior wall above the ceiling can go to the plenum; walls of several assemblies; infiltration per foot of perimeter, exhaust per fixture, miscellaneous loads; optional slab edge gain in cooling; ventilation schedule with a CO₂ comparison; equipment list; several PDFs with revisions and sheet numbers; 3D model with the sun by month and hour; easier drawing (lines that square and line up, typed sizes, moving rooms and pushing walls); new projects start on one screen, where the address can fill in the location from OpenStreetMap and USGS.
v1.32November 2026Load Calculation — the Revit import brings the envelope: wall, roof and ceiling types from their layers and materials, windows, doors and curtain wall glass by type and size with their U-factor and SHGC, ceiling heights, roofs and their slope, skylights, unconditioned spaces and slab on grade; exterior wall lengths no longer stop short where a neighboring room’s wall continues on the same line, and a short open piece of a wall that is mostly against other rooms (a recess or pocket) is not counted as exterior on plans without Revit walls. A project tree replaces the tabs: setup, the building by level, zone and space, air systems and results; Envelope lists every exterior wall and roof for bulk changes; Zones are made automatically (by exposure, level or space type), by picking spaces or by clicking them on the plan, with each zone’s coincident peak; models can be drawn from scratch on a 1 ft grid, with spaces by size, perimeter and core split from a building outline, merging, and copied levels. Room types are matched from more room names (skills labs, electrical and mechanical rooms, stairs and shafts added as types); a room whose name isn’t recognized stays on Office and is listed for review. Results explains how room totals relate to system coil totals.
v1.31November 2026Load Calculation methodology added: the radiant time series method with conduction and radiant time series computed from each construction and room, fenestration, internal and process loads, air systems with ASHRAE 62.1 outdoor air, and its validation against the ASHRAE Fundamentals Ch. 18 worked example.
v1.30November 2026Accuracy review against the source documents (ASHRAE Fundamentals 2021 and HVAC Applications 2023, SMACNA Duct Design, ASPE, Crane TP-410, IPC and UPC 2021, NFPA 80, ASHRAE 170). Ducts: friction factor is now Colebrook (it was the Altshul-Tsal estimate, about 1% different) with Re = 8.50 D V; flex duct takes a percent compressed and applies the ASHRAE correction factor (Eq. 22); aluminum, PVC and stainless roughness 0.00015 ft; fitting coefficients corrected to SMACNA Appendix A (single- and double-thickness vane elbows, offsets, expanding transitions, 45° and 90° tees, a rectangular damper value) and the abrupt contraction formula; "Design ESP" renamed "Design total pressure". Hydronic: welded long-radius elbow K values for 4, 12, 16 and 20 inch and the reducer table corrected, with more size pairs; Crane angle valve 150 fT; the Cv conversion is K = 891 d⁴/Cv²; the pipe sizer applies the ASHRAE limits as written (2 inch and smaller 2–4 fps, larger 0.75–4 ft/100 ft, 8 fps noise limit) and still recommends a size when none passes every limit. Plumbing: UPC flushometer water closets and urinals take their Appendix A Table A 103.1 values read on Chart A 103.1 Curve 1, and the flush type choice shows for both codes; the IPC 1 inch flushometer urinal branch is ¾ inch; optional aged-pipe friction (Hazen-Williams C = 130, UPC 610.6); meters are selected at 80% of their maximum (AWWA M22) with compound meter losses at 13.4 / 9.6 / 9.4 psi. Water heaters: demand is never less than the largest single fixture (ASHRAE HVAC Applications Ch. 51, under Table 13), so one Hubbard bath now sizes at 600 gph, not 150; booster output is labeled as output, with gas input at 75%; citations name Ch. 51 Table 13 and ASPE Table 6-1, and the Georgia shower note mentions §2.I's 35 gph. Room Pressurization: open doorways use a flow coefficient of 0.35 (Q = 1405 A √ΔP) per ASHRAE HVAC Applications Ch. 54, which changes only the pressure difference shown across openings; NFPA 92 citations replaced by ASHRAE Fundamentals Ch. 16 Eq. 44 and HVAC Applications Ch. 54 Eq. 9; the 1/8 inch crack is described as NFPA 80 §6.3.1.7 nominal for hollow metal doors (up to 3/16 inch) and the maximum for wood, no longer as an upper bound; ASHRAE 170 room pressure minimums added. Every worked example was rerun and still matches its source.
