Methodology & Validation
Calculations follow published sources: the ASHRAE Handbooks, SMACNA, NFPA, the International and Uniform Plumbing Codes, AWWA standards, Crane Technical Paper 410 and health department criteria. This page documents the exact formulas, assumptions, and validation examples used in each tool.
Reference Standards
ASHRAE Handbook — Fundamentals, Chapter 21: Duct Design (2021 Edition)
SMACNA HVAC Systems Duct Design Manual, 4th Edition
Sizing Method
Each result is the smallest size that meets every active limit: friction at or below the friction rate (equal-friction method), velocity at or below the velocity limit, or both. Round ducts step through standard sizes; rectangular and flat oval ducts step in 2" increments at a set aspect ratio or with one side fixed.
Rectangular and Round Conversion
The round diameter with the same friction at the same airflow as an a × b rectangle (ASHRAE Fundamentals, Ch. 21). The converter also runs it backward, solving for the second side from a diameter and one side. Results round up to the next even inch. Equal friction doesn’t mean equal area, so velocities differ.
Friction — Darcy-Weisbach
Dh = Hydraulic diameter 4A/P (inches) of the actual round, rectangular or flat oval section
ε = By duct type, Table 1: 0.0003 ft for metal (galvanized steel, average); 0.003 ft for flex, fully extended, and for fibrous glass duct board, which ASHRAE lists as tentatively medium rough because no test data is available
Kc = Flex only: percent compressed, multiplying friction by 1 + 0.58 · Kc · e^(−0.126·D), D in inches (Eq. 22)
Re = 8.50 · Dh · V (standard air, Eq. 21)
ρ = 0.075 lb/ft³ (standard air)
The round diameter for a friction rate is solved from this equation, then rounded up to the next standard size. This is the same calculation the Duct Static Pressure tool uses, so the two tools agree.
Source: ASHRAE Handbook — Fundamentals 2021, Chapter 21: Darcy-Weisbach (Eq. 18) with the Colebrook friction factor (Eq. 19), solved by iteration. Checked against Ch. 21 Table 13 (53 of 55 sizes identical; the other two sit exactly on a size boundary) and SMACNA Example 5-6.
Rectangular & Flat Oval Sizing
Rectangular and flat oval sizes are found directly against the limits, with friction calculated on their own hydraulic diameter — so a rectangle meets the friction rate itself rather than matching the round duct’s area. The suggested rectangles are taken off a ladder: for each short side in 2-inch steps, the smallest long side that meets the limits; three rungs are shown, the nearest to square, to about 2:1 and to 3:1, so each suggestion sits at the limits rather than inside them. Flat oval suggestions come off the same ladder by minor axis. The ▲▼ steppers reach every other size. Aspect ratios over 4:1 are flagged; SMACNA (§2.8) recommends keeping rectangular ducts close to 1:1, since cost and friction rise with aspect ratio.
Flat oval area and perimeter (minor axis A, major axis B):
System Presets
The System buttons fill in common design limits. None is on to start, with the low-pressure supply limits filled in; clicking an active button turns it off and restores those limits. Values are rules of thumb and can be edited; editing a limit turns the button off.
| System | Max velocity | Max friction |
|---|---|---|
| Low-pressure supply | 800 FPM | 0.08 in. wg / 100 ft |
| Medium-pressure supply | 2,000 FPM | 0.20 in. wg / 100 ft |
| Return air | 700 FPM | 0.06 in. wg / 100 ft |
| General exhaust (including toilet) | 1,000 FPM | 0.08 in. wg / 100 ft |
| Grease exhaust | 1,500 FPM target | — |
Grease ducts are sized to a target velocity: IMC 2021 Section 506.3.4 sets a minimum of 500 FPM, not a maximum.
Assumptions
- Standard air, 0.075 lb/ft³ (sea level, about 68–70°F)
- Galvanized steel ductwork, ε = 0.0003 ft
- Straight duct only — fitting losses not included (use the Duct Static Pressure tool)
- Sizes always round up, so friction and velocity are at or below the limits as displayed (whole FPM and 0.01 in. wg/100 ft); a size that reads exactly at a limit is accepted
Validation
Exact diameter from the friction equation and the selected size, galvanized steel, standard air:
| CFM | Friction rate | Exact D | Selected | Friction at size |
|---|---|---|---|---|
| 500 | 0.10 | 10.5" | 12" | 0.053 |
| 1000 | 0.10 | 13.7" | 14" | 0.089 |
| 2000 | 0.10 | 17.7" | 18" | 0.093 |
| 2000 | 0.08 | 18.6" | 20" | 0.055 |
| 4000 | 0.10 | 23.0" | 24" | 0.082 |
Independent check: 800 CFM through a 12 × 12 duct gives 0.080 in. wg / 100 ft, matching a physical ductulator reading.
Reference Standards
ASHRAE Handbook — Fundamentals, Chapter 21: Duct Design (2021 Edition)
ASHRAE Duct Fitting Database (DFDB) — loss coefficients, as tabulated in Ch. 21 Tables 10–11
SMACNA HVAC Systems Duct Design, 4th Edition — Appendix A loss coefficients (elbows with vanes, offsets, contractions, expansions, dampers)
AMCA Publication 201 — Fans and Systems (system effect)
Method
Each run is entered as its index path, component by component, and tagged as supply, return or exhaust along with the equipment that serves it. Straight-duct friction, fitting dynamic losses and equipment pressure drops are summed as total pressure for the index path, and a safety factor is applied; the fan’s external static pressure is that total less the fan outlet velocity pressure (Ch. 21 Eq. 17). Runs are independent — where a single fan serves more than one run (for example an AHU supply fan that also handles the return), the engineer adds those runs; dedicated supply, return and exhaust fans are each sized on their own run.
Straight Duct — Darcy-Weisbach
Dh = Hydraulic diameter 4A/P (inches) — actual rectangular and flat oval geometry
ε = Absolute roughness (ft) per Ch. 21 Table 1 — medium smooth 0.00015 (aluminum, PVC, stainless), average 0.0003 (galvanized), medium rough 0.003 (fibrous glass duct board; flex duct, fully extended), faced liner 0.005
Kc = Flex duct compression, percent (Eq. 22–23); D its diameter in inches
Re = Reynolds number, 8.50 · Dh · V at standard air (Eq. 21)
ρ = Air density from elevation and temperature (lb/ft³)
Source: ASHRAE Handbook — Fundamentals 2021, Chapter 21: Darcy-Weisbach (Eq. 18), Colebrook (Eq. 19), velocity pressure, Reynolds number (Eq. 21), flex duct correction (Eq. 22) — Table 2’s flex results (0.043 fully extended; 0.071, 0.148, 0.254 at 4, 15 and 30% compressed) reproduce exactly; air density from the standard atmosphere (Chapter 1)
Fittings & Equipment
Loss coefficients are representative values for common elbows, transitions, tees, dampers, entries and exits: diverging junctions from the DFDB values in Ch. 21 Tables 10–11 (branch: 45° conical wye 0.45, 45° straight wye 0.70, 45° entry tap 0.64, 90° conical tee 0.87, 90° straight tee 1.80; main 0.15, at a branch-to-main flow ratio of about 0.2), and elbows with vanes, offsets, contractions, expansions and dampers from SMACNA Appendix A (single-thickness vanes 0.22, double-thickness 0.41; abrupt contraction 0.5·(1 − A₂/A₁)^0.75). Branch coefficients are referenced to the branch velocity; a SMACNA junction coefficient, referenced to the upstream section, converts as C·(Vc/Vb)². Fire/smoke damper and equipment losses come from manufacturer data. Transitions are referenced to the higher of the upstream and downstream velocity pressures; abrupt steps compute C from the area ratio. Any coefficient can be overridden with the DFDB value for the exact geometry and flow ratio. Equipment (filters, coils, terminals, diffusers, louvers, silencers) is entered from manufacturer data.
