Duct Sizer
Duct sizing per ASHRAE Fundamentals and SMACNA
Each size is the smallest that meets both limits; click a size to type it, or use ▲▼ to step — velocity and friction update at the fixed airflow. In the chart, the tinted band is past the limit; click a size to use it above. Aspect ratios over 4:1 are flagged (SMACNA §2.8 recommends staying near 1:1). Friction by Darcy-Weisbach with the Colebrook friction factor on the actual shape (hydraulic diameter), standard air, ε = 0.0003 ft (galvanized steel) — ASHRAE Handbook—Fundamentals 2021, Ch. 21.
20in round
Exact 18.28
20in side 2
Exact 18.04
Equal friction at equal airflow, De = 1.30 (ab)^0.625 / (a + b)^0.25, ASHRAE Handbook—Fundamentals 2021, Ch. 21, rounded up to the next even inch. The two sizes won’t have the same area or velocity.
Typical Design Velocities
Common design practice, not code limits. Where noise governs, use the duct velocity limits in ASHRAE Handbook—Fundamentals 2021, Ch. 21 Table 12 (from HVAC Applications, Noise and Vibration Control).
SMACNA Pressure Classes
Pressure classes: SMACNA HVAC Systems Duct Design, 4th ed., Table 4-1.