v1.29November 2026MEP Coordination — Lights: light fixtures glow and the ones nearest you light the rooms (up to 16 at a time, following you as you walk or orbit); walking, shadows come from the whole building, including what a section cuts away, so the sun comes in only through the glass; Shaded is brighter, with neutral tone mapping; architecture modeled in plain grays and whites leans to a tone per category (walls, floors, ceilings, doors, frames and mullions, structure) with firmer edge lines, while colored materials keep their color; the selection highlight no longer flickers against the surface it covers
v1.28November 2026MEP Coordination — a sheet sets the 3D view floor to floor: from its level up to the next level, just under that level's slab (a stair landing or platform partway up no longer cuts the ceiling space away), and with no top at all on a roof plan; the mechanical piping and plumbing presets keep equipment such as VAV boxes, which carry their air system; no sun shadows while walking indoors; sheet PDFs open again in browsers that give files a bytes() method, with progress for big sets and errors shown over the viewer
v1.27November 2026MEP Coordination — the Revit add-in saves every plan sheet with the model without asking; opening sheets matches sheet numbers without regard to case, spaces or punctuation (M-111 is M111), follows each sheet's main plan rather than a key plan, turns back pages printed turned, reads a title for pages that don't match, and says how many pages matched and why the rest didn't. Shaded: a light from the camera and lighter undersides so walls, floors and ceilings read apart (floors a little darker, ceilings lighter); lay-in ceilings show their grid (2x2 or 2x4, from the ceiling type); diffusers, lights and sprinklers draw over the ceiling they're set in; edge lines no longer flicker against their faces; and elements whose faces carry several materials (a door's frame, leaf and hardware) keep each one's color, which the add-in now exports per face
v1.26November 2026Revit add-in — an Update button on the MEP Calcs tab checks mepcalcs.com, installs a newer version over the old one (cleaning up renamed buttons) and reloads pyRevit; Revit checks in the background when it starts, about once a day, and a notification says when a new version is out. The Coordination export skips faces Revit can't triangulate, keeps going past an element whose geometry can't be read, and reads nested families the way newer Revit versions expect
v1.25November 2026MEP Coordination — measuring snaps like CAD: to endpoints and midpoints of an element's real edges (face outlines and creases, not triangle diagonals), along edges, and to duct and pipe centerlines and their ends, each labeled as you hover; hold Shift to keep the second point square to the first along X, Y or vertical. The sample building's VAV branches are built like a real installation: spin-in taps with volume dampers off the main, 8" round to each box's inlet, boxes with an inlet collar and flow ring, casing, control enclosure and hot water reheat coil, 12x10 discharge with a transition to 10" round, a conical tap to the first diffuser, a reducer to 8" and an elbow into the last; the main steps down through transitions just past each pair of takeoffs, and the sheets draw the taps, dampers, transitions and boxes
v1.24November 2026MEP Coordination — sheet sets: the Revit add-in saves every plan sheet (this model and loaded links) with each viewport's level, view range, discipline and visibility; open the whole PDF set (one combined PDF or a PDF per sheet) and each page is matched to its sheet by the sheet number in its title block; pick a sheet and the 3D view goes to its level, framed on the plan, and shows its trade (HVAC and sheet metal with lights and sprinklers, mechanical piping, plumbing, fire protection, electrical, architectural, structural) or the Revit view's own visibility, still adjustable in Visibility/Graphics; a sheet with several plans follows the one you click. Walk: click a spot on the plan (drag to face a way) or press Walk to stand in the model at eye height, look around by dragging, walk with W A S D, the arrow keys or an on-screen stick on phones, up and down stairs, stopped by walls (or through them), double-click to glide to a spot, measure as you go; where you stand and what you see is drawn on the sheet. Equipment clearances and 3D door swings modeled in families are saved apart and drawn see-through on their own toggles, left out of renders. Revit's own colors: the 3D view's filter colors and material shading colors, and Shaded now has sun shadows and deeper contrast. The sample building opens with an 11-sheet set (architectural, HVAC, mechanical piping, plumbing, electrical), with equipment and NEC working clearances and door swings
v1.23November 2026MEP Coordination — floor plans pinch-zoom and pan on phones, with zoom buttons and a sharp redraw of the sheet as you zoom; the sample building now has rooms (lobby, conference, training, offices, IDF, stair), furniture on Revit's Furniture and Furniture Systems categories and plumbing chases, and its sheets are drawn like construction documents at 1/8" scale: halftone architecture, room tags, air device marks with CFM, grid dimensions, keyed and general notes, a symbol legend, air device and equipment schedules, a sheet index and a title block; the Revit add-in exports furniture and air terminal airflow. Duct Sizer — limits are checked at the precision shown, so a size that reads exactly at the maximum velocity or static loss (for example 12×12 at 800 CFM: 800 FPM, 0.08 in. wg/100 ft) is accepted
v1.22November 2026MEP Coordination — a Velocity view colors every straight duct by air velocity (its airflow over its nominal area, in FPM bands from under 600 to 2,000 and up), with a legend, the fastest duct, and airflow and velocity on any duct you click; the Revit add-in now exports each duct's calculated airflow; the sample building's ducts carry airflow summed from their diffusers, and it opens with its own floor plan sheets (M-101 Level 1, M-102 Level 2, M-103 Roof), lined up with the model for drawing sections on the plan