Import from Revit
- A run exported with the MEP Calcs add-in for Revit (pyRevit) lists every duct, fitting, accessory and terminal between two picked elements, in order, by following the physical duct connections
- Airflow is added up by the add-in from the Flow entered on each air terminal beyond each point, counting only terminals of the run’s air type. Revit’s own system flow is not used, so the airflow is right past VAV boxes, at taps, and where systems are split or unassigned
- A duct with branch taps along it is split at each tap into stretches with their own airflow, with a straight-through main loss at each tap passed
- Fittings map to the coefficients above: elbows by shape, radius or miter and angle (other angles scale the 90° value by the ASHRAE angle factor Kθ; round radius elbows use the CD3-1 value for the family’s r/D); transitions as gradual contraction, expansion or rectangular↔round; takeoffs and tees by the run’s turn (45° entry, 90° bellmouth or conical tap, 90° straight tap) and, for return and exhaust, the converging coefficients; the leg the run follows sets the airflow and size
- The fan at the end of the run is set as the serving equipment and left out; VAV boxes, air terminals and other equipment are entered from manufacturer data
Fan Power, Motor and Heat
Each run’s design total pressure and fan airflow give the air power, the fan shaft power at the entered fan efficiency, the motor input with a 3% belt drive loss (none for direct drive) at the motor efficiency, and the smallest standard motor at or above the shaft power plus drive loss (2021 ASHRAE Handbook — Fundamentals, Chapter 18, Heat Gain from Fans). The temperature rise through the fan follows HVAC Systems and Equipment Chapter 21 Equation (1), with the fan efficiency alone when the motor is outside the airstream and the fan, drive and motor efficiencies together when it is inside. Fan laws 1a–1c (Chapter 21 Table 2) carry the run’s design point to a new airflow or speed for the same fan: airflow ∝ speed, pressure ∝ speed², power ∝ speed³; fan speed = motor speed × motor sheave ÷ fan sheave on pitch diameters.
| Case | Result |
|---|---|
| 10,000 cfm at 2.5 in. wg, 65% fan, 91% motor, belt drive | 3.93 air hp, 6.04 bhp, 6.83 hp input, 7.5 hp motor |
| Same fan from 10,000 to 11,000 cfm at 1,200 rpm, 6.04 bhp | 1,320 rpm, 3.03 in. wg, 8.04 bhp |
| Fan heat at 2.5 in. wg, 65%, motor outside the airstream | 1.43°F rise |
Limitations
- Tee and wye coefficients depend on branch-to-main flow and area ratios. Fixed mid-range values are used; override with the DFDB value for takeoffs on the index run.
- Flex duct uses ε = 0.003 ft fully extended, with ASHRAE’s correction factor for the percent compressed; ASHRAE recommends 6 ft maximum, fully stretched, connecting rigid duct to diffusers only.
- Lined duct must be entered at its inside (net) dimensions.
- Losses are summed as total pressure. Fan static pressure is the total less the fan outlet velocity pressure.
Cross-check
Darcy-Weisbach friction (used by both duct tools) versus Wright’s empirical equal-friction fit, D = (0.109·Q^1.9 / Δp)^0.199, galvanized steel, 100 ft:
| CFM | Size | Darcy-Weisbach | Wright fit | Ductulator |
|---|---|---|---|---|
| 800 | 12" round | 0.125 | 0.135 | — |
| 800 | 12 × 12 | 0.080 | 0.086 | 0.080 |
| 2000 | 18" round | 0.093 | 0.100 | — |
| 4000 | 24" round | 0.082 | 0.088 | — |
The Wright fit reads about 7% high and is not used; the Darcy-Weisbach result matches the physical ductulator.
Reference Standards
2021 ASHRAE Handbook — Fundamentals, Chapter 1 Psychrometrics: Equations (3), (5), (6), (21), (24), (28), (32), (35), (37), (39), (43)–(46), Section 8 Numerical Calculation of Moist Air Properties, and Examples 1–4
Method
Perfect-gas relations as Section 8 lays them out. Saturation pressure by IAPWS-IF97 (Eq. 5) at 32°F and above and IAPWS 2008 (Eq. 6) below; humidity ratio W = 0.621945 pw/(p − pw) (Eq. 21); relative humidity pw/pws; specific volume v = 0.370486 (t + 459.67)(1 + 1.607858 W)/p (Eq. 28); enthalpy h = 0.240 t + W (1061 + 0.444 t) (Eq. 32); thermodynamic wet bulb from Eq. 35 (Eq. 37 below freezing), solved by bisection; dew point by the IAPWS-IF97 saturation temperature (Eq. 39), and below freezing by solving Eq. 6. Pressure at elevation by Eq. 3. Mixing conserves dry air, moisture and enthalpy on mass flow, cfm ÷ v (Eq. 46). A coil’s total load is the enthalpy change less the condensate leaving at the leaving air temperature (Eq. 45); the sensible part is the dry-bulb change at the leaving humidity ratio, and the latent part the rest.
Validation
| ASHRAE example | Handbook (chart) | Tool |
|---|---|---|
| Ex. 1: 100°F db, 65°F wb | W 0.00523, h 29.80, td 40°F, 13% rh, v 14.22 | W 0.00519, h 29.74, td 40.0°F, 12.8% rh, v 14.23 |
| Ex. 2: 20,000 cfm saturated at 35°F heated to 100°F | 1,507,000 Btu/h | 1,503,000 Btu/h |
| Ex. 3: 10,000 cfm, 85°F 50% rh to saturated 50°F | 50.77 tons | 50.65 tons |
| Ex. 4: 5,000 cfm at 40/35°F mixed with 15,000 cfm at 75°F 50% rh | 65.9°F db, 56.6°F wb | 65.8°F db, 56.6°F wb |
The handbook’s examples read the psychrometric chart, which is drawn from real-gas properties (Table 2); the perfect-gas relations agree within about half a percent, which ASHRAE calls accurate enough for most engineering calculations.
Reference Standards
2025 California Mechanical Code, Chapter 4: Table 402.1, Equations 403.2.1, 403.2.3, 403.3, 403.4, 403.5.1, 403.5.1.1, 403.5.1.3, 403.5.1.4 and 403.5.2, Table 403.2.2, Section 404
2025 Building Energy Efficiency Standards (Title 24 Part 6), Section 120.1(c)3 and Table 120.1-A
2021 International Mechanical Code Section 403.3.1.1, Tables 403.3.1.1, 403.3.1.1.1.2 and 403.3.1.1.2.3.2
Method
California. Every zone is calculated two ways and the greater governs. CMC: Vbz = Rp·Pz + Ra·Az from Table 402.1, with Pz the designer’s count or the table’s default density, and Voz = Vbz ÷ Ez (Table 403.2.2). Title 24: Vz is the larger of 15 cfm × Pz or Ra × Az from Table 120.1-A, with Pz the greater of the designer’s count and the table density (half the CBC egress load); spaces Table 120.1-A doesn’t list, such as animal, correctional and outpatient health care spaces, use its “All others” row. The system intake is the greater of the CMC intake and the sum of the Title 24 zone rates. CMC intake: single zone Vot = Voz; 100% outdoor air Vot = ΣVoz; multiple-zone Vou = D·Σ(Rp·Pz) + Σ(Ra·Az), D = Ps ÷ ΣPz, Vot = Vou ÷ Ev, with Ev = 0.88D + 0.22 below D = 0.60 and 0.75 above (403.5.1.3) and each zone’s primary air at least 1.5 Voz, or Section 404’s Ev = min(1 + Xs − Zpz).
Other states. 2021 IMC: Vbz = Rp·Pz + Ra·Az from Table 403.3.1.1 with Pz never less than the table’s occupant load, Voz = Vbz ÷ Ez, and multiple-zone Vot = Vou ÷ Ev with Ev from Table 403.3.1.1.2.3.2 at the largest Zp = Voz ÷ Vpz, interpolated.
Validation
| Zone (California) | CMC Voz | Title 24 Vz | Required |
|---|---|---|---|
| Office space, 5,000 sq ft, default density | 5 × 25 + 0.06 × 5,000 = 425 cfm | larger of 15 × 25 or 0.15 × 5,000 = 750 cfm | 750 cfm (Title 24) |
| Classroom, 900 sq ft, 30 students | 10 × 30 + 0.12 × 900 = 408 cfm | larger of 15 × 30 or 135 = 450 cfm | 450 cfm (Title 24) |
| Conference, 400 sq ft, ceiling warm air (Ez 0.8) | (5 × 20 + 24) ÷ 0.8 = 155 cfm | 15 × 13.2 = 198 cfm | 198 cfm (Title 24) |
Assumptions & Limitations
- Exhaust rates, residential dwelling units (CMC 405, Title 24 120.1(b), IMC 403.3.2) and natural ventilation are not covered
- Health care spaces in OSHPD facilities follow CMC Table 4-A, and elsewhere ASHRAE 170; see the ASHRAE 170 Room Check
- Demand control ventilation and occupied-standby reductions are not applied
- Zones imported from Revit get an occupancy category matched from the Space’s name, then its space type; check each one, and pick a category for any the import couldn’t place
Reference Standards
ANSI/ASHRAE/ASHE Standard 170-2025, Ventilation of Health Care Facilities: Section 7.1 and Tables 7-1 (inpatient), 8-1 (specialized outpatient) and 9-1 (residential health, care and support)
Method
Required airflow = air changes × room volume ÷ 60, rounded up to the next cfm. Per Section 7.1(a)(3) the minimum total air changes are supplied for positive rooms and exhausted for negative rooms; negative rooms not required to be exhausted count their supply. Entered supply, exhaust and outdoor air are checked against the minimums, and the pressure relationship by supply against return plus exhaust (above for positive, below for negative). Rooms imported from Revit take the ceiling height found over the Space, or the Space’s height where none is found, and a space type matched from the Space’s name, which should be checked; Revit carries no outdoor air per room, so that check waits for an entered value. The table’s pressure, direct exhaust, recirculating room unit, turndown, filter, humidity and temperature requirements are shown for the space. Where a table gives a note in place of a pressure, the note governs. Table 8-2 (general outpatient) is not included. In California, OSHPD 1–5 facilities follow CMC Table 4-A (based on Standard 170-2021 with amendments).
