Duct Sizer

Duct sizing per ASHRAE Fundamentals and SMACNA

Preset
CFM
FPM
in. wg
Size
inches
Velocity
FPM
Static loss
in. wg / 100 ft
Every round size at 1,000 CFMHover a size · click to pick it
Velocity · FPMlimit 800 FPM
01,0002,000
Friction · in. wg / 100 ftlimit 0.08 in. wg / 100 ft
0.000.200.404Ø8Ø12Ø16Ø20Ø24Ø28Ø32Ø36Ø40Ø44Ø48Ø
Round duct diameter, inches

Each size is the smallest that meets both limits; click a size to type it, or use ▲▼ to step — velocity and friction update at the fixed airflow. In the chart, the tinted band is past the limit; click a size to use it above. Aspect ratios over 4:1 are flagged (SMACNA §2.8 recommends staying near 1:1). Friction by Darcy-Weisbach with the Colebrook friction factor on the actual shape (hydraulic diameter), standard air, ε = 0.0003 ft (galvanized steel) — ASHRAE Handbook—Fundamentals 2021, Ch. 21.

Rectangular to round
in
in

20in round

Exact 18.28

Round to rectangular
in
in

20in side 2

Exact 18.04

Equal friction at equal airflow, De = 1.30 (ab)^0.625 / (a + b)^0.25, ASHRAE Handbook—Fundamentals 2021, Ch. 21, rounded up to the next even inch. The two sizes won’t have the same area or velocity.

Typical Design Velocities

ApplicationVelocity (FPM)
Low-pressure supply mains800–1200
Low-pressure supply branches600–1000
Branch to diffuser / grille400–600
Medium-pressure supply mains1500–2500
High-pressure supply mains2500–3500
Return and general exhaust700–1500
Grease exhaust1500–2500 (code minimum 500, IMC 506.3.4)

Common design practice, not code limits. Where noise governs, use the duct velocity limits in ASHRAE Handbook—Fundamentals 2021, Ch. 21 Table 12 (from HVAC Applications, Noise and Vibration Control).

SMACNA Pressure Classes

ClassOperating Pressure
½" w.g.Up to ½" w.g.
1" w.g.Over ½" up to 1"
2" w.g.Over 1" up to 2"
3" w.g.Over 2" up to 3"
4" w.g.Over 3" up to 4"
6" w.g.Over 4" up to 6"
10" w.g.Over 6" up to 10"

Pressure classes: SMACNA HVAC Systems Duct Design, 4th ed., Table 4-1.