v1.21November 2026MEP Coordination — Revit category names and Visibility/Graphics groups throughout, with a Site group (Toposolid, Topography, Planting, Hardscape, Parking, Roads) the exporter now sends; older files are renamed on open; renders texture lawn, pavers and asphalt from site categories; the sample building rebuilt with connected systems (chilled and heating hot water, domestic water, sanitary and vent, gas, refrigerant, sprinklers, supply, return and exhaust air), routing that clears the structure, detailed air handler, chiller, condensing units and rooftop unit, and a site with terrain, walks, parking and planting
v1.20November 2026MEP Coordination — path-traced renders (three-gpu-pathtracer): global illumination, reflections, refracting glass and soft shadows from a physical sky and sun at midday, golden hour, dusk (fixtures become area lights that light the rooms) or overcast; surface textures for concrete, metal panels, brick, ceiling grids and roofing; generated trees, shrubs, lawn and plaza; section cuts applied to the traced geometry; people for scale removed from renders for now
v1.19November 2026MEP Coordination — accuracy: positions saved relative to a local origin (about 1/1000" precision), finer facets on round duct and pipe, exact centerline, size and insulation from Revit for straight runs (centerline, bottom, top, slope, length), elevations from the Project Base Point and everything shown to 1/16". Clearance measure: the true minimum distance between two elements from their surfaces (vertex-to-face and edge-to-edge), or Clash where they touch. Renders can add illustrative supports, curbs, pads and people for scale (jobsite figures in hard hats and hi-vis vests); these are generated for the image only and never added to the coordination model
v1.18November 2026MEP Coordination — sections are capped: cut faces filled in the element color and outlined; soft sun shadows and a ground in Realistic, with system colors kept for ductwork and piping; section arrows grow on hover and show the cut elevation or box size while dragging; Render makes a high-quality still (anti-aliased, soft shadows, sky occlusion) up to 3840 × 2160; a sample building to try without Revit
v1.17November 2026MEP Coordination — Visibility/Graphics like Revit (search, discipline groups, categories and systems, see-through per category); visual styles (Wireframe, Hidden Line, Shaded, Consistent Colors, Realistic); saved sections (plan cuts, section lines, section boxes) to select and step through, moved with 3D drag arrows, the floor plan or the arrow keys; point-to-point measuring with horizontal and vertical distances
v1.16November 2026Added MEP Coordination — a 3D viewer for models saved from Revit, with the floor plan PDF, sections drawn on the plan, and visibility by discipline, category and system
v1.15November 2026Room Pressurization — 3D view of the floor: spaces extruded to their heights and colored by pressure, doors with airflow arrows; walls, windows, curtain walls and columns from Revit
v1.14November 2026Room Pressurization — import spaces, airflows and doors from Revit with the MEP Calcs pyRevit add-in
v1.13November 2026Duct Static Pressure — import a duct run from Revit with the MEP Calcs pyRevit add-in: airflow summed from the air terminals, tapped ducts split at each tap, fittings mapped to ASHRAE coefficients
v1.12November 2026Room Pressurization — click-to-fill reads walls only on real drawings: wall linework auto-detected (or picked) so furniture, equipment and piping no longer block the fill; doors closed at their swings (including swings drawn as short lines) so open areas fill as one space; better room-name reading from room tags; place spaces automatically from room names; split space tool
v1.11November 2026Accuracy review across all tools: Duct Sizer on Darcy-Weisbach with sizes that always meet the limits; flex duct roughness; hydronic fitting K values by connection type and Crane values beyond the tables; glycol properties from Dow data; 8 FPS erosion limit; UPC demand on the flush-tank curve; AWWA C700/C702 meter capacities with square-law meter loss; Georgia Table K-1 delivery temperatures; NFPA 80 door gaps; citations corrected
v1.10November 2026Duct Sizer — System presets (low- and medium-pressure supply, return, general and grease exhaust); flat oval tab shows flat oval sizes only
v1.9November 2026Added Room Pressurization — floor plan PDFs with click-to-fill rooms, snapping and markup import, space air balance, airflow network solution for CFM and ΔP at every door, color-coded plan report
v1.8November 2026Water Heater Sizer — multiple heaters, mixed-use areas with a category per area, food service fixtures per Georgia DPH Table K-1 with compartment sinks, dish machines and booster heaters, printable report
v1.7November 2026Added Water Heater Sizer — ASHRAE fixture method for recovery, storage and heat input. Water tools now use the official IPC 2021 and UPC 2021 fixture and demand tables, with UPC occupancy columns and unlisted fixtures
v1.6November 2026Hydronic Head Loss rebuilt — multiple loops with pump tags, cascading flow, plan and 3D piping views, velocity view, insert / edit anywhere, open-system static lift, ft or psi equipment drops
v1.5October 2026Added Duct Static Pressure Loss — Darcy-Weisbach duct friction, ASHRAE fitting coefficients, plan and 3D run views
v1.4April 2026Hydronic Head Loss — supply/return temperature zones, user-controlled pump-end marker
v1.3April 2026Added Hydronic Head Loss Calculator — Darcy-Weisbach, ASHRAE Tables 3/4/6/7, Crane TP-410
v1.2April 2026Added Water Service Sizer, updated methodology
v1.1April 2026Added Domestic Water Pipe Sizer, collapsible sections
v1.0April 2026Initial release — Duct Sizer and Hydronic Pipe Sizer

Questions or Corrections

If you find an error in any calculation or have a suggestion, please reach out at hello@mepcalcs.com

© 2026 MEP CalcsVersion 1.90