Reference Standards
2025 California Mechanical Code Sections 508.5 (Tables 508.5.1.2–508.5.1.5, 508.5.2.2), 511.2 and 511.3
2021 International Mechanical Code Sections 506.3.4, 507.5 and 508.1
Method
Net hood exhaust (total hood exhaust less makeup air discharged inside the hood) is the rate per linear foot for the hood type and the heaviest appliance duty under the hood, times the hood length; double island canopies are per side. Rates (cfm per foot) for wall-mounted, single island, double island, backshelf and eyebrow hoods: light 200, 400, 250, 250, 250; medium 300, 500, 300, 300, 250; heavy 400, 600, 400, 400, not permitted; extra-heavy 550, 700, 550, not permitted, not permitted. The CMC and IMC tables match. CMC noncanopy hoods take 300 cfm per foot of cooking equipment; IMC Type II dishwashing hoods 100 cfm per foot. The grease duct is the even-inch round size nearest the design velocity, rounded up, never under 500 fpm, and in California no more than 2,500 fpm. Listed hoods follow their label rate, which is often lower than these minimums.
Reference Standards
ASHRAE Handbook — Fundamentals, Chapter 16: Ventilation and Infiltration (flow through openings)
ASHRAE Handbook — Fundamentals (2021), Chapter 16, Eq. 44 (flow through an orifice), and ASHRAE Handbook — HVAC Applications (2023), Chapter 54 Fire and Smoke Control, Eq. 9 — the I-P form of the orifice equation for door gaps (C = 0.65; C = 0.35 for open doorways)
NFPA 80, Standard for Fire Doors and Other Opening Protectives — §4.8.4.1 (undercut) and §6.3.1.7 (edge clearances), used as the default gaps
ASHRAE Standard 170-2025 — §7.2.1(e) requires airborne infection isolation rooms to be at least −0.01 in. w.c. and §7.2.2(d) requires protective environment rooms to be at least +0.01 in. w.c. relative to adjacent spaces
Air Balance
A space with more air delivered than removed is positive and pushes its offset out through its doors; a space with more removed than delivered is negative and draws air in. Spaces whose offset is within the neutral band (±10 CFM by default) are shown as neutral.
Door Airflow — Network Solution
Q = Airflow through the door (CFM)
A = Leakage area of the door or opening (ft²)
ΔP = Pressure difference across the door (in. w.c.)
2610 = Includes a flow coefficient of 0.65, flow exponent n = 0.5 (orifice flow) and standard air density
1405 = Open doorways: flow coefficient 0.35, because stationary vortices form in the opening (Ch. 54)
Spaces are the nodes of an airflow network and doors are its openings. The pressure of every space is solved (Newton’s method) so that the flow out through its doors equals its offset. Doors to areas that are not modeled connect to a reference zone, “Rest of building,” held at 0 in. w.c. This gives the direction, CFM and ΔP at every door, including air that passes through a neutral space on its way between a positive and a negative one.
The quick check divides each space’s offset evenly over its doors. It is shown for fast review; the network flow is the governing value.
Door Leakage Area
Defaults are a 3′-0″ × 7′-0″ door with a 3/4″ undercut (NFPA 80 §4.8.4.1) and a 1/8″ crack at the jambs and head (§6.3.1.7: nominal for hollow metal doors, which are allowed 1/8″ ± 1/16″, and the maximum for wood doors), giving about 52.5 in². A hollow metal door at the full 3/16″ gives about 65.3 in²; gasketed doors leak much less, so enter a measured or manufacturer leakage area where it matters. Airflow through the default door:
| ΔP, in. w.c. | 0.01 | 0.02 | 0.03 | 0.05 |
|---|---|---|---|---|
| CFM | 95 | 135 | 165 | 213 |
Floor Plan Tools
- The scale is read from the sheet’s scale note when present, picked from standard scales, or calibrated from two points a known distance apart
- Click-to-fill floods the room from the click and traces its outline on the wall faces. Doors are found from their swings — arcs of door-sized radius and about a quarter turn, whether drawn as curves or as chains of short lines — and each doorway is closed with a line from the hinge across the opening, so the fill stops at the door while openings without a door stay open and fill as one space. Openings narrower than the gap setting (3.5 ft by default) are also closed, for doors drawn without a swing
- On vector PDFs the fill reads walls only. Walls are recognized as the line style drawn mostly as long parallel pairs a few inches apart (the two faces of a wall), so furniture, equipment, piping and text drawn in other styles are ignored; the wall style can also be picked by clicking a wall line, or turned off to use all linework
- Door swings (arcs and leaves) and small free-standing marks such as columns are left out of the fill, and room names and numbers are read from the room tag inside the outline
- Place spaces automatically runs the same fill from every room name on the sheet. Text reads as a room name when it is a word of three or more letters and not a dimension, area, equipment or system tag (VAV, FCU, CHWS and the like). Names that land in a room already found are skipped, and regions under 20 SF or over 20,000 SF, or open to the sheet edge (title block text, corridors open to a lobby), are left out. Multi-line tags are joined, even where the upper lines spill past the room outline
- Import from Revit reads the Spaces on a sheet exported with the MEP Calcs add-in for Revit: each Space’s outline at the wall finish faces, name and number; supply, return and exhaust airflow summed from the Flow of the air terminals in it (a terminal above the Space’s upper limit is matched by plan position); and doors from the model and its linked models with width and height, placed on the wall between the spaces either side. Positions are converted from the model to the sheet through the viewport, so a PDF printed from the same sheet at full size lines up exactly; a different paper size is scaled to fit. The drawing scale comes from the view. A Space still named “Space” takes the name of the architect’s Room it sits in, or else the room tag on the PDF; holes (columns, shafts) are cut out; slivers under 15 SF with no airflow are left out; a door repeated in two linked models is placed once. Each import brings in only the checked items — space outlines, names and numbers, supply, return and exhaust airflow, doors, drawing scale — so a model still in progress can be brought in a piece at a time. A Revit space updates the space already on the plan that came from it, or that was drawn by hand or auto-placed where it is (keeping that outline and anything not checked); with outlines unchecked, nothing new is added
- The 3D view extrudes each space to its height (from Revit, set on the space, or the default ceiling height in Setup) and colors it by its pressure class; doors are drawn in the walls at their width and height with an arrow and the airflow through each, or “=” where balanced. It shows the same results as the plan. With walls imported from Revit, walls are drawn at their thickness from the level to the level above (or cut at 4 ft to see into the rooms), with windows and doors as openings, glass in the windows, curtain walls as glass with mullions on their grid lines, and columns; curved walls are drawn as short straight pieces. The architecture is for presentation only and doesn’t enter the airflow calculation
- Split space cuts a space along a line drawn wall to wall. The larger part keeps the name and number; the smaller takes a room name found inside it, or the same name with “B”. Entered airflows are shared by floor area so the totals don’t change, and each door stays with the part whose wall it sits on
- Drawing tools snap to line ends, intersections and lines in vector PDFs; polygon and rectangle markups (such as Bluebeam area takeoffs) can be imported as spaces
- Space areas are reported from the outlines at the drawing scale
Assumptions & Limitations
- Steady state at standard air; stack effect, wind and door opening events are not included
- Leakage through walls, ceilings, plenums and ductwork is not included — all offset leaves through the doors and openings entered
- Spaces with offset but no path to the reference zone are flagged; a closed group that balances on its own shows pressures relative to that group
- Undercuts and crack widths are design assumptions; critical rooms should be verified by testing and against their governing standard — ASHRAE 170 (health care), ANSI/ASSP Z9.5 (laboratories), ISO 14644 (cleanrooms)
- A door with zero leakage area is treated as sealed and carries no flow
- One floor plan sheet per project
Reference Standards
ASHRAE Handbook — Fundamentals, Chapter 22: Pipe Design (2021 Edition)
ASME B36.10M — Welded and Seamless Wrought Steel Pipe
ASTM B88 — Standard Specification for Seamless Copper Water Tube
Sizing Method
Uses the Darcy-Weisbach equation with the Colebrook friction factor (ASHRAE Chapter 22), at the mean of the supply and return temperatures. The recommended size is the smallest within ASHRAE’s limits: 2″ and smaller by velocity, 2–4 FPS; over 2″ by friction, 0.75–4 ft/100 ft, with velocity capped at 8 FPS as a design limit for noise. A flow too small to reach 2 FPS in any size takes the smallest size within the upper limits.
