Duct Static Pressure Loss

External static pressure for fan selection · ASHRAE Fundamentals Ch. 21 and the ASHRAE Duct Fitting Database

Air density ρ = 0.0750 lb/ft³ (standard air)
Fan discharge → farthest diffuser · list every duct run, fitting and piece of equipment the air passes through on the index run, in order
#ComponentCFMSizeFPMPvCLossΣ

Enter the airflow, then add the ducts, fittings and equipment below in the order the air meets them. The run is drawn as you go.

Add to Supply Run 1

Enter adds · hover between rows to insert · ✎ or click a piece in the drawing to edit
Friction by Darcy-Weisbach with the Colebrook friction factor at the duct’s hydraulic diameter. Enter the actual size — rectangular and flat oval are handled directly. For lined duct, enter the inside (net) dimensions after the liner.
Enter the run’s airflow and pieces first; the fan laws start from its design point (no airflow yet).
Straight duct: Δp = 12 f (L / Dh) pv — ASHRAE Handbook—Fundamentals Ch. 21, with Dh = 4A/P
Friction factor: Colebrook, 1/√f = −2 log(12ε / 3.7Dh + 2.51 / Re√f), Ch. 21 Eq. (19), solved by iteration; Re = 8.50 Dh V for standard air (Eq. 21)
Velocity pressure: pv = ρ (V / 1097)²; standard air gives (V / 4005)²
Fittings: Δp = C pv; C values are representative entries from the ASHRAE Duct Fitting Database (C = common, S = supply, E = exhaust/return; D = round, R = rectangular; diverging junctions from HoF Ch. 21 Tables 10–11) and SMACNA HVAC Systems Duct Design Appendix A (elbows with vanes, offsets, contractions, dampers). Branch values are referenced to the branch velocity; a SMACNA junction coefficient, referenced to the upstream section, converts as C × (Vc/Vb)². Fire/smoke dampers and equipment from manufacturer data
Roughness: Ch. 21 Table 1 — medium smooth (aluminum, PVC, stainless) 0.00015 ft · average (galvanized) 0.0003 · medium rough (duct board, flex fully extended) 0.003 · faced liner 0.005. Compressed flex: the fully extended loss × PDCF = 1 + 0.58 Kc e−0.126 D, Eq. (22)
Air density: standard-atmosphere pressure at elevation, corrected to the entered temperature; pv and friction both scale with ρ
Fan selection: each run gives the total pressure of its index path; the fan’s external static pressure is that total less the fan outlet velocity pressure (Eq. 17). Where one fan serves more than one run (e.g. a single AHU fan handling supply and return), add those runs. Include a system-effect allowance per AMCA 201 where the fan inlet or outlet connection is poor.
Fan power: air power 0.000157 × cfm × in. wg, shaft power = air power ÷ fan efficiency, motor input = shaft power plus a 3% belt loss, ÷ motor efficiency (Fundamentals Ch. 18, Heat Gain from Fans); the motor is the smallest standard size at or above the shaft power plus drive loss. Fan heat ΔT = Δp ÷ (ρ cp η), S&E Ch. 21 Eq. (1), with the fan efficiency alone for a motor outside the airstream and fan, drive and motor efficiencies together inside it. Fan laws 1a–1c (S&E Ch. 21 Table 2) for the same fan: airflow ∝ speed, pressure ∝ speed², power ∝ speed³; fan speed = motor speed × motor sheave ÷ fan sheave on pitch diameters.
Limitations. Tee and wye coefficients depend strongly on the branch-to-main flow and area ratios; the fixed values here are mid-range estimates and can be off by a factor of two at a single fitting — enter the DFDB value as an override for takeoffs on the index run. Losses are summed as total pressure; fan static pressure equals that total less the fan outlet velocity pressure.