Psychrometric Calculator
Moist air properties, mixing and coil loads per ASHRAE Fundamentals Chapter 1
14.696 psia standard pressure (Eq. 3).
Perfect-gas relations of the 2021 ASHRAE Handbook — Fundamentals, Chapter 1, Section 8: saturation pressure by IAPWS-IF97 (Eq. 5) above 32°F and IAPWS 2008 (Eq. 6) below, humidity ratio Eq. 21, specific volume Eq. 28, enthalpy Eq. 32, wet bulb Eq. 35 (Eq. 37 below freezing), dew point Eq. 39, pressure at elevation Eq. 3. Mixing by Eq. 46 on mass flow, cfm ÷ specific volume. The coil load is Eq. 45, the enthalpy change less the condensate leaving at the leaving air temperature; the sensible part is the dry-bulb change at the leaving humidity ratio. These relations agree with the handbook’s chart-read examples to within about half a percent.