Formulas
Darcy-Weisbach
Colebrook-White
Reynolds Number
f = Darcy friction factor
D = Internal diameter (ft)
V = Flow velocity (ft/s)
ε = Absolute roughness (ft)
ν = Kinematic viscosity (ft²/s)
Source: ASHRAE Handbook — Fundamentals 2021, Chapter 22
Pipe Internal Diameters
| Nominal Size | Material | ID (in) | Standard |
|---|---|---|---|
| ½" | Type L Copper | 0.545 | ASTM B88 |
| ¾" | Type L Copper | 0.785 | ASTM B88 |
| 1" | Type L Copper | 1.025 | ASTM B88 |
| 1¼" | Type L Copper | 1.265 | ASTM B88 |
| 1½" | Type L Copper | 1.505 | ASTM B88 |
| 2" | Type L Copper | 1.985 | ASTM B88 |
| 2½" | Sch 40 Black Steel | 2.469 | ASME B36.10M |
| 3" | Sch 40 Black Steel | 3.068 | ASME B36.10M |
| 4" | Sch 40 Black Steel | 4.026 | ASME B36.10M |
| 6" | Sch 40 Black Steel | 6.065 | ASME B36.10M |
| 8" | Sch 40 Black Steel | 7.981 | ASME B36.10M |
| 10" | Sch 40 Black Steel | 10.020 | ASME B36.10M |
| 12" | Sch 40 Black Steel | 11.938 | ASME B36.10M |
Fluid Properties by System Type
| System Type | Supply / Return | ν at mean (ft²/s) |
|---|---|---|
| Chilled Water | 44°F / 54°F | 1.43 × 10⁻⁵ (49°F) |
| Heating Hot Water | 140°F / 120°F | 5.66 × 10⁻⁶ (130°F) |
| High Temp Hot Water | 180°F / 160°F | 4.15 × 10⁻⁶ (170°F) |
| Condenser Water | 85°F / 95°F | 8.40 × 10⁻⁶ (90°F) |
Water viscosity from a curve fit to tabulated water properties (within about 2.5%, 32–212°F) — see Hydronic Head Loss, Fluid Properties.
Glycol Solutions
Propylene and ethylene glycol at 20–50% by volume use tabulated viscosity and density, interpolated to the mean temperature (20–200°F). Viscosity relative to water rises sharply in cold water:
| Solution (by volume) | Freezes | ν ÷ water at 49°F | ν ÷ water at 130°F |
|---|---|---|---|
| 30% propylene glycol | 8°F | 3.4× | 2.2× |
| 30% ethylene glycol | 4°F | 2.2× | 1.9× |
Source: The Dow Chemical Company, Engineering and Operating Guide for DOWFROST and DOWFROST HD (propylene glycol) and for DOWTHERM SR-1 and DOWTHERM 4000 (ethylene glycol), viscosity, density and freezing point tables. The same data appear in ASHRAE Handbook—Fundamentals 2021 Ch. 31 Tables 6 and 9 (ethylene glycol) and 10 and 13 (propylene glycol), by volume percent; every tabulated point here matches them.
Assumptions & Limitations
- Straight pipe only — fitting losses not included (use the Hydronic Head Loss tool)
- Colebrook solved iteratively; laminar flow (Re < 2300) uses f = 64/Re
- Copper ε = 0.000005 ft, steel ε = 0.00015 ft
- The 8 FPS cap over 2″ is a design limit for noise. ASHRAE’s erosion limits (Ch. 22 Table 23) are higher: 15, 14, 13, 12 and 10 FPS at 1,500, 2,000, 3,000, 4,000 and 6,000 operating hours a year, and erosion is not significant below 10 FPS without cavitation
- Pipe schedule follows the project specification and the ASME B31.9 pressure–temperature rating
Reference Standards
ASHRAE Handbook — Fundamentals, 2021 I-P Edition, Chapter 22: Pipe Design
Crane Co. — Flow of Fluids Through Valves, Fittings and Pipe, Technical Paper No. 410 (TP-410)
ASME B36.10M — Welded and Seamless Wrought Steel Pipe, Schedule 40
ASTM B88 — Standard Specification for Seamless Copper Water Tube, Type L
Pipe Friction
Darcy-Weisbach — ASHRAE Ch. 22
Flow Velocity
Colebrook Friction Factor — ASHRAE Ch. 22 (solved iteratively)
ε = 0.00015 ft (carbon steel) · 0.000005 ft (copper Type L)
g = 32.174 ft/s²
Re = Reynolds number = V·D/ν
Fitting Losses
K-Factor Method — ASHRAE Ch. 22
Velocity V is referenced to the upstream pipe for reducers and expansions.
K-Factor Sources
| Fitting Type | Pipe Size Range | Source |
|---|---|---|
| Threaded fittings and valves | Below 2½" | ASHRAE Ch. 22, threaded fitting table (sizes not listed use the nearest listed size) |
| Flanged elbows, returns, valves; tees and LR elbows 2½"–3" | 2½"–12" | ASHRAE Ch. 22, flanged fitting table |
| Welded long-radius elbows (R/D = 1.5) | 4"–24" | ASHRAE Ch. 22 Table 6 (research values at 4, 8 and 12 fps), interpolated on velocity |
| Welded tees (line & branch) | 4"–16" | ASHRAE Ch. 22, welded tee table |
| Reducers & expansions | Tabulated size pairs | ASHRAE Ch. 22 Table 6 (research values at 4, 8 and 12 fps); other pairs K = 0.14, a typical value, unless overridden |
| Standard / 45° elbows, returns, valves | Above 12" | Crane TP-410: 30, 16, 50 fT; gate 8, globe 340, angle 150, swing check 100 fT |
| Tees (line / branch) | Above 16" | Crane TP-410: 20 / 60 fT |
| Ball valve, full port | All sizes | Crane TP-410: 3 fT |
| Butterfly valve | All sizes | Crane TP-410: 45 fT (2"–8"), 35 fT (10"–14"), 25 fT (16"–24") |
| Any valve from manufacturer Cv | All sizes | K = 891·d⁴/Cv² (d in inches; Crane TP-410 Ch. 3) |
fT = fully turbulent friction factor for clean commercial steel pipe, Crane TP-410. Connection type auto-selected: threaded below 2½″, flanged/welded at 2½″ and up. Copper fittings use the steel values for the same size (ASHRAE has no K table for copper fittings and treats copper elbow equivalents as roughly equal to iron). Published K values carry wide uncertainty; use manufacturer data where available.
Crane TP-410 fT Values
| Nominal Pipe Size | fT |
|---|---|
| ½" | 0.027 |
| ¾" | 0.025 |
| 1" | 0.023 |
| 1¼" | 0.022 |
| 1½" | 0.021 |
| 2" | 0.019 |
| 2½"–3" | 0.018 |
| 4" | 0.017 |
| 5" | 0.016 |
| 6" | 0.015 |
| 8"–10" | 0.014 |
| 12"–16" | 0.013 |
| 18"–24" | 0.012 |
Source: Crane Co., Flow of Fluids Through Valves, Fittings and Pipe, Technical Paper No. 410 — friction factors for clean commercial steel pipe with flow in the zone of complete turbulence.
Fluid Properties
Water density and viscosity are computed from curve fits vs. temperature, valid from 32°F to 212°F:
T in °F. The viscosity fit is within about 2.5% of tabulated water properties (NIST / IAPWS) over this range.
Supply / Return Temperature Zones
The calculator accepts separate supply and return temperatures and computes fluid properties independently for each. Components in the circuit are assigned to a zone (supply or return) based on their position relative to user-placed zone-switch markers in the component list. Each component's friction calculation uses the density and viscosity corresponding to its assigned zone.
Zone markers are bidirectional — the user can switch back and forth between supply and return as many times as needed. This supports circuits such as condenser water systems where flow goes from the pump (supply temp) through the chiller (warms up), through return piping (return temp), through the cooling tower (cools back down), and back to the pump (supply temp again).
The viscosity difference between supply and return in typical HVAC systems (44/54°F CHW, 85/95°F CW, 140/120°F HHW) changes pipe friction by about 1–2% — small, but captured.
Worked Example
500 GPM of condenser water at 85°F in 6" Sch 40 steel (ID 6.065", ε = 0.00015 ft):
| Item | Value |
|---|---|
| Velocity, Reynolds number | 5.55 ft/s, Re = 315,500 |
| Friction factor (Colebrook) | f = 0.0169 |
| Pipe friction | 1.60 ft / 100 ft |
| Four welded LR elbows, K = 0.252 (interpolated at 5.55 ft/s) | 0.48 ft |
| Tee, flow through branch, K = 0.56 | 0.27 ft |
| Two butterfly valves, K = 45 × 0.015 = 0.675 | 0.65 ft |
| Table lookups: 8" LR elbow at 7.1 ft/s / 10" at 4.5 ft/s / 8" tee line | K = 0.205 / 0.205 / 0.080 |
Velocity head V²/2g = 0.479 ft. The loop head is the sum of all components; design TDH = loop head × safety factor (default 1.10).
Assumptions & Limitations
- Supply and return temperatures are entered separately; fluid properties are computed at each temperature and applied to components based on their zone in the loop
- Zone assignment is user-controlled via divider markers in the component list — supports multi-zone circuits (e.g., condenser water where flow goes supply → chiller → return → tower → supply)
- Each loop is entered as its pump's index circuit: discharge → most resistant path → suction. Flow carries down the loop and is set only where it changes (at branches)
- Static lift is counted only when the loop is marked as an open system (e.g. condenser water to a cooling tower); in a closed loop it cancels
- Equipment pressure drops are entered from manufacturer data in ft or psi (psi × 144 / ρ at the zone temperature)
- Plain water properties — glycol solutions need corrected density and viscosity (the Hydronic Pipe Sizer includes them)
- Threaded fittings below 2½", flanged/welded at 2½" and up, per common HVAC practice
- Welded long-radius elbow K values are velocity-interpolated across the 4 / 8 / 12 ft/s columns
- Welded tee K values are taken at the tabulated velocity — velocity dependence not accounted for
- Crane K values above the ASHRAE table range are less conservative than the welded data near the table edge — check large fittings against manufacturer data
- Published K values carry wide uncertainty (ASHRAE Ch. 22)
- Safety factor default 1.10 — adjustable by user
Reference Standards
International Plumbing Code (IPC) 2021 — Appendix E: Sizing of Water Piping System
2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 6: Water Supply and Distribution
ASTM B88 — Standard Specification for Seamless Copper Water Tube (Type L)
Sizing Method
Uses Water Supply Fixture Units (WSFU) to estimate peak demand, converted to GPM on Hunter’s demand curves. IPC: Table E103.3(3), using its flushometer column when the load includes flushometer valves. UPC: the Appendix A method — fixture units per Table A 103.1 (Table 610.3 with flushometer valves given their own values: 1.6 GPF water closet 5.0 / 5.0 / 8.0 private / public / assembly, 1.0 GPF urinal 3.0 / 4.0 / 5.0), converted on Chart A 103.1: Curve 1 when the load includes flushometer valves (the same Hunter curve as the IPC flushometer column; Appendix A Example A 108.1, 1365 FU → 252 GPM, reproduces), Curve 2 for flush tanks (as tabulated in the UPC Useful Tables). Table 610.10 belongs to the code’s Table 610.4 sizing method and isn’t used. Pipe size is the smallest that keeps velocity within the limit and leaves the required flow pressure at the most demanding fixture.
Table 610.4, 2025 California Plumbing Code. That edition also permits sizing the meter and building supply straight from its fixture unit table (Section 610.4). Street pressure, at 80% where a regulator sets it (608.2), less ½ psi per foot to the highest outlet (610.8) places the system in the 30–45, 46–60 or over-60 psi range; the first length column at or past the developed length to the most remote outlet is read down to the first meter and building supply pair whose fixture units reach the total. Fixture units are Table 610.3 values, except water closets and urinals with flushometer valves, which count by Table 610.10 in accumulative values (40, 70, 90, 105, 115 + 10 each for water closets; 20, 35, 45, 53, 58 + 5 each for urinals). Branches are sized the same way from the fixture units they serve (610.9); no building supply is smaller than ¾″. Below 30 psi, past 1,000 ft or past the last row, the Appendix A method applies.
Pressure Drop Formula
0.4335 = Conversion factor from ft w.g. to PSI
ν = 1.217 × 10⁻⁵ ft²/s (water at 60°F)
ε = 0.000005 ft (Type L Copper)
Pressure Budget
P_elevation = Height × 0.433 PSI/ft
P_system = Meter + backflow preventer + valves, from manufacturer data (default 10 PSI)
P_friction = Darcy-Weisbach loss over the developed length on new, smooth copper, or Hazen-Williams C = 130 for aged pipe (UPC 610.6 asks for aged-pipe friction unless no loss with age is expected; new copper runs about 6–8% below the code friction charts)
Method: IPC 2021 Appendix E (Section E103.3); required flow pressure at the fixture from IPC Table 604.3 or UPC Section 608.1.
IPC 2021 Fixture Unit Values (selected)
| Fixture | WSFU (total) | Min Pipe | Flow PSI |
|---|---|---|---|
| Water closet — public, flushometer valve | 10.0 | 1" | 35 (siphonic) |
| Water closet — private, flushometer valve | 6.0 | 1" | 35 (siphonic) |
| Water closet — public, flush tank | 5.0 | 3/8" | 20 |
| Water closet — private, flush tank | 2.2 | 3/8" | 20 |
| Urinal — public, ¾" flushometer valve | 5.0 | ¾" | 25 |
| Lavatory — public | 2.0 | 3/8" | 8 |
| Lavatory — private | 0.7 | 3/8" | 8 |
| Shower head — public / private | 4.0 / 1.4 | ½" | 20 (mixing valve) |
| Kitchen sink — hotel, restaurant | 4.0 | ½" | — |
| Service sink — offices, etc. | 3.0 | ½" | 8 |
| Drinking fountain | 0.25 | 3/8" | 8 |
Source: IPC 2021 Table E103.3(2) (loads), Table 604.5 (minimum pipe), Table 604.3 (flow pressure). The tools carry all 27 rows of Table E103.3(2) and all of UPC Table 610.3, with UPC flushometers per Appendix A Table A 103.1. Values checked against the 2021 IPC and the 2025 California Plumbing Code (2024 UPC base); the California code lists a mobile home at 6.0 fixture units where the UPC lists 12.0.
Assumptions & Limitations
- Type L Copper used for all domestic water sizing
- Water properties at 60°F; for hot water this slightly overstates friction, which is conservative
- Straight pipe friction only — enter a developed length that includes an allowance for fittings
- System losses default to 10 PSI; a reduced-pressure backflow preventer alone is often 10–15 PSI, so use manufacturer data
- Loads above the end of the code demand table are extrapolated and flagged
- IPC and UPC WSFU values differ — select correct code for your jurisdiction
- UPC 610.12.1 limits copper to 8 FPS cold and 5 FPS hot; the IPC sets no fixed velocity limit
- UPC minimum residual pressure is 15 PSI (Section 608.1); fixtures requiring more use the manufacturer’s value
Reference Standards
International Plumbing Code (IPC) 2021 — Appendix E
2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 6
AWWA Manual M22, Tables 5.6–5.8 — displacement (C700), compound (C702) and Class II turbine meter capacities and average pressure losses
AWWA Manual M22 — Sizing Water Service Lines and Meters (meter capacities, design at 80% of maximum, average losses), as tabulated in the ASPE Data Book Vol. 2, Tables 5-1 and 5-2
Sizing Method
Fixture counts are multiplied by their WSFU values per IPC / UPC tables, totaled, and converted to peak GPM on the code demand curves. UPC fixtures use the Private, Public or Assembly column of Table 610.3, with flushometer valves at their Appendix A Table A 103.1 values, converted on Appendix A Chart A 103.1. Continuous loads (irrigation, cooling tower makeup, etc.) are added directly. The service pipe is sized for velocity ≤ 8 FPS (the UPC 610.12.1 limit for copper on cold water) and the meter is the smallest with the peak flow within 80% of its safe maximum operating capacity (AWWA M22).
Demand Curve Selection
If any flushometer water closets or urinals are entered, the flushometer curve is used for the total and cold-water load (IPC Table E103.3(3) flushometer column; UPC Appendix A Curve 1); otherwise the flush-tank curve. This is conservative where flushometers are a small part of the load (ASPE suggests computing both and using the greater, which for the same fixture units is the flushometer curve). Hot-water demand uses the flush-tank curve by default, since flushometers draw cold water only (ASPE practice); the IPC’s own Appendix E sample problem applies the system’s curve to the hot side too, which the tool offers as an option.
Validation
| Load | Fixture units | Demand |
|---|---|---|
| IPC public: 10 flushometer water closets, 5 ¾" flushometer urinals, 10 lavatories | 100 + 25 + 20 = 145 WSFU | 78.0 GPM (flushometer column) |
| IPC: 400 WSFU, flushometer / flush tank | 400 WSFU | 127 / 105 GPM |
| UPC public: 10 1.6 GPF flushometer water closets, 5 1.0 GPF flushometer urinals, 10 lavatories (Table A 103.1) | 50 + 20 + 10 = 80 FU | 61.2 GPM (Curve 1) |
| Meter at 78 GPM | 1½" displacement, 100 GPM max (78 ≤ 80% of 100) | Loss ≈ 15 × (78/100)² = 9.1 PSI |
Demand by linear interpolation in the code tables (the IPC sample problem rounds up to the next table row instead, about 1.5% higher). Below about 50 fixture units the UPC flush-tank curve runs under the IPC’s, as the UPC chart does.
Fixtures Not Listed in the Code Tables
Fixtures that neither code lists, such as a three-compartment sink, can be added with a user-entered load. IPC Table E103.3(2) note a and UPC Table 610.3 note 2 both direct the designer to assign such fixtures a load by comparison with listed fixtures of similar flow and use. For example, a three-compartment sink is commonly compared with the IPC kitchen sink, hotel or restaurant (4.0 WSFU), or the UPC service sink (3 FU public). The assigned value is the designer’s judgment and should be confirmed with the authority having jurisdiction.
Meter Capacities
| Meter Size | Type | Safe Max (GPM) | Continuous (GPM) |
|---|---|---|---|
| ⅝" | Displacement | 20 | 10 |
| ¾" | Displacement | 30 | 15 |
| 1" | Displacement | 50 | 25 |
| 1½" | Displacement | 100 | 50 |
| 2" | Displacement | 160 | 80 |
| 3" | Compound | 320 | 160 |
| 4" | Compound | 500 | 250 |
| 6" | Compound | 1000 | 500 |
| 8" | Compound | 1600 | 800 |
| 2"–12" | Turbine, Class II | 160 – 5,000 | 100 – 3,300 |
Source: AWWA Manual M22, Tables 5.6 (displacement), 5.7 (compound) and 5.8 (Class II turbine), averages of 1990-model meters. M22 recommends designing to 80% of the maximum capacity; the meter is selected at 80%. The displacement and compound capacities match the ASPE Data Book reprint used before. Meter type and size are set by the water utility.
Pressure Budget
P_elevation = Elevation × 0.433 PSI/ft
P_pipe_friction = Darcy-Weisbach loss over service line length
P_meter = P_max × (Q / Q_max)² — P_max is 15 PSI for displacement meters (the AWWA C700 limit; M22’s averages are about 9–11 PSI, so this is conservative) and M22’s averages for compound meters (7.2, 6.2, 8.4 and 14.5 PSI at 3", 4", 6" and 8") and turbine meters (4.0 to 1.7 PSI); actual losses vary by make, so use the utility’s or manufacturer’s curve
Assumptions & Limitations
- Service pipe sized as Type L Copper, velocity ≤ 8 FPS
- Meter sized with the peak GPM within 80% of its safe maximum operating capacity (AWWA M22); a continuous load above the meter’s continuous rating is flagged — verify with the water utility
- The pressure left at the building entry is reported for comparison with the building’s needs; it is not judged against a fixed threshold
- Emergency shower ANSI Z358.1 minimum 20 GPM — add to continuous load if simultaneous operation required
- Eyewash, ice makers, coffee makers and other unlisted fixtures — enter as not-listed fixtures with a load assigned by comparison
- Continuous loads added directly to fixture GPM before service sizing
Reference Standards
International Plumbing Code (IPC) 2021 — Chapter 7 Sanitary Drainage (Tables 709.1, 709.2, 710.1(1), 710.1(2); Sections 704.2, 709.3, 711) and Chapter 9 Vents (Table 906.1; Sections 904.2, 906.1, 908)
2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 7 (Tables 702.1, 702.1(1), 702.2, 703.2, 717.1; Sections 702.3, 703)
Sizing Method
Fixture counts are multiplied by their drainage fixture units and totaled, with continuous flow at 2 fixture units per gpm in both codes. Each pipe is the smallest size whose table capacity reaches the total. IPC: the building drain or sewer from Table 710.1(1) at the chosen slope, 3″ or larger with a water closet (note a); the horizontal branch and stack from Table 710.1(2), the stack by its number of branch intervals (three or fewer, or more) and also by the most that enters one interval; branches and stacks with a water closet are 3″ or larger, since a 3″ closet outlet can’t drain into smaller pipe (704.2); the stack vent or vent stack from Table 906.1 for the stack size, load and developed length, never under half the stack or 1¼″ (906.1). Five or more branch intervals call for a vent stack (904.2), more than ten for relief vents (908). UPC: Table 702.1 values for the private, public or assembly column, with three or more clothes washers in a battery at 6 each (note 5); drains, stacks and vents from Table 703.2 — horizontal at ¼″ per foot or 0.8 of that at ⅛″ for 4″ and up (note 5), stacks within the listed length, vents within their units and length and never under 1¼″ or half the drain served (note 6); water closets and six-unit traps on 3″ or larger, six at most on 3″ (notes 3 and 4); up to eight public lavatories on 1½″ (note 7). Past 6″, the building sewer comes from Table 717.1, whose minimum load for each slope is flagged when the load falls short.
Validation
| Load | Fixture units | Sizes |
|---|---|---|
| IPC: 20 public 1.6 gpf water closets, 20 lavatories; ¼″ slope, 3 intervals, 100 ft vent | 80 + 20 = 100 dfu | Drain 4″ (216), branch 4″ (160), stack 5″ (one-interval limit 90 on 4″), vent 4″ |
| IPC: 60 bathroom groups (1.6 gpf); 6 intervals, 50 dfu per interval, 120 ft vent | 300 dfu | Stack 4″ (500, 90 per interval), vent 3″ (170 ft); vent stack required |
| UPC public: 10 flushometer water closets, 10 lavatories, 4 1.0 gpf urinals; ¼″ slope, 40 ft stack, 100 ft vent | 40 + 10 + 8 = 58 FU | Drain 4″ (216), stack 4″ (256), vent 3″ (84 units, 212 ft) |
| UPC: 4 domestic clothes washers in a battery | 4 × 6 = 24 FU | Drain 3″ (35), vent 2″ (24 units) |
| UPC public: 150 flushometer water closets at ⅛″ | 600 FU | 8″ sewer (2,800), flagged under its 625 FU minimum at ⅛″ |
Assumptions & Limitations
- One run carries the whole load entered; size each branch and stack with the load it carries, and never reduce a drain in the direction of flow
- Stack offsets in buildings of five stories or more (IPC 711) and the UPC vent rules beyond Table 703.2 are left to the designer
- Individual, branch and circuit vents are not sized; the vent shown is the stack vent or vent stack
- Fixtures not listed take the value for their trap size: IPC Table 709.2, or UPC Section 702.1 within the Table 702.1(1) limit
Reference Standards
International Plumbing Code (IPC) 2021 — Chapter 11 Storm Drainage (Equation 11-1; Tables 1106.2, 1106.3, 1106.6; Sections 1105.2, 1106.4, 1108)
2024 Uniform Plumbing Code (UPC), as adopted in the 2025 California Plumbing Code — Chapter 11 (Tables 1103.1, 1103.2, 1103.3; Sections 1101.12, 1103.4, 1104.1)
Sizing Method
The design rainfall is the 100-year, 1-hour rate the user enters from the code’s map or table or local data. IPC: flow is gpm = R × A × 0.0104 (Eq. 11-1) on the projected roof plus half of any wall draining onto it (1106.4). With the roof shared equally among the drains, each roof drain and vertical conductor is the smallest size in Table 1106.2’s vertical column for one drain’s flow, each leader the smallest in Table 1106.3 (with its rectangular equivalents), and the horizontal storm drain the smallest in Table 1106.2 at the slope for the total flow plus any continuous flow. Gutters come from Table 1106.6 at the gutter slope. UPC: each roof drain, leader or vertical pipe is the smallest in Table 1103.1 whose allowable area at the rate covers the area one drain serves; the horizontal storm drain comes from Table 1103.2 at 1/8, 1/4 or 1/2 in/ft; semicircular gutters from Table 1103.3. At rates a table doesn’t list, the allowable area is the 1 in/h value divided by the rate (notes 2). Walls add 50% (one wall) or 35% (two adjacent walls of equal height) of their area (1103.4); continuous flow counts 24 sq ft per gpm at 4 in/h (1104.1). A secondary system combined with the primary is sized at double the rate (1101.12.2.2.2). Scuppers are at least 4″ high and as wide as the circumference of the roof drain for the area served (IPC 1108.3, UPC 1101.12.2.1).
Validation
| Case | Load | Sizes |
|---|---|---|
| IPC: 20,000 sq ft at 3 in/h, 4 drains, 1/8″ slope | 3 × 20,000 × 0.0104 = 624 gpm; 156 gpm per drain | Conductor 4″ (180), leader 4″ (192), horizontal 8″ (714 gpm) |
| UPC: the same roof | 5,000 sq ft per drain | Vertical 4″ (6,130 sq ft at 3 in/h), horizontal 10″ at 1/8″ (27,600) |
| UPC: 10,000 sq ft at 2.5 in/h, 2 drains, 1/4″, 10 gpm continuous | 5,000 sq ft per drain; 10,000 + 10 × 96 ÷ 2.5 = 10,384 sq ft | Vertical 4″ (18,400 ÷ 2.5 = 7,360), horizontal 6″ (30,200 ÷ 2.5 = 12,080) |
| UPC: 20,000 sq ft, 4 drains, combined secondary at 3 in/h | Sized at 6 in/h | Vertical 5″ (5,765), horizontal 12″ at 1/8″ (22,200) |
Assumptions & Limitations
- The roof is shared equally among the drains entered; size each drain and branch with the area it actually serves
- Roof drains must also be checked against the manufacturer’s published flow at the design head
- Ponding depth, overflow elevations and roof structure are for the structural design (IBC 1611); siphonic and controlled-flow systems are not covered
Reference Standards
2025 California Plumbing Code (2024 UPC) Chapter 12 Fuel Gas Piping, which carries NFPA 54 Chapter 6: Sections 1214 and 1215, Tables 1208.3.1, 1215.2(1)–(36) and 1215.3, Equations 1215.3(1) and (2)
NFPA 54 National Fuel Gas Code (2006 edition consulted for comparison)
Sizing Method
Longest length method (1215.1.1). Each section is sized for the load it carries, read at the length from the meter or regulator to the most remote outlet, rounded up to the next length row of the tables. Natural gas loads are converted to cfh at the heating value entered (1214.3); propane is sized in thousands of Btu/h, as its tables are. Capacities come from the Section 1215.3 sizing equations in their flow form, Q = 2313 D2.623 (ΔH / (Cr L))0.541 below 1.5 psi and Q = 2237 D2.623 [(P1² − P2²) Y / (Cr L)]0.541 at 1.5 psi and above, with Table 1215.3’s Cr and Y and each table’s inside diameters, rounded to three figures as the tables print them. Every cell of Tables 1215.2(1), (5), (7), (8), (9) and (27) agrees, and Tables 1215.2(2), (3), (11), (19)–(21) and (24)–(26) agree to within one unit in the last printed figure (for example 859 against 860). Tables 1215.2(4) and (6), natural gas in Schedule 40 pipe at 2 psi and 5 psi, print 5–11% lower capacities than the equation; for ½″–4″ at those pressures the tool reads the printed tables. Propane converts at 2.488 MBH per cfh below 1.5 psi and 2.49 above, the factors that reproduce the propane tables. Other pressures and drops use the equations directly, as Section 1215.1 permits.
Validation
| Case | Load | Size |
|---|---|---|
| CPC Figure 1215.1.1 example: 1,100 Btu/cf, 0.5 in. w.c. drop, 60 ft | Outlets 32, 3, 59 and 136 cfh; sections 35, 94 and 230 cfh | Outlets ½″, ½″, ½″, ¾″; sections ½″, ¾″ and 1″, as the example |
| Natural gas, 2 psi, 1 psi drop, ½″ Schedule 40 at 60 ft | — | 615 cfh, Table 1215.2(4) |
| Propane, 10 psi, 1 psi drop, ½″ Schedule 40 at 10 ft | — | 3,320 MBH, Table 1215.2(24) |
| Propane, 11 in. w.c., 0.5 in. drop, ½″ Schedule 40 at 60 ft | — | 110 MBH, Table 1215.2(27) |
Assumptions & Limitations
- Specific gravity 0.60 for natural gas and 1.50 for propane, as the tables; other gases need the supplier’s conversion factors (1214.1)
- Appliance inputs default to Table 1208.3.1’s approximate values; the nameplate input governs (1214.2)
- The branch and hybrid pressure methods, regulator losses and CSST are not covered; size CSST from the manufacturer’s tables
- Plastic pipe is for outdoor underground use only (1210.1.7)
Reference Standards
2020 ASHRAE Handbook — HVAC Systems and Equipment, Chapter 13 Hydronic Heating and Cooling, Equations (13)–(15) and Example 1
ASPE Plumbing Engineering Design Handbook Vol. 2 (2010), Chapter 5, Equation 5-6 and Tables 5-10 and 5-11
2025 California Plumbing Code Section 608.3 and IPC 2021 Section 607.3 (thermal expansion control)
Sizing Method
Hydronic: the net expansion is the water’s v2/v1 − 1 between the lower and higher temperatures less the piping’s 3αΔt (α = 6.5 × 10⁻⁶ in/in·°F for steel, 9.5 × 10⁻⁶ for copper). The tank volume is the system volume times the net expansion divided by (Pa/P1 − Pa/P2) for a plain steel tank with an air/water interface, divided by (1 − P1/P2) for a diaphragm tank, or doubled for an open tank, with absolute pressures at 14.7 psia atmospheric. The acceptance volume is the net expansion; a diaphragm tank is precharged to the fill pressure. Water heaters: ASPE Equation 5-6, the heater and piping volume times the density ratio (d1 − d2)/d2 times p2/(p2 − p1) in absolute pressure, precharged to the minimum supply pressure. Water density is from Kell’s equation (1975), which reproduces ASHRAE Fundamentals Chapter 1 Table 3 specific volumes to their four printed figures and ASPE Table 5-10 within 0.0002.
Validation
| Case | Handbook | Tool |
|---|---|---|
| ASHRAE Example 1: 3,000 gal, 40 to 220°F, 10 and 25 psig, steel, plain steel tank | 578 gal | 580 gal |
| The same with a diaphragm tank | 344 gal | 345 gal |
| ASPE: 40 to 140°F expansion ratio (Table 5-10) | 0.0171 | 0.0171 |
| ASPE: 40 and 100 psig pressure ratio (Table 5-11) | 1.91 | 1.91 |
The handbook example uses specific volumes rounded to four figures (0.01602 and 0.01677 ft³/lb); unrounded, the same example gives 580 and 345 gal.
Assumptions & Limitations
- Pressures are at the tank connection; the fill pressure must keep the highest point positive, and the maximum stays below the relief valve setting
- Glycol solutions expand differently from water; use the fluid manufacturer’s data
- The system volume estimate counts pipe only; add equipment volumes from manufacturer’s data
Reference Standards
2023 ASHRAE Handbook — HVAC Applications, Chapter 51 Service Water Heating, Table 13: Hot-Water Demand per Fixture for Various Types of Buildings (p. 51.29). Values also checked against ASPE Plumbing Engineering Design Handbook Vol. 2 (2010), Chapter 6, Table 6-1.
Georgia Department of Public Health — Food Service Establishment Manual for Design, Installation and Construction (Rules and Regulations, DPH Chapter 511-6-1), Section K: Hot Water Supply Requirements, Table K-1 and worked examples (2013). Table K-1 is adapted from the FDA Plan Review for Food Establishments guidance (2008).
Heaters and Areas
A project can hold any number of water heaters, each with a tag, the area it serves, its own storage temperature, fuel and efficiency. Each heater serves one or more areas, and each area has a category: one of the ten ASHRAE building types, or food service. Fixtures are entered under the area they belong to, so a mixed-use building is sized area by area with the right values for each use.
Areas on one heater are combined by heat, because building areas are tabulated at 140°F and food service fixtures at their delivery temperatures (100–140°F). Adding areas assumes their peak hours coincide, which is conservative.
Food Service Areas
Kitchens use the Georgia DPH Table K-1 fixture method instead of an ASHRAE building column. Each fixture’s peak hourly demand is added with no diversity factor, and recovery must meet that peak hour. Health departments differ — other jurisdictions may require their own tables, so confirm the method with the local health authority.
| Fixture | Peak hourly demand |
|---|---|
| Handwashing sink (including restrooms) | 5 gph |
| Food preparation sink | 5 gph per compartment |
| Hand-operated pre-rinse sprayer | 45 gph |
| Mop / utility sink, hose reel | 10 gph |
| Clothes washer | 15 gph |
| Shower head | 14 gph (Section K §2.I lists 35 gph) |
| Hose bibb used for cleaning | 35 gph |
| 3-compartment, bar and utensil soak sinks | L × W × D (in) × compartments × 0.003255 |
| Warewashing machine | final-rinse gph × 0.70 |
- Compartment-sink factor 0.003255 gal/in³ is a 75% fill, allowing for submerged utensils; × 0.80 where only single-service tableware is used
- Low-flow hand sinks, pre-rinse sprayers and showers: table gph × rated gpm ÷ standard gpm (2.2, 3.5 and 2.5 gpm)
- Delivery temperatures follow Section K’s worked examples: hand sinks 100°F, showers 120°F, warewashing sinks and other fixtures 110°F, warewashing machine supply 140°F
- Fixtures not in Table K-1 (for example a garbage can washer) are entered as unlisted fixtures from manufacturer data
- Hot-water sanitizing machines need a booster from 140°F to 180°F: booster output = machine gph × 8.33 × 40°F, sized separately from the main heater. The tool shows output (equal to input for an electric booster); a gas booster’s input is output ÷ efficiency, and Georgia’s worked example uses 75%
- The method sizes recovery only; minimum storage for kitchens is set by the local health authority
Sizing Method
Building areas (ASHRAE fixture method):
The probable maximum demand is the heater recovery rate. The handbook notes that total demand is never less than the demand of the largest single fixture, and that the demand factors are not valid for very few fixtures, so the tool uses the larger of the two and says when the largest fixture governs. Fixture demand, demand factor and storage capacity factor come from the table column for the building type. Heat input is output divided by the heater’s thermal efficiency; electric heaters show input in kW (3,412 Btu/h per kW).
Storage Temperature Adjustment
The table is based on a final temperature of 140°F. For other storage temperatures, recovery is scaled so the delivered heat is unchanged, and storage scales with it (stored water at a lower temperature delivers less heat per gallon):
Storing at 140°F with mixing valves at the fixtures keeps the table basis and helps control Legionella growth.
Assumptions & Limitations
- Applies to storage-type heaters; instantaneous and semi-instantaneous heaters need peak-flow sizing instead
- Dishwasher demand uses the manufacturer’s value when entered, otherwise the top of the table range (table note a)
- Fixtures not listed for a building type are excluded; enter them as unlisted fixtures with a manufacturer or comparison value
- Table data predates low-flow fixtures; shower demand in particular may be conservative
- Demand and storage factors may be overridden where the building type is not listed or historical data supports it
- Recirculation heat loss is not included
- Each heater is sized for the areas assigned to it; heaters are not combined
Reference Standards
ASHRAE Handbook — Fundamentals (2021): Chapter 18, Nonresidential Cooling and Heating Load Calculations (radiant time series method, heating loads, system effects); Chapter 14, Climatic Design Information (solar position, clear-sky model, design-day profiles); Chapter 15, Fenestration (angular SHGC, interior attenuation, exterior shading); Chapter 1, Psychrometrics.
ANSI/ASHRAE Standard 62.1 (ventilation rate procedure, multiple-zone system ventilation efficiency) and ANSI/ASHRAE/ASHE Standard 170 (minimum air changes for healthcare spaces).
Cooling: Radiant Time Series
Each space is calculated hour by hour on a design day for the 21st of every month; the peak is the largest hourly sensible load of the 288. Every heat gain is split into radiant and convective parts (Ch. 18 Table 14). The convective part is load in the same hour; the radiant part is spread over the following hours by the space’s radiant time series — the solar series for beam sun through unshaded glass, the nonsolar series for everything else.
- Walls and roofs: sol-air temperature on each surface, then the conduction time series of the construction: q(θ) = U·A·Σ cⱼ (t_sol-air(θ − j) − t_room)
- Conduction time series are computed from the construction’s own layers (finite-volume model of the layers, steady periodic) rather than taken from a table of representative walls
- Radiant time series are computed for each space by a heat balance of its own surfaces — exterior walls, glass, partitions, floor slab shared with the floor below, ceiling, roof and furnishings — instead of one prototype for the whole project
- Windows: beam SHGC at the hour’s incidence angle and diffuse SHGC from the rated SHGC and pane count (Fresnel transmittance with path-length absorption), interior shades by their attenuation coefficients, overhangs and fins by the sunlit area
- Lighting splits between the room and the ceiling plenum by luminaire (Ch. 18 Table 3); people by activity (Table 1); equipment with or without cooling fans; process loads with their own radiant share and schedule
- Infiltration and outdoor air: 1.10 · CFM · Δt sensible and 4840 · CFM · ΔW latent, corrected for elevation
Heating and Systems
Heating is steady state at the heating design temperature: U·A·Δt for every exterior surface, slab edges by F-factor × exposed perimeter, partitions to unconditioned space, below-grade surfaces to the ground temperature, and infiltration — with no credit for sun, people, lights or equipment.
An air system’s coil load is the coincident (block) load of its spaces each hour, plus the return plenum (lighting and roof heat), supply and return duct gains, duct leakage, supply and return fan heat (brake horsepower from total static and fan efficiency) and the outdoor air (less any energy recovery). Outdoor air follows the 62.1 multiple-zone procedure: Vou from people and area rates with occupant diversity, zone Voz = Vbz/Ez, and Ev from the zone with the highest outdoor air fraction; VAV box minimums are taken at least 1.5 × Voz. The coil-leaving state is checked against saturation, which flags supply temperatures too warm to meet the room humidity.
Envelope from Revit
- Exterior walls are the walls of Exterior function along each space’s boundary where no other space is across; interior-function walls are never exterior. Wall area is the wall’s height in the storey (floor to floor), less its windows and doors
- Constructions come from the Revit type’s layers, outside to inside: each material’s thermal asset (conductivity, density, specific heat) where it has one, otherwise a typical material matched by name. Air spaces and empty stud layers count as air spaces (R-0.87); insulation between steel studs counts at 45% of its R-value (ASHRAE 90.1 Appendix A). Revit doesn’t model framing, so check the U-factor of framed walls
- Windows, doors and skylights by type and size; a type’s U-factor and SHGC are used when they are set in Revit (Revit’s stock single-glazing default is ignored). Curtain walls give their glass from the share of glazed panels, with door panels as doors
- When set, the share of an exterior wall above the ceiling (wall height less ceiling height, over wall height) goes to the plenum and the return air rather than the room. Slab edge gain in cooling, when set, is F-factor × exposed perimeter × (outdoor dry bulb − room), off by default
- Ceiling height, and the roof or floor above, from the ceiling and roof found straight above each space; a roof keeps its slope and the ceiling below it (with a ceiling air space) becomes part of the roof assembly
Air Balance
Required supply is the larger of the space’s load airflow and its minimum air changes; design supply rounds that up to the chosen increment unless entered. Return = supply + transfer in − exhaust − transfer out − offset, and not less than zero, so a space whose exhaust exceeds its supply shows a negative net. In heating, a VAV space runs the larger of its heating airflow and its box minimum; other systems keep their cooling airflow. The CO₂ figure on the ventilation schedule is a steady-state comparison, V = N / (Cs − Co), with an editable generation rate, and doesn’t set the design.
Validation
ASHRAE Fundamentals 2021 Ch. 18 worked example: a corner office, 130 ft², spandrel and brick walls, two windows with blinds and a 5 ft overhang, roof above (Btu/h):
| Result | Handbook | Handbook tables | Computed by MEP Calcs |
|---|---|---|---|
| July 3:00 PM | 3,158 | 3,152 | 3,250 |
| True peak (September 5:00 PM) | 3,916 | 3,905 | 4,004 |
| Peak month and hour, four orientations | Sep 17 · Sep 17 · Jul 15 · Jul 13 | all match | all match |
| Block load of the four offices | 12,793 | 12,888 | 13,310 |
| Heating | 4,033 | 4,033 | 4,033 |
- “Handbook tables” runs the engine with the chapter’s own conduction and radiant time series and design-day temperatures; it lands within 0.3% (the example’s brick and roof conduction series are not stated in the chapter)
- “Computed” uses the method as built — every conduction and radiant series from the actual constructions and room — and runs 2–4% above the printed values, the conservative side, consistent with ASHRAE’s own comparison of RTS with the heat balance method
- Conduction time series computed from layers match all 103 walls and roofs of Ch. 18 Tables 16–17 within 1 percentage point per hour, except one wall the handbook misprints (Wall 5)
- Room heat balance radiant series follow Ch. 18 Tables 19–20 for the representative zones of Table 21 within a few percentage points per hour (medium-weight, carpeted, 50% glass: 48% vs 49% in the first hour)
- Solar geometry and clear-sky irradiance reproduce Ch. 14 Examples 2–8 (sun angle 68.62°, beam 244 Btu/h·ft², wall irradiance 88.8 / 22.4 / 27.9); design-day temperatures reproduce Ch. 14 Table 8
- Angular SHGC from the rated SHGC and pane count reproduces the Ch. 15 values for the example glass within 0.01 at every angle
Assumptions & Limitations
- Design weather is entered from the station’s climatic design data; months not entered are estimated from the peak month
- Design days are clear-sky and steady periodic (each day repeats); weekend and holiday schedules don’t apply
- Below-grade surfaces are left out of cooling, as the chapter recommends; floors over conditioned space carry no load
- The multiple-zone outdoor air uses the zone with the highest outdoor air fraction; systems with DOAS give their terminal units no outdoor air
- Safety factors, duct gains and leakage are as entered for each system; none are added by default
Intended Use
MEP Calcs is intended as a quick-check and preliminary sizing tool for licensed MEP engineers and designers. Results should be reviewed by a qualified engineer before use on construction documents. All calculations are provided for informational purposes only.
Version History
Questions or Corrections
If you find an error in any calculation or have a suggestion, please reach out at hello@mepcalcs.com